Plan Review Details - Permit 23040005
Plan Review Stops For Permit 23040005
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-19 Cont ID  
Sent By pleduc Date 2023-05-17 Time   Rev Time 0.00
Received By pleduc Date 2023-05-17 Time 13:08 Sent To  
Notes
2023-05-17 13:17:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF GATES WITHIN THE PROPOSED
 FENCE.
  
 THERE ARE NO INDICATIONS OF LOCKS/LATCHES/HARDWARE FOR
 THESE GATES.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
  
 PLEASE PROIVIDE DETAILS, INCLUDING IF WILL BE FREE
 EGRESS.
  
  
  
 2) THERE APPEARS TO BE INDICATIONS OF A CABLE RAIL WITH
 THIS PERMIT.
  
 IS THIS CORRECT?
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 IF SO PLEASE PROVIDE DETAILS OR PROVIDE CLARIFICATIONS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-22 Cont ID  
Sent By aoliver Date 2023-05-22 Time 13:10 Rev Time 0.00
Received By aoliver Date 2023-04-04 Time 14:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-05-16 Cont ID  
Sent By eschneid Date 2023-05-16 Time 15:48 Rev Time 0.25
Received By eschneid Date 2023-05-16 Time 15:48 Sent To  
Notes
2023-05-16 16:07:43FAILED
  
 1) THE SITE PLAN NEEDS TO CLEARLY SHOW WHERE THE FULL
 LENGTH OF THE FENCE IS BEING INSTALLED.
  
 2) PROVIDE A DETAIL SHOWING THE HEIGHT AND MATERIAL OF
 THE PROPOSED FENCE.
  
 3) PROVIDE VERIFICTAION THAT THE TOP OF THE FENCE WILL
 NOT EXCEED SIX (6) FEET IN HEIGHT WHEN MEASURED FROM
 THE EXTIRIOR SIDE ADJACENT TO A NEIGHBORING PROPERTY.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]