Plan Review Details - Permit 23040885
Plan Review Stops For Permit 23040885
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-05-09 Cont ID  
Sent By jgomez Date 2023-05-09 Time 13:34 Rev Time 0.00
Received By jgomez Date 2023-05-09 Time 11:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-05-08 Cont ID  
Sent By jgomez Date 2023-05-08 Time 13:49 Rev Time 0.00
Received By jgomez Date 2023-05-08 Time 09:04 Sent To  
Notes
2023-05-08 13:49:51RESIDENTIAL (R2) THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23040885
 300 S AUSTRALIAN AVE # 1119
  
 1- OK.
 2- OK.
 3- OK.
  
 ORIGINAL COMMENT:
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES (IF ANY) AS REQUIRED BY SEC. 109.3
 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS
 OR PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN
 PROFESSIONAL FEES (IF ANY).
  
 RESPONSE:
 VALUE WAS UPDATED TO $6, 120. OWES $92.64.
  
 5)NOTICE OF COMMENCEMENT
 - NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
  
 6- FLOORING SOUND INSULATION MATERIAL:
  
 PREVIOUS COMMENT:
 (B)PROFLEX MSC-90 COPY OF THE SOUND TRANSMISSION CLASS
 (STC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR
 NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR.
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
 NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB.
 SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS.
  
 RESPONSE:
 THERE ARE TWO DIFFERENT TESTS SUBMITTED FOR LV200
 UNDERLAYMENT. ONE IS FOR 12MM LAMINATED WOOD AND THE
 OTHER ONE IS FOR 4MM LUXURY VINYL PLANK. NONE OF THESE
 TESTS MATCH PROPOSED FINISH FLOORING. CONTRACTOR
 SUBMITTED SPECIFICATIONS FOR JESSAMINE OAK 7MM
 LAMINATED WOOD FLOORING. NEED TO PROVIDE TEST FOR 7MM
 THAT MATCHES PROPOSED INSTALLATION.
 NOTE:
 CONTRACTOR ALSO SUBMITTED TEST FOR PROFLEX SUPER SIM 90
 UNDERLAYMENT ON A 6 INCH CONCRETE SLAB. THIS TEST
 CANNOT BE USED BECAUSE THIS TEST IS FOR TILE
 INSTALLATION NOT FOR LAMINATED FLOORING AS SPECIFIED BY
 THE CONTRACTOR.
  
 PREVIOUS COMMENT:
 (C)PROFLEX MSC-90 COPY OF THE IMPACT INSULATION CLASS
 (IIC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR
 NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR.
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
 NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB.
 SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS.
  
 RESPONSE:
 THERE ARE TWO DIFFERENT TESTS SUBMITTED FOR LV200
 UNDERLAYMENT. ONE IS FOR 12MM LAMINATED WOOD AND THE
 OTHER ONE IS FOR 4MM LUXURY VINYL PLANK. NONE OF THESE
 TESTS MATCH PROPOSED FINISH FLOORING. CONTRACTOR
 SUBMITTED SPECIFICATIONS FOR JESSAMINE OAK 7MM
 LAMINATED WOOD FLOORING. NEED TO PROVIDE TEST FOR 7MM
 THAT MATCHES PROPOSED INSTALLATION.
 NOTE:
 CONTRACTOR ALSO SUBMITTED TEST FOR PROFLEX SUPER SIM 90
 UNDERLAYMENT ON A 6 INCH CONCRETE SLAB. THIS TEST
 CANNOT BE USED BECAUSE THIS TEST IS FOR TILE
 INSTALLATION NOT FOR LAMINATED FLOORING AS SPECIFIED BY
 THE CONTRACTOR.
  
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION
 (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED
 FLOOR FINISH.
 NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH
 OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT
 SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT).
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-05 Cont ID  
Sent By jgomez Date 2023-05-05 Time 09:49 Rev Time 0.00
Received By jgomez Date 2023-05-05 Time 09:08 Sent To  
Notes
2023-05-05 09:49:48RESIDENTIAL (R2) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23040885
 300 S AUSTRALIAN AVE # 1119
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- FINISH FLOOR MATERIAL TO BE INSTALLED IS NOT CLEAR.
 PERMIT APPLICATION STATES " REMOVE CARPETS AND REPLACE
 WITH VINYL FLOORING". CONTRACTOR UPLOADED
 SPECIFICATIONS FOR LAMINATED WOOD FLOORS. CONTRACTOR TO
 REVISE SCOPE OF WORK ON PERMIT APPLICATION TO MATCH
 SPECIFICATIONS SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 FINISH FLOORING TO BE INSTALLED NOT SPECIFIED.
  
 ORIGINAL COMMENT:
 3- CONTRACTOR UPLOADED SPECIFICATIONS FOR LAMINATED
 PLANKS WALL MOUNTING . PROVIDE FLOOR PLAN SHOWING AREAS
 TO HAVE LAMINATED WALL PLANKS AND PROVIDE DETAILS
 SHOWING WALLS AREAS TO BE COVERED. FULL WALL, PARTIAL
 WALL, ETC.? SPECIFY FLOOR AREA OF EACH ROOM. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE.
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES (IF ANY) AS REQUIRED BY SEC. 109.3
 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS
 OR PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN
 PROFESSIONAL FEES (IF ANY).
  
