Plan Review Details - Permit 23031523
Plan Review Stops For Permit 23031523
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2023-04-10 Cont ID  
Sent By lbond Date 2023-04-10 Time 10:47 Rev Time 0.00
Received By lbond Date 2023-04-10 Time 10:47 Sent To  
Notes
2023-04-10 10:48:032005 BUILDING THE STRAND

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-21 Cont ID  
Sent By lbond Date 2023-04-21 Time 08:51 Rev Time 0.00
Received By lbond Date 2023-04-21 Time 08:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By lbond Date 2023-04-10 Time 10:48 Rev Time 0.00
Received By lbond Date 2023-04-10 Time 10:48 Sent To  
Notes
2023-04-10 10:51:08BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23031523
  
 REVIEWED: 04.10. 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 AS PER SECTION 107.2.1
 PROVIDE WALL SECTION AT TUB ENCLOSURE.
 MAKE SURE THAT FIRE COMMENTS ARE ADDRESED.
  
  
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-04-10 Cont ID  
Sent By rperdomo Date 2023-04-10 Time 10:48 Rev Time 0.00
Received By rperdomo Date 2023-04-10 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-20 Cont ID  
Sent By pleduc Date 2023-04-20 Time   Rev Time 0.00
Received By pleduc Date 2023-04-20 Time 12:00 Sent To  
Notes
2023-04-20 12:04:56FIRE PROVISO:
  
 THE REMOVAL OF WALLS MAY REQUIRE MODIFICATIONS TO THE
 FIRE SPRINKLER HEAD LOCATIONS AND PROTECTION.
  
 ANY WORK ON THE FIRE SPRINKLER, INCLUDING DEMO, SHALL
 BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 THE REMOVAL TILE AND DRYWALL AROUND THE TUB AND
 REPLACEMENT OF THE SAME MAY DAMAGE THE REQUIRED FIRE
 RATING OF THOSE WALL.
  
 ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED,
 ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-03-30 Cont ID  
Sent By pleduc Date 2023-03-30 Time   Rev Time 0.00
Received By pleduc Date 2023-03-30 Time 11:13 Sent To  
Notes
2023-03-30 13:14:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT
 NAME FOR THE ACTUAL PROPOSED VINYL FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL
 FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) THE REMOVAL OF WALLS MAY REQUIRE MODIFICATIONS TO
 THE FIRE SPRINKLER HEAD LOCATIONS AND PROTECTION.
  
 ANY WORK ON THE FIRE SPRINKLER, INCLUDING DEMO, SHALL
 BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT
  
  
  
  
 3) THE REMOVAL TILE AND DRYWALL AROUND THE TUB AND
 REPLACEMENT OF THE SAME MAY DAMAGE THE REQUIRED FIRE
 RATING OF THOSE WALL.
  
 ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED,
 ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-21 Cont ID  
Sent By lbond Date 2023-04-21 Time 08:51 Rev Time 0.00
Received By lbond Date 2023-04-21 Time 08:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-10 Cont ID  
Sent By lbond Date 2023-04-10 Time 10:53 Rev Time 0.00
Received By lbond Date 2023-03-30 Time 09:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-04-07 Cont ID  
Sent By rwbrown Date 2023-04-07 Time 07:05 Rev Time 0.00
Received By rwbrown Date 2023-04-07 Time 07:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-04-10 Cont ID  
Sent By lbond Date 2023-04-10 Time 10:51 Rev Time 0.00
Received By lbond Date 2023-04-10 Time 10:51 Sent To  
Notes
2023-04-10 10:52:22PALM BEACH LICENSED CONTRACTOR SIGNED PLAN.