| 2023-04-14 09:59:32 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23040217 |
| | 4/14/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: |
| | A) PLEASE IDENTIFY WHICH METER IS FOR 805 AND WHICH IS |
| | FOR 807- SEC. 107.2.1 WPB. |
| | B) SHOW THE TOTAL DEVELOPED LENGTH FOR EACH SYSTEM FROM |
| | THE METER TO THE WATER HEATER- SEC. 402.4.1 FBC FG. |
| | |
| | 2) PROVIDE A BASIC SITE PLAN SHOWING THE METER AND |
| | WATER HEATER LOCATIONS AND THE GAS PIPING RUNS- SEC. |
| | 107.3.5.1.5 WPB. |
| | |
| | 3) PROVIDE AN ELEVATION VIEW OF EACH WATER HEATER WITH |
| | CLEARANCE DISTANCE MEASUREMENTS FROM THE HEATER EXHAUST |
| | TO AIR INTAKES INTO THE BUILDING INCLUDING OPERABLE |
| | DOORS AND WINDOWS, MECHANICAL AIR INTAKES, SOFFIT |
| | VENTS- SEC. 503.8 FBC FG. |
| | |
| | 4) PLEASE NOTE COMPLETE GAS RISER DRAWINGS ARE REQUIRED |
| | WHICH SHOW ALL NEW AND EXISTING GAS APPLIANCES FOR EACH |
| | APARTMENT- SECS 401.3 & 401.4 FBC FG. PLEASE CONFIRM |
| | WITH A NOTE THAT THE WATER HEATERS ARE THE ONLY GAS |
| | APPLIANCES. |
| | |
| | 5) THE RESUBMITTED RISER AND PLAN SHALL BEAR THE |
| | PRINTED NAME AND SIGNATURE OF THE CONTRACTOR WHO |
| | PREPARED THE DRAWINGS- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |