Plan Review Details - Permit 23040476
Plan Review Stops For Permit 23040476
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-04-18 Cont ID  
Sent By cpuell Date 2023-04-18 Time 15:38 Rev Time 0.00
Received By cpuell Date 2023-04-18 Time 15:38 Sent To  
Notes
2023-04-18 15:39:25ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-05-03 Cont ID  
Sent By ccole Date 2023-05-03 Time 09:26 Rev Time 0.00
Received By ccole Date 2023-05-03 Time 09:26 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-04-19 Cont ID  
Sent By lbond Date 2023-04-19 Time 12:05 Rev Time 0.00
Received By lbond Date 2023-04-19 Time 12:05 Sent To  
Notes
2023-04-19 12:07:01BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23040476
  
 REVIEWED: 4/19/2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENT:
  
 ASBESTOS REVIEW:
  
 FAILED PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-04-19 Cont ID  
Sent By lbond Date 2023-04-19 Time 13:30 Rev Time 0.00
Received By lbond Date 2023-04-19 Time 13:30 Sent To  
Notes
2023-04-19 13:34:51BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23040476
  
 REVIEWED: MARCH 9, 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
 FBC ACCESSIBITILY
  
 COMMENTS: PASSED
 PROVISO:
  
 SHEET A-0.1 DRINKING FOUNTAINS UPDATE PROVIDED : 1
 (HI-LOW)
  
 SHEET A-1.0: ADA CHANGING ROOM 107 DOOR SHOULD SWING
 OUT, DOOR SWING NOT TO ENCROACH INTO THE 5FT RADIUS
 CIRCLE CLEAR SPACE-SHOW SEAT LOCATION AS WELL. UPDATE
 ON SHEET A-1.1A AS WELL
  
 MAKE SURE THAT EXISTING LAVATORY AND FIXTURES AS PER
 SHEET A-1.1B ARE WELL COORDINATED WITH PLUMBING SHEETS.
  
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-02 Cont ID  
Sent By rperdomo Date 2023-05-02 Time 16:16 Rev Time 0.00
Received By rperdomo Date 2023-05-02 Time 16:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-04-21 Cont ID  
Sent By rperdomo Date 2023-04-21 Time 11:52 Rev Time 0.00
Received By rperdomo Date 2023-04-21 Time 11:18 Sent To  
Notes
2023-04-21 11:52:26FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE INFORMATION OF THE FOLLOWING EXISTING
 FEEDERS:
 A. FROM THE 208/120V 400AS/400AF DISCONNECT TO THE
 EXIST. PANEL A
 B. FROM EXIST. PANEL A TO EXIST. PANEL B
 FBC 107.3.5.3
  
 NOTE: LOW VOLTAGE NEEDS A SEPARATE PERMIT APPLICATION
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-20 Cont ID  
Sent By pleduc Date 2023-04-20 Time   Rev Time 0.00
Received By pleduc Date 2023-04-19 Time 09:32 Sent To  
Notes
2023-04-19 09:59:02FIRE PROVISO:
  
  
 1) THERE IS AN INDICATION OF EXIT ACCESS PASSING
 THROUGH A STOREOOM.
  
 PER NFPA 101 CH 36
  
 36.2.5.11 EXIT ACCESS IN CLASS A AND CLASS B MERCANTILE
 OCCUPANCIES
 THAT ARE PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1), AND
 EXIT ACCESS IN ALL
 CLASS C MERCANTILE OCCUPANCIES, SHALL BE PERMITTED TO
 PASS THROUGH
 STOREROOMS, PROVIDED THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
  
 (1) NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE
 PROVIDED THROUGH
 THE STOREROOM.
  
 (2) THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING.
  
 (3) THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT
 LESS THAN 44 IN.
 (1120 MM) WIDE.
  
 (4) THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE
 DEFINED, DIRECT,
 AND CONTINUOUSLY MAINTAINED IN AN UNOBSTRUCTED
 CONDITION.
  
 A DELINEATED LINED PATH SHALL BE PLACED/TAPED/PAINTED
 ON THE FLOOR TO HELP
 ENSURE THE EXIT PATH IS MAINTAINED AND UNOBSTRUCTED.
  
  
 2) ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AND
 EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2023-05-03 Time   Rev Time 0.00
Received By lmarchan Date 2023-04-26 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-23 Cont ID  
Sent By lmarchan Date 2023-04-23 Time 07:14 Rev Time 0.00
Received By lmarchan Date 2023-04-18 Time 12:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-04-27 Cont ID  
Sent By ccole Date 2023-04-27 Time 08:18 Rev Time 0.00
Received By ccole Date 2023-04-27 Time 07:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-19 Cont ID  
Sent By ccole Date 2023-04-19 Time 10:56 Rev Time 0.00
Received By ccole Date 2023-04-19 Time 09:53 Sent To  
Notes
2023-04-19 11:00:301ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23040476
 4/19/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1.0: PLEASE ADD THE NEW SERVICE SINK AND THE
 MEN???S NEW ACCESSIBLE LAVATORY SINK AND FAUCET TO THE
 FIXTURE SCHEDULE- SECS. 404.1 422.1 FBC P.
  
 2) P-1.0: PROVIDE A DETAIL SHOWING THE LAV SINK RIM
 HEIGHT, AND KNEE AND TOES CLEARANCES- SEC. 606.2 &
 606.3 FBC ACC.
  
 3) P-1.0: SHOW THE DRINKING FOUNTAIN SPOUT HEIGHTS IN
 THE DETAIL PER SECS. 602.4 & 602.7 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-03 Cont ID  
Sent By ccole Date 2023-05-03 Time 09:26 Rev Time 0.00
Received By ccole Date 2023-05-03 Time 09:23 Sent To  
Notes
2023-04-27 08:44:11PLUMBING PLANS PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-04-19 Cont ID  
Sent By lbond Date 2023-04-19 Time 12:04 Rev Time 0.00
Received By lbond Date 2023-04-19 Time 12:04 Sent To  
Notes
2023-04-19 11:01:21PLUMBING PLANS PASSED.