| 2023-05-24 10:43:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS INFORMATION REGARDING THE UNDERLAYMENT BUT, |
| | THERE IS NO INDICATION OF A MANUFACTURER'S |
| | SPECIFICATION SHEET NOR A PRODUCT NAME FOR THE PROPOSED |
| | WOOD FLOORING. |
| | |
| | WOOD FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT |
| | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE WOOD |
| | FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING |
| | THE FIRE BEHAVIOR RATING. |
| | |
| | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| | WOULD NOT BE REQUIRED. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ETC. |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF NEW WALLS, AS WELL AS, A |
| | STATEMENT OF NO FIRE SPRINKLER WORK. |
| | |
| | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR |
| | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR |
| | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED |
| | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. |
| | |
| | ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE |
| | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER |
| | SEPARATE PERMITS AND SHOP DRAWINGS. |
| | |
| | THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR |
| | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE |
| | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE A LETTER FROM A FIRE |
| | SPRINKLER CONTRACTOR OR PROVIDE A NOTE OF |
| | ACKNOWLEDGMENT TO PROVIDE FIRE SPRINKLER MODIFICATIONS |
| | UNDER SEPARATE PERMIT. |
| | |
| | |
| | |
| | |
| | |
| | 3) THERE ARE INDICATIONS OF BATHROOM WORK ON WALLS THAT |
| | MAY BE FIRE RATED TENANT OR CORRIDOR SEPARATIONS. |
| | |
| | ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED, |
| | ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION. |
| | |
| | PROVIDE A NOTE OF ACKNOWLEDGMENT |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |