| 2023-04-18 10:25:59 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II/INSPECTOR |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1.) WPB AMENDMENTS TO FBC B 109.3, THE VALUATION |
| | APPEARS TO BE TOO LOW PER THE MARSHALL/SWIFT VALUATIONS |
| | RANGE. IT APPEARS THAT THE VALUE FOR THIS PROJECT |
| | SHOULD BE MORE THAN TWICE AS MUCH AS INDICATED IN THIS |
| | APPLICATION. PLEASE RE-EVALUATE AND RESUBMIT VALUATION. |
| | |
| | 2.) FBC B 107.2.1, THE SUBMITTED APPLICATION INDICATES |
| | THAT THIS IS FOR A HARDWOOD FLOOR INSTALLATION BUT THE |
| | SUBMITTED COPY OF THE CONTRACT ESTIMATE INDICATES THIS |
| | IS FOR VINYL FLOORING. PLEASE CLARIFY THE TYPE OF |
| | FLOORING THAT IS PROPOSED. |
| | |
| | 3.) FBC B 107.2.1, THERE IS NO INDICATION OF THE TYPE |
| | OF FLOORING UNDERLAYMENT THAT IS INTENDED TO BE USED |
| | FOR SOUND PROOFING AND FLAME SPREAD. |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| 2023-04-17 10:17:35 | THE CONTRACT INDICATES VINYL FLOORING TO BE INSTALLED. |
| | PROVIDE TESTING DOCUMENTATION FOR THE FIRE PERFORMANCE |
| | OF THE MATERIALS TO BE INSTALLED TO INCLUDE THE |
| | CRITICAL RADIANT FLUX OF THE MATERIALS. NFPA 101, |
| | 10.2.7 |
| | |