Plan Review Details - Permit 23040456
Plan Review Stops For Permit 23040456
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2023-04-20 Cont ID  
Sent By lbond Date 2023-04-20 Time 15:59 Rev Time 0.00
Received By lbond Date 2023-04-20 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-04-20 Cont ID  
Sent By lbond Date 2023-04-20 Time 16:05 Rev Time 0.00
Received By lbond Date 2023-04-20 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-15 Cont ID  
Sent By jleahy Date 2023-05-15 Time 11:29 Rev Time 0.00
Received By jleahy Date 2023-05-15 Time 10:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-12 Cont ID  
Sent By   Date 2023-04-12 Time   Rev Time 0.00
Received By jcclark Date 2023-04-12 Time 14:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-23 Cont ID  
Sent By rwbrown Date 2023-06-23 Time 15:11 Rev Time 0.00
Received By rwbrown Date 2023-06-21 Time 15:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-19 Cont ID  
Sent By hmoser Date 2023-05-19 Time 14:29 Rev Time 0.00
Received By hmoser Date 2023-04-11 Time 16:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-05-19 Cont ID  
Sent By hmoser Date 2023-05-19 Time 14:28 Rev Time 0.00
Received By hmoser Date 2023-05-19 Time 14:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-06-23 Cont ID  
Sent By rwbrown Date 2023-06-23 Time 15:08 Rev Time 0.00
Received By rwbrown Date 2023-06-23 Time 15:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-05-08 Cont ID  
Sent By rwbrown Date 2023-05-08 Time 07:17 Rev Time 0.00
Received By rwbrown Date 2023-05-08 Time 07:17 Sent To  
Notes
2023-05-08 07:24:361ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 1003.3.1 - IT APPEARS THAT A GREASE TRAP IS
 REQUIRED. PLEASE DETAIL AND UPDATE THE RISER TO SHOW
 ALL FIXTURES THAT WILL HAVE F.O.G. WASTE WILL DISCHARGE
 INTO AN INTERCEPTOR.
  
 2. 2020 FPC 1002.1 - THE "HUB DRAIN" AT THE FRONT OF
 THE DISPLAY COUNTER CANNOT DISCHARGE INTO THE RISER OF
 THE NEARBY FLOOR DRAIN. EACH FIXTURE MUST BE SEPARATELY
 TRAPPED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-23 Cont ID  
Sent By rwbrown Date 2023-06-23 Time 15:11 Rev Time 0.00
Received By rwbrown Date 2023-06-23 Time 15:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-04-20 Cont ID  
Sent By lbond Date 2023-04-20 Time 15:53 Rev Time 0.00
Received By lbond Date 2023-04-20 Time 15:53 Sent To  
Notes
***NONE***