| Plan Review Stops For Permit 23031894 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2023-07-25 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-07-25 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-07-25 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2023-07-25 11:36:13 | PLANS AND APPLICATION FORM ARE STILL NOT MATCHING, | | | PLEASE CONTACT [email protected] OR CALL | | | 561-805-6659 TO DISCUSS ADDRESSING ISSUES. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2023-06-14 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-06-14 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-06-14 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2023-06-14 11:46:49 | APPLICATION LISTS 111 N OLIVE AVE AS THE ADDRESS AND | | | THE PLANS LIST 301 CLEMATIS ST UNITS 101 AND 102. | | | PLEASE CONTACT [email protected] OR CALL | | | 561-805-6659 TO DISCUSS ADDRESSING ISSUES. |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2023-07-24 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-24 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-24 |
Time |
09:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2023-04-25 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-25 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-25 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2023-04-25 14:49:19 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23031894 | | | | | | REVIEWED: 4.25.2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | ASBESTOS REVIEW: | | | FAILED PLAN REVIEW: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | | ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION | | | -RENOVATION.HTML | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-07-24 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-24 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-24 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2023-07-24 09:37:22 | ****CORRECTIONS**** | | | | | | LOUIS BOND | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 301, PROVIDE THE FLORIDA PRODUCT APPROVAL | | | COVER SHEET FOR THE DOOR, WINDOWS. A COMPLETE PRODUCT | | | APPROVAL SHOULD INCLUDE: | | | | | | THE COVER SHEET WHICH SHOWS THE APPROVAL NUMBER, CODE | | | VERSION, AND STATUS | | | EVALUATION REPORT | | | INSTALLATION INSTRUCTIONS | | | | | | FOR SOME PRODUCT APPROVALS, THE EVALUATION REPORT AND | | | INSTALLATION INSTRUCTIONS ARE ONE DOCUMENT. IT IS | | | PREFERABLE THAT YOU UPLOAD THE COVER PAGE, EVALUATION | | | REPORT, AND INSTALLATION INSTRUCTIONS AS ONE PDF. | | | | | | THESE DOCUMENTS ARE AVAILABLE AT FLORIDABUILDING.ORG. | | | | | | 2. PROVIDE WIND LOAD ON WALL, DESIGN PRESSURE, ROOF | | | HEIGHT, ZONE A, B, C OR D FOR NEW SGD AND LOUVERS | | | | | | ANY QUESTIONS OR CONCERNS: | | | | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-04-25 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-25 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-25 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2023-04-25 15:04:52 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23031894 | | | | | | REVIEWED: 4.25.2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | AS PER SECTION 107.2.1 | | | | | | SHEET A-10.0 | | | | | | PROVIDE FBC PRODUCT APPROVAL FOR NEW IMPACT CLERESTORY | | | WINDOW | | | PROVIDE FPC PRODUCT APPROVAL FOR NEW IMPACT RESISTANT | | | LOUVER | | | | | | SHEET A-12 | | | | | | PROVIDE FBC PRODUCT APPROVAL FOR NEW SGD | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-04-24 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-04-24 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2023-04-24 12:55:57 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW | | | | | | 1. SEPARATE PERMIT REQUIRED FOR LOW VOLTAGE. | | | | | | END OF COMMENTS | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2023-04-25 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
2023-04-25 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
2023-04-25 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2023-04-25 13:37:16 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23031894 | | | | | | REVIEWED: 4.25.2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENT: | | | | | | ASBESTOS REVIEW: | | | | | | FAILED PLAN REVIEW: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | | ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION | | | -RENOVATION.HTML | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-07-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-07-21 |
Time |
10:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-04-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-04-14 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2023-04-17 13:16:33 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET 012 A-8.0 - THERE IS AN INDICATION OF A | | | DIAGONAL LINE SPANNING ACROSS THE DINING AREA THAT HAS | | | A DIMENSION IN THE CENTER. | | | | | | THAT DIMENSION IS UNREADABLE AND NEEDS TO BE CLARIFIED | | | IN ORDER TO ENSURE THE TWO FRONT EXITS ARE SEPARATED | | | PER NFPA 101, CH 7, MEANS OF EGRESS. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A CLEAR | | | DIMENSION AND THAT THE FRONT EXIT DOOR SEPARATION | | | DIMENSION MEETS THE REQUIRMENTS. | | | | | | | | | 2) SHEET 012 A-8.0 - THE MENS RESTROOM DOOR OPENS OUT | | | INTO A EXIT ACCESS CORRIDOR. | | | | | | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL | | | LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF | | | AN AISLE, A CORRIDOR, | | | A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF | | | THE FOLLOWING | | | CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING | | | BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF | | | 7.2.1.4.3.2. | | | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL | | | NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED | | | WIDTH OF AN AISLE, | | | A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR | | | LEAF IS EQUIPPED | | | WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT | | | REQUIRED BY THE PROVISIONS | | | OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS | | | TRAVEL. | | | | | | PLEASE REVIEW AND PROVIDE DIMENSIONS WITHIN THE | | | REQUIREMENT OR CORRECT THE SWING OF THE DOOR. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-07-21 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-07-21 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2023-07-21 14:31:48 | 2ND REVIEW FBC-2020 FUEL GAS | | | PERMIT- 23031894 | | | 7/21/2023 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #1B AND #2 | | | FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL | | | NOTES FOR CLARIFICATION. | | | | | | 1) FAILED. SHEET P2 GAS RISER- SEC. 107.3.5.1.5 WPB. | | | | | | B) PROVIDE THE SIZES OF THE SUPPLY PIPES FROM THE | | | MANIFOLDS TO THE WATER HEATERS AND COOKING APPLIANCES. | | | BASED ON TABLE 402.4(2) FBC FG 1-INCH PIPES ARE | | | REQUIRED FOR THE WATER HEATERS, AND 3/4-INCH PIPES ARE | | | REQUIRED AT THE OVEN AND THE HOT PLATE. | | | | | | REVISION PERMIT #22120309 SHOWS A 2 PSI SYSTEM WITH A | | | TOTAL LENGTH OF 245 FT. AT THE CAPPED POINT ADJACENT TO | | | THE NEW RESTAURANT SPACE. THERE IS NO LOW-PRESSURE | | | REGULATOR(S) SHOWN ON THE NEW RISER EITHER AT THE | | | COOKING LINE OR AT EACH APPLIANCE- SEC. 410.2 FBC FG. | | | PLEASE SHOW THE REGULATOR(S) AND SHOW THE VENT LINE RUN | | | AND TERMINATION LOCATION UNLESS THE REGULATOR(S) IS/ARE | | | THE VENT-LIMITING TYPE(S). | | | | | | 2) FAILED. P2: PROVIDE COMBUSTION AIR CALCULATIONS FOR | | | THE COOKING APPLIANCES AND INDICATE HOW THE AIR WILL BE | | | SUPPLIED- SEC. 304.1 FBC FG. | | | | | | 2ND REQUEST FOR COMBUSTION AIR CALCULATIONS FOR THE | | | COOKING APPLIANCES. PLEASE NOTE THAT MAKEUP AIR FOR THE | | | EXHAUST HOOD CANNOT BE USED TO SUPPLY COMBUSTION AIR- | | | SEC. 304.9.1 FBC FG. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-19 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-19 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2023-04-19 16:06:07 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 23031894 | | | 4/19/2023 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P2 GAS RISER- SEC. 107.3.5.1.5 WPB. | | | | | | A) PROVIDE THE PIPE SIZE AND LENGTH OF THE BRANCH LINE | | | SUPPLYING THE WATER HEATERS. | | | | | | B) PROVIDE THE SIZES OF THE SUPPLY PIPES FROM THE | | | MANIFOLDS TO THE WATER HEATERS AND COOKING APPLIANCES. | | | BASED ON TABLE 402.4(2) FBC FG 1-INCH PIPES ARE | | | REQUIRED FOR THE WATER HEATERS, AND 3/4-INCH PIPES ARE | | | REQUIRED AT THE OVEN AND THE HOT PLATE. | | | | | | 2) P2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | WATER HEATER AND COOKING APPLIANCES AND INDICATE HOW | | | THE AIR WILL BE SUPPLIED- SEC. 304.1 FBC FG. | | | | | | 3) P2: PROVIDE A COMPLETE VENTING DIAGRAM FOR THE WATER | | | HEATERS BASED ON MANUFACTURER'S SPECIFICATIONS (SEC. | | | 624.1) AND SECS. 503.6- 503.8 FBC FG. SHOW THE TYPE AND | | | SIZE OF VENT FLUES, VENT FLUE RUN LENGTHS AND | | | TERMINATION LOCATIONS WITH REQUIRED CLEARANCES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-07-20 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-26 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-13 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-26 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-26 |
Time |
06:34 |
Sent To |
|
|
| Notes |
| 2023-04-26 06:34:30 | 1ST REVIEW FMC | | | PERMIT: 23031894 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE COVER SHEET INDICATES THIS TO BE A PROPOSED | | | OCCUPANCY OF A-2. WHAT IS THE CURRENT OCCUPANCY OF THIS | | | SPACE? | | | | | | 2) PROVIDE A MECHANICAL DEMO PLAN FOR THIS PROJECT. FBC | | | 107.3.5 | | | | | | 3) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT | | | THE KITCHEN HOODS AND ALL GREASE DUCT WILL REQUIRE A | | | SEPARATE PERMIT APPLICATION AND A SEPARATE REVIEW AS IT | | | WILL NOT BE REVIEWED UNDER THIS PERMIT. | | | 4) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT | | | REFRIGERATION EQUIPMENT WILL REQUIRE A SEPARATE PERMIT | | | APPLICATION AND A SEPARATE REVIEW AS IT WILL NOT BE | | | REVIEWED UNDER THIS PERMIT. | | | 5) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS PROJECT. FEC C403.2.1 | | | | | | 6) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH SPACE | | | IN THIS BUILDOUT ACCORDING TO THE OCCUPANCY | | | CLASSIFICATION OF EACH SPACE AND THE OCCUPANT DENSITY | | | FROM FMC TABLE 403.3.1.1 | | | | | | 7) SHOW THE VENTILATION AIR INTAKES ARE 10 FEET FROM | | | THE LOT LINE AND STREET. FMC 401.3 AND 401.4 | | | | | | 8) VERIFY THAT THE RETURN AIR INTAKES IN THE KITCHEN | | | ARE A MINIMUM OF 10 FEET FROM THE COOKING APPLIANCES. | | | FMC 601.5 NUMBER 7. | | | | | | 9) SHOW THAT THE MECHANICAL SYSTEM WILL BE SIZED FOR | | | THE LOAD OF THE WALK-IN COOLER AND FREEZER CONDENSING | | | UNITS INSTALLED INSIDE THE KITCHEN CONDITIONED AREA. | | | FEC C403.