Plan Review Details - Permit 23040153
Plan Review Stops For Permit 23040153
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-04-10 Cont ID  
Sent By cpuell Date 2023-04-10 Time 08:30 Rev Time 0.00
Received By cpuell Date 2023-04-10 Time 08:30 Sent To  
Notes
2023-04-10 08:31:05REROOF FOR THE WHOLE BUILDING ENCOMPASSING UNITS A AND
 B.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-05-02 Cont ID  
Sent By jbrooks Date 2023-05-02 Time 13:43 Rev Time 0.00
Received By jbrooks Date 2023-05-02 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-20 Cont ID  
Sent By jbrooks Date 2023-04-20 Time 14:33 Rev Time 0.00
Received By jbrooks Date 2023-04-20 Time 14:06 Sent To  
Notes
2023-04-20 14:33:32JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED FORM PB-O-131/ATTACHMENT B
 IS A PALM BEACH COUNTY BUILDING DEPARTMENT DOCUMENT AND
 IS NOT APPROVED FOR USE AS A SUBSTITUTE FOR SIGNED AND
 SEALED ENHANCED NAILING CALCULATIONS BY THE CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT THE AUTHORITY OF
 JURISDICTION. GENERAL LIMITATION #7 IS SPECIFICALLY
 REFERRED TO IN THIS NOA. SUBMIT FASTENER DENSITY
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT,
 OR REGISTERED ROOF CONSULTANT.
 2. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT
 LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 150.
 SUBMITTED MIAMI-DADE COUNTY NOA 22-0706.09 COVERS
 MULTIPLE ROOFING SYSTEMS TYPES A (1) THROUGH E (8).
 SELECT SYSTEM TYPE TO BE USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS. GENERAL LIMITATION #7 IS
 SPECIFICALLY REFERRED TO IN THIS NOA. SUBMIT FASTENER
 DENSITY CALCULATIONS PREPARED, SIGNED AND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT, OR REGISTERED ROOF CONSULTANT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By jbrooks Date 2023-04-19 Time 14:36 Rev Time 0.00
Received By jbrooks Date 2023-04-19 Time 14:09 Sent To  
Notes
2023-04-19 14:37:00JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED MIAMI-DADE COUNTY NOA 22-0706.09 COVERS
 MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(8).
 SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED
 CALCULATIONS MAY BE REQUIRED. PLEASE NOTE THIS IS AN
 EXPOSURE CATEGORY C AREA.
 2. SUBMITTED MIAMI-DADE COUNTY NOA 22-1221.05 COVERS
 MULTIPLE PRODUCTS & APPROVED ASSEMBLIES: SYSTEMS E(1)
 THROUGH E(4). SELECT SYSTEM TO BE USED. ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-07 Cont ID  
Sent By jbrooks Date 2023-04-07 Time 08:57 Rev Time 0.00
Received By jbrooks Date 2023-04-07 Time 07:34 Sent To  
Notes
2023-04-07 08:57:33JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 18-1109.03 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT
 SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 2. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA
 17-1004.09 HAS EXPIRED AND IS NO LONGER VALID. PLEASE
 PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA???S FOR THE PROPOSED FLAT ROOFING SYSTEM
 TO BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 3. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-02 Cont ID  
Sent By jbrooks Date 2023-05-02 Time 13:43 Rev Time 0.00
Received By jbrooks Date 2023-05-01 Time 12:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-20 Cont ID  
Sent By jbrooks Date 2023-04-20 Time 14:34 Rev Time 0.00
Received By jbrooks Date 2023-04-20 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-19 Cont ID  
Sent By jbrooks Date 2023-04-19 Time 14:37 Rev Time 0.00
Received By jbrooks Date 2023-04-11 Time 11:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-10 Cont ID  
Sent By cpuell Date 2023-04-10 Time 08:31 Rev Time 0.00
Received By cpuell Date 2023-04-06 Time 09:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-05-02 Cont ID  
Sent By ccole Date 2023-05-02 Time 12:25 Rev Time 0.00
Received By ccole Date 2023-05-02 Time 12:25 Sent To  
Notes
2023-05-02 12:26:50REVIEW OF SIGNATURE AND SEAL ON PAPER DOC APPROVED AND
 DOC ROUTED TO STORAGE/CLC