Plan Review Details - Permit 23031581
Plan Review Stops For Permit 23031581
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-01 Cont ID  
Sent By rmcdouga Date 2023-06-01 Time 09:10 Rev Time 0.00
Received By rmcdouga Date 2023-06-01 Time 09:10 Sent To  
Notes
2023-06-01 09:21:29PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [DISTANCES TO PROPERTY LINES AND BUILDINGS WAS NOT
 SPECIFIED.] SUBMIT A SURVEY. SHOW THE LOCATION OF THE
 PROPOSED GENERATOR. SPECIFY THE DISTANCE TO PROPERTY
 LINES AND BUILDINGS. FBC AMENDMENTS 107.2.1
  
 2) [NOT RESOLVED.] THE GENERATOR EXHAUST IS REQUIRED TO
 BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING.
 R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 3) [NOT RESOLVED.] THE PROPOSED GENERATOR IS LOCATED IN
 A SPECIAL FLOOD HAZARD AREA. THE GENERATOR AND
 EQUIPMENT IS REQUIRED TO BE LOCATED AT OR ABOVE THE
 LIVING SPACE OF THE DWELLING. SHOW COMPLIANCE, FBC-
 R322.1.6
  
 4) SUBMIT A RESPONSE LETTER SPECIFYING HOW EACH OF THE
 REVIEW COMMENTS HAS BEEN ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-14 Cont ID  
Sent By rmcdouga Date 2023-04-14 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2023-04-14 Time 10:48 Sent To  
Notes
2023-04-14 11:42:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A SURVEY. SHOW THE LOCATION OF THE PROPOSED
 GENERATOR. SPECIFY THE DISTANCE TO PROPERTY LINES AND
 BUILDINGS. FBC AMENDMENTS 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 3) THE PROPOSED GENERATOR IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA. THE GENERATOR AND EQUIPMENT IS REQUIRED TO
 BE LOCATED AT OR ABOVE THE LIVING SPACE OF THE
 DWELLING. SHOW COMPLIANCE, FBC- R322.1.6
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-04-18 Cont ID  
Sent By fgiaquin Date 2023-04-18 Time 08:25 Rev Time 0.00
Received By fgiaquin Date 2023-04-17 Time 21:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-25 Time 14:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-14 Cont ID  
Sent By avolcy Date 2023-07-14 Time 09:28 Rev Time 0.00
Received By avolcy Date 2023-05-18 Time 17:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-01 Cont ID  
Sent By avolcy Date 2023-05-01 Time 08:14 Rev Time 0.00
Received By avolcy Date 2023-04-07 Time 11:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-01 Cont ID  
Sent By rmcdouga Date 2023-06-01 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2023-06-01 Time 09:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-04-14 Cont ID  
Sent By rmcdouga Date 2023-04-14 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2023-04-14 Time 10:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-07-14 Cont ID  
Sent By avolcy Date 2023-07-14 Time 09:28 Rev Time 0.00
Received By avolcy Date 2023-07-14 Time 09:28 Sent To  
Notes
2023-07-14 09:28:0607.14.2023 - FAILED
  
 PROVIDE SETBACKS FOR THE GENERATOR ON THE SURVEY.
  
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
 **** REVIEWD BY ****
 GAISHA (ANNE CLERISSE) VOLCY
 PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-05-01 Cont ID  
Sent By AVolcy Date 2023-05-01 Time 08:12 Rev Time 0.00
Received By avolcy Date 2023-05-01 Time 08:12 Sent To  
Notes
2023-05-01 08:14:4705.01.2023 - FAILED
  
 PROVIDE SURVEY WITH THE LOCATION OF THE PROPOSED
 GENERATOR AND SETBACKS.
  
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
 **** REVIEWD BY ****
 GAISHA (ANNE CLERISSE) VOLCY
 PLANNER
 [email protected]
  