Plan Review Details - Permit 23040943
Plan Review Stops For Permit 23040943
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-19 Cont ID  
Sent By cthroop Date 2023-04-19 Time 14:37 Rev Time 0.00
Received By cthroop Date 2023-04-19 Time 14:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-18 Cont ID  
Sent By cthroop Date 2023-04-18 Time 13:05 Rev Time 0.00
Received By cthroop Date 2023-04-18 Time 12:16 Sent To  
Notes
2023-04-18 13:08:081ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
  
 1. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY
 LOCATION OF WORK.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE
 SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE AND INCLUDED BOUNDRY LINE SURVEY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-19 Cont ID  
Sent By pleduc Date 2023-04-19 Time   Rev Time 0.00
Received By pleduc Date 2023-04-19 Time 15:41 Sent To  
Notes
2023-04-19 15:42:17FIRE COMMENT:
  
 THIS PERMIT APPROVAL DOES NOT INCLUDE THE TENTS
 ON THE BARGES.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-04-18 Cont ID  
Sent By pleduc Date 2023-04-18 Time   Rev Time 0.00
Received By pleduc Date 2023-04-18 Time 10:43 Sent To  
Notes
2023-04-18 10:46:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO SITE PLAN PROVIDED INDICATING THE SIZE,
 LOCATION AND EXITING OF EACH PROPOSED TENT.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A SITE PLAN.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-18 Cont ID  
Sent By cthroop Date 2023-04-18 Time 13:08 Rev Time 0.00
Received By cthroop Date 2023-04-17 Time 16:15 Sent To  
Notes
***NONE***