Plan Review Details - Permit 23031599
Plan Review Stops For Permit 23031599
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-04-11 Cont ID  
Sent By jwitmer Date 2023-04-11 Time 10:37 Rev Time 0.00
Received By jwitmer Date 2023-04-11 Time 09:43 Sent To  
Notes
2023-04-11 10:37:13410 EVERNIA ST. BUILT IN 2004 NO ASBESTOS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 17:00 Rev Time 0.00
Received By jwitmer Date 2023-06-06 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-05-31 Cont ID  
Sent By shill Date 2023-05-31 Time 12:01 Rev Time 0.00
Received By shill Date 2023-05-31 Time 12:01 Sent To  
Notes
2023-05-31 12:05:01[email protected]
 561-805-6724
 UNABLE TO LOCATE FLAME SPREAD TEST FOR QUIETWALK.
 EITHER PROVIDE THE FLAME SPREAD TEST OR SELECT A
 PRODUCT WITH THE THREE TESTS REQUIRED.
 SEE PREVIOUS REVIEWS FOR CODE REFERENCES.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-08 Cont ID  
Sent By jwitmer Date 2023-05-08 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2023-05-08 Time 14:45 Sent To  
Notes
2023-05-08 15:15:33WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031599
 ADD: 410 EVERNIA ST. # 622
 CONT: GNEISS CORP.
 TEL: 561-797-5274
 E-MAIL: [email protected]
  
 1- 2) COMPLIED.
  
 3)SEMI COMPLIED. THE FLOOR PLAN SCOPE OF WORK NOTE # 3
 INDICATES PORCELAIN TILE IN KITCHEN, DINING ROOM AND
 LIVING ROOM AND NEW HARDWOOD FLOORING IN BEDROOMS 1 &
 2. NOTE # 4 STATES INSTALL PROFLEX SUPER SIM 90
 UNDERLAYMENT, PROFLEX SUPER SIM 90 HAS BEEN TEST FOR
 PORCELAIN TILE ONLY. SEPARATE TESTING REPORTS ARE
 REQUIRED FOR HARDWOOD FLOOR UNDERLAYMENT.
  
 NO TEST REPORTS WERE SUBMITTED FOR HARDWOOD FLOORS. THE
 CITY IS IN RECEIPT OF TEST REPORTS FOR PROFLEX LV-200
 WOOD LAMINATE FLOORING.
  
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
 3C) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 -PILL TEST (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-11 Cont ID  
Sent By jwitmer Date 2023-04-11 Time 10:35 Rev Time 0.00
Received By jwitmer Date 2023-04-11 Time 09:43 Sent To  
Notes
2023-04-11 10:35:35WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031599
 ADD: 410 EVERNIA ST. # 622
 CONT: GNEISS CORP.
 TEL: 561-797-5274
 E-MAIL: [email protected]
  
 1) THE VALUE IS LOW FOR THE WHOLE CONDO UNIT TO HAVE
 FLOOR INSTALLATION AND CABINETS, SAME LOCATION.
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 109.3 BUILDING PERMIT VALUATION. IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING OR ALTERATION APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDING
 OR ALTERATION THE TOTAL REPLACEMENT PURPOSES, VALUATION
 OF THE ALTERATION SHALL BE THE TOTAL REPLACEMENT VALUE
 TO INCLUDE THE DEMOLITION, DISPOSAL OF DEBRIS FLOORS
 AND CABINETRY, FLOOR FLASH PATCH, UNDERLAYMENT COST AND
 LABOR, THE FLOOR FINISH COST OF MATERIALS AND LABOR
 PLUS, OVERHEAD AND PROFIT AS WELL FOR THE CABINETRY .
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE FLOOR PLAN OF THE KITCHEN PROVIDES DIMENSIONS
 FOR ALL OF THE CABINETRY BUT NOT THE DISTANCE BETWEEN
 COUNTERTOPS FROM ONE SIDE TO THE OTHER. FAIR HOUSING
 GUIDELINES. FAIR HOUSING ACT DESIGN AND CONSTRUCTION
 REQUIREMENTS. FOR PURPOSES OF THIS SECTION, A COVERED
 MULTIFAMILY DWELLING SHALL BE DEEMED TO BE DESIGNED AND
 CONSTRUCTED FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13,
 1991, IF THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST
 BUILDING PERMIT OR RENEWAL THEREOF FOR THE COVERED
 MULTIFAMILY DWELLINGS IS ISSUED BY A STATE, COUNTY OR
 LOCAL GOVERNMENT ON OR BEFORE JANUARY 13, 1990.
 PAGES 7.7 & 7.8 OF THE FAIR HOUSING GUIDELINES BOOK
 SHOWS A MINIMUM OF 40 INCHES FROM THE FACE OF
 REFRIGERATOR, RANGE AND OR DISHWASHER TO THE OPPOSITE
 WALL OF CABINETRY.
  
 3) THE FLOOR PLAN SCOPE OF WORK NOTE 3 INDICATES
 PORCELAIN TILE IN KITCHEN, DINING ROOM AND LIVING ROOM
 AND NEW HARDWOOD FLOORING IN BEDROOMS 1 & 2. NO TEST
 REPORTS WERE SUBMITTED FOR HARDWOOD FLOORS. PROFLEX
 DOES HAVE TEST REPORTS FOR WOOD FLOORS LV200 LAMINATES.
  
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
 3C) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 -PILL TEST (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-06-02 Cont ID  
Sent By pleduc Date 2023-06-02 Time   Rev Time 0.00
Received By pleduc Date 2023-06-02 Time 09:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-12 Cont ID  
Sent By pleduc Date 2023-05-12 Time   Rev Time 0.00
Received By pleduc Date 2023-05-12 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-26 Cont ID  
Sent By pleduc Date 2023-04-26 Time   Rev Time 0.00
Received By pleduc Date 2023-04-26 Time 13:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By pleduc Date 2023-04-04 Time   Rev Time 0.00
Received By pleduc Date 2023-04-04 Time 16:00 Sent To  
Notes
2023-04-04 16:03:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT
 NAME FOR THE ACTUAL PROPOSED FLOORING.
  
 FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT ALL
 ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 NAME AND THE PRODUCT SPEC SHEETS INDICATING THE FIRE
 BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) THERE APPEARS TO BE INDOCATIONS OF THE KITCHEN WALL
 LAYOUT THAT MAY AFFECT THE FIRE SPRINKLER PROTECTION.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A
 NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN.
  
  
 2A) DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A
 NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2023-06-06 Time   Rev Time 0.00
Received By amcgrego Date 2023-06-01 Time 08:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-31 Cont ID  
Sent By shill Date 2023-05-31 Time 12:05 Rev Time 0.00
Received By shill Date 2023-05-11 Time 09:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2023-05-08 Time   Rev Time 0.00
Received By amcgrego Date 2023-04-21 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-04-11 Time   Rev Time 0.00
Received By amcgrego Date 2023-04-03 Time 13:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-04-11 Cont ID  
Sent By jwitmer Date 2023-04-11 Time 10:37 Rev Time 0.00
Received By jwitmer Date 2023-04-11 Time 09:43 Sent To  
Notes
***NONE***