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-07-21 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-07-21 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2023-07-21 14:16:04 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT-23031894 | | | 7/21/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #8 & 10 | | | FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL | | | NOTES FOR FURTHER CLARIFICATION. | | | | | | 8) FAILED. P2 & P4: REFER TO SEC. 607.1.1 FBC P | | | TEMPERATURE LIMITING MEANS. THE THERMOSTAT CONTROLS ON | | | THE WATER HEATERS CANNOT BE THE LIMITING DEVICES FOR | | | HOT WATER DELIVERY. PLEASE PROVIDE A MASTER | | | THERMOSTATIC MIXING VALVE AND DETAIL THE PIPING | | | CONNECTIONS. | | | | | | PLEASE PROVIDE A MASTER THERMOSTATIC MIXING VALVE AT | | | THE WATER HEATERS. | | | | | | 10) FAILED. P2 & P4: REFER TO SEC. AND TABLE C404.5.1 | | | FBC ENERGY. THE PLANS SHOW THE 1/2-INCH HOT WATER | | | SUPPLY PIPES TO THE PUBLIC LAVATORIES ARE EXCEEDINGLY | | | THE 2FT. MAXIMUM ALLOWABLE LENGTHS FROM THE HOT WATER | | | SOURCES. | | | | | | THE HW RECIRCULATION LINES MUST BE LOOPED DOWN AND | | | CONNECT TO THE LAVATORY HW FIXTURE SUPPLY PIPES AT A | | | POINT WITHIN 2 FT. OF THE FIXTURE SUPPLY PIPE | | | TERMINATIONS AT THE LAVS. | | | | | | NEW COMMENT. | | | | | | 1) P-1 & P-4: PLEASE PROVIDE A FLOOR CLEANOUT (FCO) FOR | | | THE GREASE WASTE LINE INSIDE THE SPACE AT A POINT WHERE | | | IT WILL NOT EXCEED 100 FT. FROM THE CLEANOUT AT THE | | | GREASE INTERCEPTOR- SEC. 708.1.1 FBC P. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-19 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-19 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2023-04-19 15:42:34 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-23031894 | | | 4/19/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE F | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-8.0: IN ACCORDANCE WITH TABLE 403.1 FBC P, A | | | PUBLIC OCCUPANT LOAD OF 152 REQUIRES 2 MALE AND 2 | | | FEMALE WATER CLOSETS. THE PLANS SHOWS A DEFICIENCY OF | | | ONE MALE AND ONE FEMALE WATER CLOSET FOR PUBLIC USE. | | | PLEASE REVISE THE PLANS TO SHOW COMPLIANCE. | | | | | | 2) A-11.0: PLEASE SHOW THE CLEAR FLOOR SPACE DIMENSIONS | | | FOR THE WATER CLOSETS AND THE LAVATORIES- SECS. 604.3 & | | | 606.2 FBC ACC. | | | | | | 3) A-11.0: PLEASE SHOW THE CENTERLINES OF THE TOILET | | | PAPER DISPENSERS MEASURED FROM THE FRONTS OF THE WATER | | | CLOSETS- SEC. AND FIGURE 604.7 FBC ACC. | | | | | | 4) P-1: A PERMIT APPLICATION FOR THE GREASE INTERCEPTOR | | | IS REQUIRED TO BE SUBMITTED PRIOR TO THE MAIN PLUMBING | | | PLAN APPROVAL. YOU CAN SUBMIT AN APPLICATION TBD (TO BE | | | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY | | | EMAILING A COMPLETED PERMIT APPLICATION TO | | | [email protected]. YOU WILL RECEIVE INSTRUCTIONS | | | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND | | | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS | | | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES | | | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE | | | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL | | | ([email protected]) AND I WILL CHANGE THE REVIEW STATUS TO | | | PASS. | | | | | | 5) P-1: A COMPLETE REVIEW OF THE PLUMBING SYSTEMS | | | CANNOT BE COMPLETED WITHOUT NUMBERED OR LETTERED | | | PLUMBING FIXTURE AND EQUIPMENT SCHEDULES WITH | | | CORRESPONDING NUMBERS OR LETTERS ON THE PLANS- SEC. | | | 107.2.1 WPB. | | | | | | 6) P-1 & P4: THE PLAN AND RISER DRAWING APPEAR TO SHOW | | | DRAINAGE FROM HAND SINKS AND FLOOR SINKS BELOW