Plan Review Details - Permit 23031578
Plan Review Stops For Permit 23031578
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-07-14 Cont ID  
Sent By cpuell Date 2023-07-14 Time 12:04 Rev Time 0.00
Received By cpuell Date 2023-07-14 Time 12:04 Sent To  
Notes
2023-07-14 12:06:21THE PLAN ADDRESSES LISTED AND THE APPLICATION FORM DOES
 NOT MATCH, IF THE SCOPE OF WORK IS FOR THE RESTRAUNT
 THEN THE ADDRESS WOULD BE 718 S DIXIE HWY IF IT IS FOR
 THE HOTEL THEN THE ADDRESS WOULD BE 380 TRINITY PLACE,
 PLEASE UPDATE THE PLANS OR APPLICATION FORM TO REFLECT
 THE CORRECT ADDRESS. [email protected] OR CALL
 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-08-15 Cont ID  
Sent By jwitmer Date 2023-08-15 Time 07:08 Rev Time 0.00
Received By jwitmer Date 2023-08-15 Time 06:41 Sent To  
Notes
2023-09-26 07:43:42PLEASE REVIEW FIRE COMMENTS AND SHOW COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-07-26 Cont ID  
Sent By jleahy Date 2023-07-26 Time 14:58 Rev Time 0.00
Received By jleahy Date 2023-07-26 Time 14:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-07-13 Cont ID  
Sent By pleduc Date 2023-07-13 Time   Rev Time 0.00
Received By pleduc Date 2023-07-13 Time 15:31 Sent To  
Notes
2023-07-13 15:37:33THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF A VENTLESS HOOD SYSTEM
 OVER COOKING EQUIPMENT, HOWEVER, THERE IS NO
 MANUFACTURE SPECIFICATION SHEETS TO VERIFY COMPLIANCE
 WITH NFPA CODES.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS OF THE PROPOSED.
  
  
  
 2) THERE IS AN INDICATION OF A VENTLESS HOOD SYSTEM
 OVER COOKING EQUIPMENT, HOWEVER, THERE IS NO
 INDICATIONS COMPLIANCE WITH NFPA 96 AND THE CONTROL AND
 EXTINGUISHMENT OF GREASE LADEN VAPORS.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE A HOOD AND SUPPRESSION SYSTEM PER NFPA
 96 OR PROVIDE DETAILED JUSTIFICATION AND FIRE CODE
 REFERENCES WHY IS IS NOT REQUIRED FOR THIS COMMERICIAL
 HOOD SYSTEM.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-09-26 Cont ID  
Sent By jwitmer Date 2023-09-26 Time 07:39 Rev Time 0.00
Received By jwitmer Date 2023-07-12 Time 16:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-07-26 Cont ID  
Sent By cmontell Date 2023-07-26 Time 13:25 Rev Time 0.00
Received By cmontell Date 2023-07-26 Time 13:23 Sent To  
Notes
2023-07-26 13:25:01MECHANICAL PALN REVIEW FAIL
  
 1 - SEE FIRE MARSHAL NOTES
  
  
 CHRIS MONTELLO
 561-805-6733

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-07-26 Cont ID  
Sent By jleahy Date 2023-07-26 Time 14:58 Rev Time 0.00
Received By jleahy Date 2023-07-26 Time 14:58 Sent To  
Notes
***NONE***