| 2023-04-18 08:53:38 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 3RD REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | 1) ON PAGE 1 OF THE ROOFING PRODUCT APPROVAL THAT WAS |
| | SUBMITTED THE SYSTEMS THAT ARE SPECIFIED AT THE TOP OF |
| | THE PAGE ARE W-30 AND C-20. THE W-30 SYSTEM IS FOR WOOD |
| | ROOF DECKS AND THE C-30 IS FOR CONCRETE ROOF DECKS. THE |
| | DESIGN PRESSURE FOR THE W-30 WOOD DECK ON PAGE 10 HAS A |
| | MAXIMUM DESIGN PRESSURE OF -60 PSF. THIS DESIGN |
| | PRESSURE WILL NOT WORK FOR THE PERIMETER AND ROOF |
| | AREAS. YOU WILL HAVE TO SUBMIT DIGITALLY SIGNED |
| | ENHANCED FASTENING CALCULATIONS IF YOU WANT TO USE THAT |
| | SYSTEM. FBC-R301.2.1 |
| | |
| | 2) PLEASE SPECIFY ON THE ROOF DRAWING WHICH PART OF THE |
| | ROOF IS WOOD AND WHICH PART IS CONCRETE. FBC 107.2.1 |
| | |
| | 3) THE VALUATION ON THE PERMIT APPLICATION OF $7200.00 |
| | APPEARS TO BE TOO LOW. SUBMIT AN ITEMIZED COST |
| | BREAKDOWN FOR THIS ROOFING PROJECT INCLUDING ALL COSTS |
| | FOR MATERIALS, LABOR, COSTS AND OVERHEAD. BUILDING |
| | PERMIT VALUATION. FOR PERMITTING PURPOSES, VALUATION OF |
| | FBC 109.3 BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |