| 2023-04-18 16:31:55 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II/INSPECTOR |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A |
| | DEMO PERMIT PER FLORIDA BUILDING |
| | CODE, BUILDING 3303: |
| | |
| | 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC) |
| | RELEASE OF SERVICE CONFIRMATION |
| | 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS) |
| | RELEASE OF SERVICE CONFIRMATION |
| | 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER |
| | DEPARTMENT, REQUEST FOR METER PULL, ON |
| | THEIR FORM "DEMOLITION APPLICATION" |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | WATERDOWN METHOD: |
| | IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED |
| | INFPRMATION OF THE WATER TRUCK SUCH AS: THE |
| | GALLON CAPACITY OF THE WATER TANK AND A LETTER |
| | INCLUDING A STATEMENT THAT THE WATER |
| | USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY |
| | AND WILL BE ON-SITE AT ALL TIMES |
| | DURING DEMOLITION. |
| | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, |
| | THEN A PARTIAL RELEASE WILL BE NOTED |
| | ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS |
| | SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE |
| | SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE |
| | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY |
| | THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE |
| | COMPLETED "DEMOLITION APPLICATION" FORM TO |
| | 561-822-2183. |
| | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT |
| | APPLICATION TO BUILDING DIVISION); |
| | SCHEDULE A FINAL PLUMBING #703. |
| | 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST |
| | CONTROL COMPANY STATING THAT |
| | DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED |
| | FOR RODENTS. |
| | 6. COMPLETE THE DEMO DEBRIS FORM: HTTP://WPB.ORG/DEPART |
| | MENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FORMS |
| | IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR |
| | THE FORM TO [email protected]. |
| | 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN. |
| | |
| | |