| 2023-04-14 11:16:12 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23040706 |
| | 4/14/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SURVEY APPEARS TO SHOW THE PE LINE RUNNING |
| | UNDERNEATH THE BUILDING WHICH IS PROHIBITED REGARDLESS |
| | OF THE PIPING BEING RUN IN A CONDUIT- SEE SEC. |
| | G2415.17.1 FBC RES. PLEASE NOTE CSST PIPING RATED FOR |
| | UNDERGROUND INSTALLATION IS ALLOWED AND IS USED |
| | FREQUENTLY UNDER THE BUILDING. |
| | |
| | 2) GAS RISER: APPROVED GAS PLAN UNDER PERMITS 15040343 |
| | AND 15120040 SHOW A 180,000 BTU TANKLESS WATER HEATER |
| | SUPPLIED BY A ??-INCH GALVANIZED LINE. IS THIS WATER |
| | HEATER STILL IN USE, REMOVED OR RELOCATED? |
| | |
| | A) I WAS UNABLE TO LOCATE A PERMIT FOR THE FIREPLACE. |
| | PLEASE PROVIDE COMBUSTION AIR CALCULATIONS AND A |
| | VENTING DIAGRAM- SECS. G2407.1, G2427.1 FBC RES. IF |
| | USING THE STANDARD INDOOR AIR METHOD FOR COMBUSTION, |
| | THE CALCULATION I 50 CU.FT. PER 1000 BTU- SEC. |
| | G2407.5.1 FBC RES. THE VENT DIAGRAM SHALL SHOW THE TYPE |
| | AND SIZE OF VENT FLUE, VENT RUN LENGTH AND TERMINATION |
| | LOCATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |