| 2023-04-14 15:22:15 | 1ST REVIEW FMC |
| | PERMIT: 23031984 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) WHAT WAS THE USE OF SPACE WHERE THIS HOOD IS TO BE |
| | INSTALLED? FBC 107.3.5 |
| | |
| | 2) PROVIDE THE CALCULATIONS FOR THE EXISTING HVAC |
| | SYSTEM SHOWING IT IS SIZED LARGE ENOUGH FOR MAKE-UP AIR |
| | FOR THIS HOOD. FMC 508.1.1 |
| | |
| | 3) PROVIDE THE AIR BALANCE SCHEDULE OR DIAGRAM FOR THIS |
| | FACILITY. FMC 508.1.2 |
| | |
| | 4) PROVIDE SPEC SHEETS ON THE COOKING EQUIPMENT THIS |
| | MUST SHOW THE LISTING AND LABELING FOR EACH PIECE OF |
| | EQUIPMENT. FMC 917.1 |
| | |
| | 5) PROVIDE THE HEAT SOURCE FOR THE SMOKER OVEN ALONG |
| | WITH THE SPECS. FOR THIS SMOKER OVEN. FBC 107.3.5 |
| | |
| | 6) SHEET H-2 NOTE STATES THE GREASE DUCT USED WILL |
| | PROVIDE REDUCED CLEARANCE TO COMBUSTIBLES. WHAT IS THE |
| | CLEARANCE REDUCTION? |
| | |
| | 7) PROVIDE A SITE PLAN SHOWING THE PROPERTY LINES FOR |
| | THIS PROPERTY. FMC 506.3.13.3 |
| | |
| | 8) PROVIDE SPECS FOR THE MAKE UP AIR FAN INCLUDING |
| | CFMS. FMC 508.1 |
| | |
| | 9) SHEET H-1: THE EQUIPMENT SCHEDULE HAS ITEM NUMBERS |
| | BUT THESE NUMBERS ARE NOT ON THE DRAWING WHICH WOULD |
| | SHOW THEIR LOCATION. ADD THE LOCATION OF THESE PIECES |
| | OF EQUIPMENT TO THE DRAWING. FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |