| 2023-04-24 11:21:40 | ELECTRIC REVIEW FAILED |
| | |
| | 1) IT APPEARS THIS IS A REMOTE STRUCTURE. PLEASE DETAIL |
| | HOW THE ELECTRIC FEEDING THIS STRUCTURE IS IN |
| | COMPLIANCE WITH NEC 225.30, NUMBER OF SUPPLIES.IF AN |
| | ELECTRIC PANEL IS LOCATED IN THE REMOTE STRUCTURE |
| | PLEASE DETAIL THE REQUIRE GROUNDING ELECTRODE SYSTEM AS |
| | REQUIRED PER NEC 250.32 |
| | |
| | A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE |
| | FEEDER OR BRANCH CIRCUIT |
| | |
| | |
| | 2) PLEASE LOCATE ALL ELECTRICAL EQUIPMENT ON FLOOR |
| | PLAN, I.E. AIR HANDLER/AIR CONDENSER/ DISCONNECTS, |
| | WATER HEATERS, ELECTRIC PANEL, ELECTRIC METER, ENSURE |
| | CLEARANCES AS REQUIRED. PLEASE INDICATE AND DISTINGUISH |
| | BETWEEN NEW AND EXISTING EQUIPMENT NEC 110.26 FBC 107.2 |
| | |
| | 3) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM DETAILING |
| | ALL ELECTRICAL EQUIPMENT, CONDUIT, CONDUCTOR AND |
| | OVERCURRENT PROTECTION SIZES. NEC 215.5 NEC 240.4 FBC |
| | 107.2 |
| | |
| | 4) PLEASE PROVIDE AN ELECTRIC LOAD CALCULATION FOR ALL |
| | ELECTRIC LOADS SERVED. NEC 220.40 OR NEC 220.80 |
| | |
| | 5) PLEASE INDICATE USE OF SPACE. WILL THIS SPACE BE |
| | USED AS A SLEEPING AREA? THIS SPACE MAY REQUIRE SMOKE |
| | ALARMS AS REQUIRED PER FBC R 314 |
| | |
| | 6) PLEASE DETAIL COMPLIANCE WITH NEC 210.8 AND NEC |
| | 210.12 FOR GROUND FAULT AND ARC FAULT PROTECTION. |
| | |
| | 7) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AS |
| | REQUIRED PER NEC 210.52(E) |
| | |
| | 8) PLEASE DETAIL THE REQUIRED OUTDOOR LIGHTING OUTLETS |
| | AS REQUIRED PER NEC 210.70(A)(2)(2) |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |