Plan Review Details - Permit 23031769
Plan Review Stops For Permit 23031769
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-05-25 Cont ID  
Sent By rmcphers Date 2023-05-25 Time 14:25 Rev Time 0.00
Received By rmcphers Date 2023-05-25 Time 14:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By rmcphers Date 2023-04-10 Time 14:55 Rev Time 0.00
Received By rmcphers Date 2023-04-10 Time 14:27 Sent To  
Notes
2023-04-10 14:54:19CREATING SHELL SUITES
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS ALS1.1 AND ALS1.2 - UNDER "CODE DATA" SUITE
 NUMBERS DO NOT MATCH FLOOR PLAN AND INCLUDE ONLY 3
 UNITS - PLEASE RE EVALUATE.
  
 2) DRAWINGS ALS1.1 AND ALS1.2 - UNDER "OCCUPANCY LOAD"
 THE OCCUPANT LOAD SHOULD MATCH THE INFO SHOWN UNDER
 "CODE DATA"
  
 3) DRAWING A-8.0.1 - DETAIL 6 - OR THE STRUCTURAL
 DRAWINGS - PLEASE SHOW THE EXTERIOR WALL BOTTOM AND TOP
 TRACK ATTACHMENTS, SHOW THE PLYWOOD ATTACHMENTS, SHOW
 THE DENS DECK ATTACHMENTS ETC. FBC WPB 107.2.1
  
 4) DRAWING A-8.0.1 - DETAIL 6 - PLEASE SHOW THE
 EXTERIOR WALL WATER RESISTIVE BARRIER - FBC 1404.2
 WATER-RESISTIVE BARRIER.
 NOT FEWER THAN ONE LAYER OF NO.15 ASPHALT FELT,
 COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR OTHER
 APPROVED MATERIALS, SHALL BE ATTACHED TO THE STUDS OR
 SHEATHING, WITH FLASHING AS DESCRIBED IN SECTION
 1405.4, IN SUCH A MANNER AS TO PROVIDE A CONTINUOUS
 WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR WALL
 VENEER.
  
 5) PLEASE SHOW THE EXTERIOR WINDOW/DOOR FLASHING PER -
 FBC 1405.4

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-04-13 Cont ID  
Sent By jleahy Date 2023-04-13 Time 17:35 Rev Time 0.00
Received By jleahy Date 2023-04-13 Time 16:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-23 Cont ID  
Sent By pleduc Date 2023-05-23 Time   Rev Time 0.00
Received By pleduc Date 2023-05-23 Time 14:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-06 Cont ID  
Sent By pleduc Date 2023-04-06 Time   Rev Time 0.00
Received By pleduc Date 2023-04-05 Time 10:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2023-04-10 Cont ID  
Sent By rwbrown Date 2023-04-10 Time 08:21 Rev Time 0.00
Received By rwbrown Date 2023-04-10 Time 08:21 Sent To  
Notes
2023-04-10 08:21:59RESULTS CHANGED TO PASSED - 5-18-23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-25 Cont ID  
Sent By rmcphers Date 2023-05-25 Time 14:25 Rev Time 0.00
Received By rmcphers Date 2023-05-22 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-09 Cont ID  
Sent By lmarchan Date 2023-05-09 Time 11:05 Rev Time 0.00
Received By lmarchan Date 2023-04-03 Time 08:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-04-18 Cont ID  
Sent By medwards Date 2023-04-18 Time 10:28 Rev Time 0.00
Received By medwards Date 2023-04-18 Time 10:28 Sent To  
Notes
2023-04-18 10:28:50SHELL ONLY

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-05-24 Cont ID  
Sent By rwbrown Date 2023-05-24 Time 12:17 Rev Time 0.00
Received By rwbrown Date 2023-05-24 Time 12:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By rwbrown Date 2023-04-10 Time 08:07 Rev Time 0.00
Received By rwbrown Date 2023-04-10 Time 08:07 Sent To  
Notes
2023-04-10 08:20:001ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 105.1/107.3 --THE GREASE TRAP
 REQUIRES A SEPARATE PERMIT THAT IS REQUIRED TO BE
 APPLIED FOR PRIOR TO ISSUANCE OF THE PRIMARY PERMIT.
 YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED)
 IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO
 [email protected]. AFTER YOU HAVE THE PERMIT
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
  
 2. 2020 FPC 708.1.1 AND 708.1.3 - DETAIL THE REQUIRED
 CLEANOUT AT INTERVALS NO MORE THAN 100 FEET ON THE
 BUILDING DRAINS AS WELL AS THE REQUIRED CLEANOUTS JUST
 OUTSIDE THE BUILDING AT THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER ON BOTH THE SANITARY AND
 THE GREASE WASTE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-24 Cont ID  
Sent By rwbrown Date 2023-05-24 Time 12:19 Rev Time 0.00
Received By rwbrown Date 2023-05-24 Time 12:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-04-10 Cont ID  
Sent By rmcphers Date 2023-04-10 Time 15:13 Rev Time 0.00
Received By rmcphers Date 2023-04-10 Time 15:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-05-09 Cont ID  
Sent By eschneid Date 2023-05-09 Time 09:39 Rev Time 0.75
Received By eschneid Date 2023-05-09 Time 09:38 Sent To  
Notes