| Plan Review Stops For Permit 23031983 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-07-20 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-20 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-20 |
Time |
11:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-07-03 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-03 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-03 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2023-07-03 09:53:13 | DIFFER WINDOWS AND DOORS | | | DIFFER ROOF AND TREILLIS | | | DIFFER POOL | | | UNDER SEPERATE PERMIT | | | | | | THIS BUILDING APPROVAL IS FOR INTERIOR ALTERATIONS ONLY | | | AS PER APPLICATION. | | | | | | PLEASE UPDATE VALUE ON APPLICATION TO 25,000 NOT 250000 | | | FOR THIS PHASE | | | THANK YOU |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-04-06 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-06 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-06 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2023-04-06 15:04:53 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23031983 | | | | | | REVIEWED: 4/6, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | AS PER SECTION 107.2.1 | | | PLEASE PROVIDE EXISTING FLOOR PLAN AND ELEVATIONS, | | | PROPOSED NEW ELEVATION INCLUDING PROPOSED AWNING | | | STRUCTURE IN PLAN AND ELEVATION, | | | CURRENT PROPERTY SURVEY WITH SETBACKS. | | | PRODUCT APPROVAL FOR ALL NEW WINDOWS AND DOORS, WIND | | | LOAD CALCUATION TABLE FOR THE SPECIF ZONE WHERE THE | | | PROPORTY IS LOCATED. IF THE ROOF STRUCTURE HAS FABRIC | | | ATTACHED TO IT PLEASE PROVIDE PRODUCT APPROVAL. | | | IF ANY TRADES MODIFICATION ARE INCLUDED AS PART OF THIS | | | ALTERATION PLEASE PROVIDE ALL APPROPRIATE DOCUMENTATION | | | REQUIRED BY EACH REVIEWER. | | | | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-07-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-07-26 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-07-26 |
Time |
14:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-06-30 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-06-30 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2023-06-30 11:33:09 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. REVIEW ELECTRICAL RISER PRESENTED FOR CORRECT | | | GROUNDED ELECTRICAL CONDUCTOR (GEC) PER NEC TABLE | | | 250(C)(1) AND INDICATE THE MINIMUM SIZES FOR THE | | | EQUIPMENT GROUNDING CONDUCTORS PER NEC TABLE 250.122. | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN P. PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-04-07 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-04-07 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-04-07 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2023-04-07 13:36:09 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE ELECTRICAL SCOPE OF WORK. FBC 107.2.1, | | | 107.3.5 | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-07-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-07-26 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-07-18 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-07-14 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2023-07-14 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2023-06-28 |
Time |
08:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-04-18 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-04-18 |
Time |
14:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-07-14 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2023-07-14 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2023-07-14 |
Time |
07:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-04-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-06 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-06 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2023-04-06 17:30:21 | OUR RECORDS INDICATE NO PERMITTED MECHANICAL SYSTEM FOR | | | THIS ADDRESS. PROVIDE A COMPLETE SCOPE OF WORK FOR THE | | | MECHANICAL SYSTEM INCLUDING THE ENERGY CALCULATIONS AND | | | MECANICAL EQUIPMENT SIZING CALCULATIONS AND A | | | MECHANICAL DRAWING. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-06-29 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-06-29 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-06-29 |
Time |
07:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-04-06 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-04-06 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-04-06 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2023-04-06 09:47:41 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.2.1 - PLEASE SHOW AN EXISTING | | | FLOOR PLAN ALONG WITH THE PROVIDED PROPOSED FLOOR PLAN | | | TO SHOW THE CHANGES BEING MADE. | | | | | | 2. 2017 WPB AMEND 107.3.5.3 (12) - IF THERE ARE ANY | | | CHANGES TO THE FLOOR PLAN AND LAYOUT OF THE PLUMBING | | | FIXTURES, YOU WILL NEED TO SUPPLY A RISER DIAGRAM FOR | | | THE DRAIN/WASTE/VENT SYSTEM FOR THE NEW CONNECTION | | | CONFIGURATION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2023-07-20 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-20 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-20 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2023-07-20 11:19:43 | DIFFERED UNDER SEPERATE PERMIT |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-07-03 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-03 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-03 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2023-07-03 09:57:41 | DIFFER UNDER SEPERATE PERMIT | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-07-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-07-26 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-07-20 |
Time |
11:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-07-03 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-03 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-03 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2023-07-03 09:37:46 | VERDIFIED DIGITALLY SIGNED SHEETS ARE IN THE SIGNATURE | | | FOLDER |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2023-04-06 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-06 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-06 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2023-04-06 15:07:57 | PALM BEACH COUNTY LICENSED CONTRACTOR SIGNED DOCUMENTS | | | REQUIRED WITH CONTACT INFORMATION IF ALTERATION MUST | | | INCLUDE THEM OR DIFFER TO SEPERATE PERMITS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-07-13 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-07-13 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-07-13 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
ASangele |
Date |
2023-04-18 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-04-18 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2023-04-18 14:47:39 | FAILED | | | 4/18/2023 | | | | | | PLEASE PROVIDE PROPERTY SURVEY WITH APPLICATION | | | | | | PLEASE PROVIDE ENGINEER SEALED PLANS OF WORK BEING | | | COMPLETED. | | | | | | | | | ALEXIS SANGELEER | | | PLANNER | | | [email protected] |
|
|