Plan Review Details - Permit 23031548
Plan Review Stops For Permit 23031548
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-26 Cont ID  
Sent By aoliver Date 2023-06-26 Time 14:19 Rev Time 0.00
Received By aoliver Date 2023-06-22 Time 16:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-21 Cont ID  
Sent By lmarchan Date 2023-06-21 Time 13:00 Rev Time 0.00
Received By lmarchan Date 2023-06-15 Time 08:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-14 Cont ID  
Sent By aoliver Date 2023-04-14 Time 08:45 Rev Time 0.00
Received By aoliver Date 2023-04-12 Time 06:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-06-23 Cont ID  
Sent By ccole Date 2023-06-23 Time 15:02 Rev Time 0.00
Received By ccole Date 2023-06-23 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-06-16 Cont ID  
Sent By ccole Date 2023-06-16 Time 08:10 Rev Time 0.00
Received By ccole Date 2023-06-16 Time 08:06 Sent To  
Notes
2023-06-16 08:18:072ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23031548
 4/13/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 2ND REQUEST FOR SPECS FOR THE 2-INCH IRIGATION BACKLFOW
 PREVENTER. THE SUBMITTED SPECS ARE APPROVED FOR THE TWO
 4-INCH RPZ POTABLE WATER SERVICE BACKFLOW PREVENTERS.
 AS PREVIOUSLY NOTED THE SPECS INDICATE THE MINIMUM SIZE
 IS 2-1/2-INCH- SEE 1ST REVIEW COMMENT BELOW.
  
 1) THE BACKFLOW SPECS ARE FOR SIZES 2-1/2- 10 INCHES.
 THE APPLICATION INDICATES ONE BACKFLOW IS A 2-INCH.
 PLEASE PROVIDE THE CORRECT SPEC SHEET- SEC. 107.2.1
 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-13 Cont ID  
Sent By ccole Date 2023-04-13 Time 09:34 Rev Time 0.00
Received By ccole Date 2023-04-13 Time 09:28 Sent To  
Notes
2023-04-13 09:34:421ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23031548
 4/13/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE BACKFLOW SPECS ARE FOR SIZES 2-1/2- 10 INCHES.
 THE APPLICATION INDICATES ONE BACKFLOW IS A 2-INCH.
 PLEASE PROVIDE THE CORRECT SPEC SHEET- SEC. 107.2.1
 WPB.
  
 1) PROVIDE A BASIC SITE PLAN SHOWING THE LOCATION OF
 THE BACKFLOW PREVENTER- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PU PUBLIC UTILITIES
Rev No 3 Status P Date 2023-06-26 Cont ID  
Sent By aoliver Date 2023-06-26 Time 14:19 Rev Time 0.00
Received By aoliver Date 2023-06-26 Time 14:19 Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status P Date 2023-06-21 Cont ID  
Sent By lmarchan Date 2023-06-21 Time 13:00 Rev Time 0.00
Received By lmarchan Date 2023-06-21 Time 13:00 Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date 2023-04-14 Cont ID  
Sent By aoliver Date 2023-04-14 Time 08:45 Rev Time 0.00
Received By aoliver Date 2023-04-14 Time 08:45 Sent To  
Notes
2023-04-14 08:45:45APPROVED BY RONALD JENKINS