 RESPONSE:
 ESTIMATE SUBMITTED IS TOO LOW.
  
 ORIGINAL COMMENT:
 5- FLOORING SOUND INSULATION MATERIAL:
 (A)PROFLEX SUPER SIM-90 COPY OF THE FLAME SPREAD INDEX
 AND SMOKE DEVELOPED INDEX TEST SUBMITTED IS FOR TILE
 INSTALLATION. CONTRACTOR NEEDS TO SUBMIT COPY OF TEST
 FOR LAMINATED WOOD FLOOR. (NOTE: UNDERLAYMENT PRODUCT
 TO MATCH UNDERLAYMENT USED ON REQUIRED TESTS BELOW).
 SEC. 720.1 AND 720.2 OF FBC 7TH EDITION (2020).
  
 (B)PROFLEX MSC-90 COPY OF THE SOUND TRANSMISSION CLASS
 (STC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR
 NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR.
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
 NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB.
 SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS.
  
 (C)PROFLEX MSC-90 COPY OF THE IMPACT INSULATION CLASS
 (IIC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR
 NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR.
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
 NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB.
 SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS.
  
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION
 (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED
 FLOOR FINISH.
 NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH
 OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT
 SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT).
  
 RESPONSE:
 NOT ADDRESSED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-02 Cont ID  
Sent By jgomez Date 2023-05-03 Time 18:01 Rev Time 0.00
Received By jgomez Date 2023-05-02 Time 18:01 Sent To  
Notes
2023-05-02 18:04:55RESIDENTIAL (R2)BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23040885
 300 S AUSTRALIAN AVE # 1119
  
 1- PROVIDE FLOOR PLAN SHOWING AREAS TO HAVE NEW
 FLOORING. AND, SPECIFY FLOOR AREA OF EACH ROOM. SEC.
 107.2.1 CITY AMENDMENTS.
  
 2- FINISH FLOOR MATERIAL TO BE INSTALLED IS NOT CLEAR.
 PERMIT APPLICATION STATES " REMOVE CARPETS AND REPLACE
 WITH VINYL FLOORING". CONTRACTOR UPLOADED
 SPECIFICATIONS FOR LAMINATED WOOD FLOORS. CONTRACTOR TO
 REVISE SCOPE OF WORK ON PERMIT APPLICATION TO MATCH
 SPECIFICATIONS SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- CONTRACTOR UPLOADED SPECIFICATIONS FOR LAMINATED
 PLANKS WALL MOUNTING . PROVIDE FLOOR PLAN SHOWING AREAS
 TO HAVE LAMINATED WALL PLANKS AND PROVIDE DETAILS
 SHOWING WALLS AREAS TO BE COVERED. FULL WALL, PARTIAL
 WALL, ETC.? SPECIFY FLOOR AREA OF EACH ROOM. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES (IF ANY) AS REQUIRED BY SEC. 109.3
 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS
 OR PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN
 PROFESSIONAL FEES (IF ANY).
  
 5- FLOORING SOUND INSULATION MATERIAL:
 (A)PROFLEX SUPER SIM-90 COPY OF THE FLAME SPREAD INDEX
 AND SMOKE DEVELOPED INDEX TEST SUBMITTED IS FOR TILE
 INSTALLATION. CONTRACTOR NEEDS TO SUBMIT COPY OF TEST
 FOR LAMINATED WOOD FLOOR. (NOTE: UNDERLAYMENT PRODUCT
 TO MATCH UNDERLAYMENT USED ON REQUIRED TESTS BELOW).
 SEC. 720.1 AND 720.2 OF FBC 7TH EDITION (2020).
  
 (B)PROFLEX MSC-90 COPY OF THE SOUND TRANSMISSION CLASS
 (STC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR
 NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR.
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
 NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB.
 SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS.
  
 (C)PROFLEX MSC-90 COPY OF THE IMPACT INSULATION CLASS
 (IIC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR
 NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR.
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
 NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB.
 SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS.
  
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION
 (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED
 FLOOR FINISH.
 NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH
 OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT
 SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT).
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-08 Cont ID  
Sent By pleduc Date 2023-05-08 Time   Rev Time 0.00
Received By pleduc Date 2023-05-08 Time 14:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-19 Cont ID  
Sent By cwalker Date 2023-04-19 Time   Rev Time  
Received By cwalker Date 2023-04-19 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-09 Cont ID  
Sent By jgomez Date 2023-05-09 Time 13:38 Rev Time 0.00
Received By jgomez Date 2023-05-09 Time 11:01 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-09 Cont ID  
Sent By lmarchan Date 2023-05-09 Time 10:26 Rev Time 0.00
Received By lmarchan Date 2023-05-05 Time 09:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-02 Cont ID  
Sent By jgomez Date 2023-05-03 Time 18:05 Rev Time 0.00
Received By jgomez Date 2023-04-18 Time 11:34 Sent To  
Notes
***NONE***