ICE | | | MAKERS AND BINS DISCHARGING INTO THE GREASE WASTE LINE | | | WHICH IS NOT ALLOWED PER SEC. 1003.3.1 FBC P. | | | | | | 7) P1 & P4: PLEASE NOTE THE GREASE INTERCEPTOR PERMIT | | | 22060318 IS IN APPLICATION PHASE AND NO PLANS HAVE BEEN | | | SUBMITTED FOR REVIEW. GREASE INTERCEPTOR SUBMITTAL | | | REQUIREMENTS ARE AS FOLLOWS- | | | A) CIVIL PLAN SHOWING THE INTERCEPTOR, PIPING, AND | | | CLEANOUT LOCATIONS | | | B) EQUIPMENT SCHEDULE INDICATING THE MAKE AND MODEL AND | | | CAPACITY OF THE UNIT. | | | C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME | | | A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, | | | OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7 | | | FOR GRAVITY TYPES. | | | D) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND | | | SIZES OF INLETS, OUTLETS, CLEANOUTS, FLOW CONTROL | | | VENTS, AND SAMPLING PORTS. | | | E) MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP BY | | | THE ENGINEER OF RECORD- SECS.1003.3.5 OR 1003.3.7 FBC | | | P. | | | F) ACCESS LID SPECIFICATIONS INDICATING THE LIDS WILL | | | BE EQUIPPED WITH ACCESS RESTRICTORS AND WILL BE HEAVY | | | DUTY TRAFFIC RATED (WHERE REQUIRED). | | | | | | 8) P2 & P4: REFER TO SEC. 607.1.1 FBC P TEMPERATURE | | | LIMITING MEANS. THE THERMOSTAT CONTROLS ON THE WATER | | | HEATERS CANNOT BE THE LIMITING DEVICES FOR HOT WATER | | | DELIVERY. PLEASE PROVIDE A MASTER THERMOSTATIC MIXING | | | VALVE AND DETAIL THE PIPING CONNECTIONS. | | | | | | 9) P2 & P4: REFER TO SECS. 419.5 & 607.1.2 FBC P AND | | | INDICATE THE MEANS OF PROVIDING TEMPERED WATER DELIVERY | | | FROM THE PUBLIC LAVATORY SINKS. | | | | | | 10) P2 & P4: REFER TO SEC. AND TABLE C404.5.1 FBC | | | ENERGY. THE PLANS SHOW THE 1/2-INCH HOT WATER SUPPLY | | | PIPES TO THE WATER HEATERS ARE EXCEEDINGLY THE 2FT. | | | MAXIMUM ALLOWABLE LENGTHS FROM THE HOT WATER SOURCES. | | | IN ORDER TO CORRECT, THE RECIRCULATION LINES MUST BE | | | DROPPED DOWN AND CONNECT WITHIN 2 FT. OF THE HW SUPPLY | | | PIPE TERMINATIONS. | | | | | | 11) P2 & P4: SHOW THE LOCATIONS OF BACKFLOW PREVENTERS | | | FOR SUPPLY PIPES TO THE DISHWASHER AND OTHER FIXTURES | | | AND EQUIPMENT THAT COULD CAUSE CONTAMINATION OF THE | | | POTABLE WATER SUPPLY- SEC. 608.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-07-24 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-24 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-24 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-04-25 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-25 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-25 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
CIbaven |
Date |
2023-04-19 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
cibaven |
Date |
2023-04-19 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2023-04-19 12:17:05 | COMMENTS: | | | 1. PLEASE, CLEARLY MARK/LABEL PROPERTY LINE ON DRAWINGS | | | 2. REMOVE ALL OUTDOOR FURNITURE FROM DRAWINGS ON | | | SIDEWALKS THAT ARE NOT INCLUDED IN THIS PERMIT | | | APPLICATION, SUCH AS CHAIRS, TABLES, PLANTERS, | | | UMBRELLAS, ETC. A SEPARATE PERMIT IS REQUIRED FOR | | | SIDEWALK CAF?? SEATING. FOR MORE INFO, SEE WPB CODE OF | | | ORDINANCES, CHAPTER 78.- STREETS, SIDEWALKS AND PUBLIC | | | SPACES, ARTICLE X. | | | 3. A SEPARATE PERMIT IS REQUIRED FOR SIGNAGE, PLEASE | | | REMOVE SIGNS ON AWNINGS ON THIS SUBMITTAL. FOR MORE | | | INFORMATION ABOUT SIGN REGULATIONS GO TO CHAPTER 94.- | | | ZONING AND PLANNING REGULATIONS, SEC. 94-110. | | | | | | | | | CLAUDIA D. IBAVEN | | | CITY URBAN DESIGNER / ZONING AND PLANNING | | | [email protected] | | | 561-822-1402 | | | | | | |
|
|