Plan Review Details - Permit 23031646
Plan Review Stops For Permit 23031646
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-05-24 Cont ID  
Sent By jwitmer Date 2023-05-24 Time 16:37 Rev Time 0.00
Received By jwitmer Date 2023-05-24 Time 16:16 Sent To  
Notes
2023-05-24 16:37:38COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By jwitmer Date 2023-04-04 Time 07:26 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 17:29 Sent To  
Notes
2023-04-04 07:26:38COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-05-24 Cont ID  
Sent By jwitmer Date 2023-05-24 Time 16:37 Rev Time 0.00
Received By jwitmer Date 2023-05-24 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By jwitmer Date 2023-04-04 Time 07:27 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 17:29 Sent To  
Notes
2023-04-04 07:27:35WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031646
 ADD: 250 S AUSTRALIAN AVE # 1302
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 04TH/ 2023
 ACTION: DENIED
  
 1) SHEET A101 THE CONSTRUCTION FLOOR PLAN SHOWS A BREAK
 ROOM COUNTER AND SINK. THE PLANS LACK AN ACCESSIBILITY
 DETAIL IF THIS AN FRONT APPROACH OR SIDE APPROACH. 2020
 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED, SEE EXCEPTIONS ALSO, BUT
 SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE FLOOR PLAN.
  
 2) SHEET A-514 DETAIL 2 SHOWS A CUT SECTION THROUGH THE
 SINK AND CABINETRY AND DRAINPIPE NOT INSULATED. PLEASE
 REVIEW THE 2020 FBC-ACCESSIBILITY CODE SECTION 606.5
 EXPOSED PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES
 UNDER LAVATORIES AND SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED TO PROTECT AGAINST CONTACT.
  
 3) SHEET A-201 LOUNGE/ BREAK AREA DETAILS 8 & 9 SHOWS
 THE FRONT ELEVATION OF THE CABINETRY AND SINK, JUST
 ABOVE THE SINK IS A SHELF FOR A MICROWAVE. THE
 ELECTRICAL PANEL SCHEDULE CONFIRMS THERE IS TO BE A NEW
 MICROWAVE INSTALLED. THIS LOCATION IS TO HIGH FOR THE
 REACH RANGES AND OPERABLE PARTS. SEE THE 2020
 FBC-ACCESSIBILITY CODE SECTIONS:
 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 4) SHEET A-101 SHOWS THE RECEPTIONIST DESK AND DETAIL
 3/ A.202. THE FRONT & SIDE PANELS OF THE RECEPTIONIST
 DESK SHOW A HEIGHT OF 42 INCHES ABOVE THE FINISH FLOOR.
 THERE IS NO LOCATION PROVIDED FOR A WHEELCHAIR BOUND
 INDIVIDUAL TO DO ANY KIND OF PAPERWORK.
 4)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4)(B) 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE
 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 4)( C ) CHECK WRITING SURFACES. 2020 ACCESS. CODE
 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK
 WRITING SURFACES SHALL COMPLY WITH 902.3HEIGHT. THE
 TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-18 Cont ID  
Sent By rperdomo Date 2023-05-18 Time 14:28 Rev Time 0.00
Received By rperdomo Date 2023-05-18 Time 14:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-04-07 Cont ID  
Sent By rperdomo Date 2023-04-07 Time 15:29 Rev Time 0.00
Received By rperdomo Date 2023-04-07 Time 14:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By pleduc Date 2023-05-09 Time   Rev Time 0.00
Received By pleduc Date 2023-05-09 Time 10:02 Sent To  
Notes
2023-05-09 10:06:58FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-03-30 Cont ID  
Sent By cwalker Date 2023-03-30 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2023-03-30 11:37:27FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE
 DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (3) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED AND QUALIFIED CONTRACTORS UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 (4) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (5) ANY ACCESS CONTROL INSTALLATION WILL REQUIRE A
 SEPARATE PERMIT.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2023-05-24 Time   Rev Time 0.00
Received By amcgrego Date 2023-05-08 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-10 Cont ID  
Sent By cthroop Date 2023-04-10 Time 10:56 Rev Time 0.00
Received By cthroop Date 2023-03-29 Time 08:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 15:41 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 15:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-04-07 Cont ID  
Sent By medwards Date 2023-04-07 Time 15:25 Rev Time 0.00
Received By medwards Date 2023-04-07 Time 15:25 Sent To  
Notes
2023-04-07 15:26:42PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE IN THIS TENANT SPACE. FMC 403.3.1.1 AND TABLE
 403.3.1.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-05-11 Cont ID  
Sent By ccole Date 2023-05-11 Time 16:32 Rev Time 0.00
Received By ccole Date 2023-05-11 Time 16:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-07 Cont ID  
Sent By ccole Date 2023-04-07 Time 10:50 Rev Time 0.00
Received By ccole Date 2023-04-07 Time 09:12 Sent To  
Notes
2023-04-07 10:52:051ST REVIEW FBC-2020 PLUMBING
 PERMIT-23031646
 4/7/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLUMBING PLAN SHEETS P-001, P-102, P-201, P-501, &
 P-901 ARE NOT DIGITALLY SIGNED AND SEALED BY THE
 ENGINEER- FL. STATUTE 471.025 AND FAC SEC.
 61G15-23.005.
  
 2) SHEETS P-501 & P-901: PLEASE SHOW THE WATER HEATER
 LOCATION IN THE APPLIANCE DETAIL ON P-901, AND PROVIDE
 A THERMOSTATIC MIXING VALVE TO LIMIT THE HOT WATER
 TEMPERATURE DELIVERY TO THE SINK- SEC. 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-24 Cont ID  
Sent By jwitmer Date 2023-05-24 Time 16:39 Rev Time 0.00
Received By jwitmer Date 2023-05-24 Time 16:33 Sent To  
Notes
2023-05-09 15:42:38MECHANICAL DIGITAL SIGNATURES APPROVED ME.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By cthroop Date 2023-04-10 Time 10:55 Rev Time 0.00
Received By cthroop Date 2023-04-10 Time 10:52 Sent To  
Notes
2023-04-10 10:56:211ST SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: ALL PLAN PAGES ???
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
2023-04-07 15:29:43MECHANICAL DIGITAL SIGNATURES APPROVED ME
2023-04-07 10:21:28PLUMBING FAILED- NO DIG/SIGS ON SHEETS P-001, P-102,
 P-201, P-501, P-901.
2023-04-04 07:30:52ARCHITECTS SHEETS COULD NOT BE VERIFIED. J WITMER