Plan Review Details - Permit 23040797
Plan Review Stops For Permit 23040797
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-21 Cont ID  
Sent By hmoser Date 2023-06-21 Time 13:54 Rev Time 0.00
Received By hmoser Date 2023-06-09 Time 08:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-01 Cont ID  
Sent By medwards Date 2023-05-01 Time 10:19 Rev Time 0.00
Received By medwards Date 2023-04-21 Time 13:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-06-21 Cont ID  
Sent By hmoser Date 2023-06-21 Time 13:51 Rev Time 0.00
Received By hmoser Date 2023-06-21 Time 10:02 Sent To  
Notes
2023-06-21 13:51:35PLAN DENIED
 1) PROVIDE A PLAN SHOWING THE GENERATOR AND EXHAUST.
 PER SECTION 501.3.1 #2.
 2) REFER TO SECTION 510.9 DUCT CONSTRUCTION #1
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-05-01 Cont ID  
Sent By medwards Date 2023-05-01 Time 10:18 Rev Time 0.00
Received By medwards Date 2023-05-01 Time 10:18 Sent To  
Notes
2023-05-01 10:18:531ST REVIEW FMC
 PERMIT: 23040797
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A COMPLETE SUBMITTAL FOR THIS GENERATOR
 INCLUDING THE TYPE OF FUEL AND ANY PIPING THAT WILL BE
 USED TO BRING THE FUEL FROM THE FUEL TRUCK TO THE
 GENERATOR TANK. INCLUDE THE TANK AND THE FUEL FILL
 STATION INFORMATION. THIS INFORMATION SHOULD ALSO
 INCLUDE THE GENERATOR MUFFLER WITH A DETAIL DRAWING
 SHOWING THE INSTALLATION OF THE EXHAUST TERMINATION.
 FBC 107.3.5
  
 2) THE APARTMENT BESIDE OF THIS GENERATOR ROOM SHOWS 2
 WINDOWS IN THE BEDROOM WHICH IS NEXT TO THE GENERATOR
 EXHAUST LOCATION. PLEASE SHOW THAT THESE WINDOWS ARE
 NOT OPERABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status N Date 2023-04-13 Cont ID  
Sent By aoliver Date 2023-04-13 Time 16:45 Rev Time 0.00
Received By aoliver Date 2023-04-13 Time 16:45 Sent To  
Notes
2023-04-13 16:45:38PRIVATE PROVIDER INSPECTIONS ONLY - REVIEW UNDER MASTER
 21100002

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-21 Cont ID  
Sent By hmoser Date 2023-06-21 Time 13:54 Rev Time 0.00
Received By hmoser Date 2023-06-21 Time 13:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-05-01 Cont ID  
Sent By medwards Date 2023-05-01 Time 10:19 Rev Time 0.00
Received By medwards Date 2023-05-01 Time 10:19 Sent To  
Notes
***NONE***