| 2023-07-13 15:37:33 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF A VENTLESS HOOD SYSTEM |
| | OVER COOKING EQUIPMENT, HOWEVER, THERE IS NO |
| | MANUFACTURE SPECIFICATION SHEETS TO VERIFY COMPLIANCE |
| | WITH NFPA CODES. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT |
| | SPEC SHEETS OF THE PROPOSED. |
| | |
| | |
| | |
| | 2) THERE IS AN INDICATION OF A VENTLESS HOOD SYSTEM |
| | OVER COOKING EQUIPMENT, HOWEVER, THERE IS NO |
| | INDICATIONS COMPLIANCE WITH NFPA 96 AND THE CONTROL AND |
| | EXTINGUISHMENT OF GREASE LADEN VAPORS. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE PROVIDE A HOOD AND SUPPRESSION SYSTEM PER NFPA |
| | 96 OR PROVIDE DETAILED JUSTIFICATION AND FIRE CODE |
| | REFERENCES WHY IS IS NOT REQUIRED FOR THIS COMMERICIAL |
| | HOOD SYSTEM. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |