| 2023-06-01 18:33:08 | RESIDENTIAL (R2)SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23031597 |
| | 2621 VILLAGE BLVD # 405 |
| | |
| | |
| | 2-FLOORING SOUND INSULATION MATERIAL: |
| | (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 AND 720.2 OF FBC |
| | 7TH EDITION (2020). |
| | |
| | RESPONSE: |
| | TEST REPORT SUBMITTED IS FOR PROFLEX SUPER SIM-90 TO BE |
| | USED WITH PORCELAIN TILE. THE PROPOSED FINISH FLOOR IS |
| | NOT TILE. NEED TO PROVIDE TEST WITH THE SAME FINISH |
| | FLOR THAT IS GOING TO BE INSTALLED. |
| | |
| | (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| | SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | NOTE: CONTRACTOR SUBMITTED SALES BROCHURE INFORMATION |
| | FOR 8MM THICK PARKAY MERCURY WPL LAMINATE FLOORING. |
| | NEED TO PROVIDE TEST FOR 8MM LAMINATE FLOORING ON A 6" |
| | CONCRETE SLAB AN NO ACOUSTICAL CEILING WHICH REFLECTS |
| | ACTUAL FLOORING CONDITIONS. |
| | |
| | (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| | SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | NOTE: CONTRACTOR SUBMITTED SALES BROCHURE INFORMATION |
| | FOR 8MM THICK PARKAY MERCURY WPL LAMINATE FLOORING. |
| | NEED TO PROVIDE TEST FOR 8MM LAMINATE FLOORING ON A 6" |
| | CONCRETE SLAB AN NO ACOUSTICAL CEILING WHICH REFLECTS |
| | ACTUAL FLOORING CONDITIONS. |
| | |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION |
| | (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED |
| | FLOOR FINISH. |
| | NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH |
| | OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT |
| | SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| | |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT). |
| | |
| | NOTE: |
| | SOUND INSULATION TEST FOR A CONCRETE SLAB WITH A |
| | SUSPENDED ACOUSTICAL CEILING WILL NOT BE APPROVED |
| | UNLESS APPLICANT PROVIDES PROOF OF ACOUSTICAL CEILING |
| | IN AREAS TO HAVE THE NEW FLOORING. |
| | |