| 2023-04-21 17:25:30 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23040449 |
| | 5904 N FLAGLER DR |
| | |
| | 1-THIS STRUCTURE IS GOING TO BE BUILT IN A AE FLOOD |
| | ZONE WITH THE BASE FLOOD BFE: 6 FEET BASED ON NAVD |
| | 1988. |
| | CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2) |
| | FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC. |
| | 18-284 CITY ORDINANCE NO. 4729-17). |
| | NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY THE PROPOSED |
| | FINISH FLOOR ELEVATION IN ALL FLOOR PLANS. (NOTE: |
| | COORDINATE WITH CIVIL DRAWING C-1 AND ELECTRICAL AND |
| | PLANS). |
| | DURING THE PERMITTING/CONSTRUCTION OF THIS STRUCTURE |
| | THREE DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE |
| | REQUIRED (SEC. 107.3.5.1.1 CITY AMENDMENTS): |
| | A) CONSTRUCTION DRAWINGS. |
| | B) BUILDING UNDER CONSTRUCTION. |
| | C) FINISHED CONSTRUCTION. |
| | |
| | NOTE: |
| | NEED TO PROVIDE THE CONSTRUCTION DRAWINGS ELEVATION |
| | CERTIFICATE AND SURVEY SHOWING THE ELEVATIONS NOW FOR |
| | REVIEW. |
| | |
| | 2- IF THE PROPOSED FINISHED ELEVATION SPECIFIED ON ITEM |
| | #1 ABOVE IS BELOW THE DESIGN FLOOD ELEVATION OF 8 FT AS |
| | REQUIRED BY ITEM #1, THEN DESIGNER OF RECORD NEEDS TO |
| | PROVIDE COMPLETE INFORMATION FOR THE DESIGN OF THE |
| | FLOOD VENT OPENINGS SHOWING COMPLIANCE WITH SEC. 2.7 |
| | ASCE 24-14. |
| | |
| | 3- DESIGN CRITERIA ON SHEET 1 OF 1: |
| | A)ENGINEER TO REVISE THE BUILDING EXPOSURE. ACCORDING |
| | TO SEC. 1609.4 FBC-BUILDING, THIS BUILDING-IS LOCATED |
| | IN EXPOSURE "D" NOT "C". |
| | |
| | B)ENGINEER TO SPECIFY THE HEIGHT OF THE STRUCTURE. SEC. |
| | 1609.1 FBC-BUILDING. |
| | MEAN ROOF HEIGHT: N/A IS INCORRECT. OR ENGINEER TO |
| | PROVIDE ENGINEERING ANALYSIS SHOWING WHY THE HEIGHT IS |
| | NOT REQUIRED. SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | C)ENGINEER TO SPECIFY THE DOORS DESIGN PRESSURES |
| | (COMPONENTS & CLADDING). |
| | SEC. 1609.1 FBC-BUILDING. SEC. 107.2.1.2 CITY |
| | AMENDMENTS. |
| | |
| | 4- PRODUCT APPROVALS. F.A.C. 61G20.3.001: |
| | A)DOOR PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. NEED |
| | TO PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL REPORT, |
| | INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT |
| | CORRESPONDS TO THE DRAWINGS SUBMITTED. FAC 61G20.3.001. |
| | NOTE: THE FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE |
| | IT SHOWS IF PRODUCT IS APPROVED AND CURRENT CODE IN |
| | EFFECT. CHAPTER 553 F.S. |
| | NOTE: THERE ARE MANY DOORS IN THIS PRODUCT APPROVAL. |
| | CLERLY MARK WHICH DOOR IS GOING TO BE INSTALLED. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | B)PROVIDE PRODUCT APPROVAL FOR FLOOD VENTS IS THEY ARE |
| | SPECIFIED AS "ENGINEERED OPENINGS" ON ITEM #2 ABOVE. |
| | |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 6-DIGITAL SIGNATURE: |
| | A) STRUCTURAL SHEET 1 OF 1 HAVE A COPY OF THE |
| | ENGINEER'S SEAL AND SIGNATURE. |
| | DRAWING NEEDS TO HAVE THE ORIGINAL SEAL/SIGNATURE OF |
| | THE ENGINEER OF RECORD AS REQUIRED BY SEC. 61G15-23.001 |
| | FAC AND CHAPTER 471 F.S. WHEN SUBMITTING |
| | PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| | NOTE: THIS IS AN ELECTRONIC SUBMITTAL. SUBMIT |
| | PLANS/DOCUMENTS WITH ENGINEER'S VERIFIABLE DIGITAL |
| | SIGNATURE. |
| | |
| | ENGINEERS |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | B) CIVIL SHEET C-1: |
| | ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. THE "TEXT BOX LANGUAGE" MUST BE |
| | IDENTICAL TO THE EXAMPLES PUBLISHED BY FBPE. SEE FBPE.O |
| | RG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/ AND |
| | REVISE AS REQUIRED TO MATCH WHEN A DIGITALLY CREATED |
| | SEAL IS NOT USED. |
| | NOTE: BASED ON THE TEXT LOCATED WITHIN THE TEXT BOX IT |
| | IS NOT CLEAR IF THIS IS A DIGITALLY OR ELECTRONICALLY |
| | SIGNED DOCUMENT. THE TEXT READS "THIS ITEM HAS BEEN |
| | DIGITALLY SIGNED AND SEALED USING A SHA-1 |
| | AUTHENTICATION CODE. IF USING SHA-1 AUTHENTICATION |
| | CODE, THEN IT IS ELECTRONICALLY SIGNED NOT DIGITALLY. |
| | REVISE AS REQUIRED. |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/ AND REVISE AS REQUIRED TO MATCH. |
| | |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 61G15-23.005 PROCEDURES FOR ELECTRONICALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | C) ELECTRICAL SHEET E1: (SIGNATURE REVIEW ONLY): |
| | ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. THE "TEXT BOX LANGUAGE" MUST BE |
| | IDENTICAL TO THE EXAMPLES PUBLISHED BY FBPE. SEE FBPE |
| | .ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/ |
| | AND REVISE AS REQUIRED TO MATCH. |
| | NOTE: BASED ON THE TEXT LOCATED WITHIN THE TEXT BOX IT |
| | IS NOT CLEAR IF THIS IS A DIGITALLY OR ELECTRONICALLY |
| | SIGNED DOCUMENT. THE TEXT READS "THIS ITEM HAS BEEN |
| | DIGITALLY SIGNED AND SEALED USING A SHA-1 |
| | AUTHENTICATION CODE. IF USING SHA-1 AUTHENTICATION |
| | CODE, THEN IT IS ELECTRONICALLY SIGNED NOT DIGITALLY. |
| | REVISE AS REQUIRED. ALSO, THE TEXT BOX CANNOT BE A PART |
| | OF THE ELECTRONIC SIGNATURE ITSELF. SEE FBPE |
| | .ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/ |
| | AND REVISE AS REQUIRED TO MATCH. |
| | |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 61G15-23.005 PROCEDURES FOR ELECTRONICALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |