| 2023-04-06 17:00:25 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23031497 |
| | 10221 BLUE HERON PT |
| | |
| | 1- GENERATOR CONCRETE PAD ENGINEERING SUBMITTED IS FOR |
| | GENERAC AND KOHLER GENERATORS. GENERATOR SPECS |
| | SUBMITTED ARE FOR A HONEYWELL GENERATOR. NEED TO |
| | PROVIDE ENGINEERING FOR HONEYWELL GENERATORS. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE |
| | ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL |
| | SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS. |
| | ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL |
| | SIGNATURE. |
| | |
| | ENGINEERS |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 3- THE ENGINEER IS LIMITING THE USE OF THIS CONCRETE |
| | PAD ENGINEERING TO A SPECIFIC LOCATION (ZIP CODE AND |
| | COMPANY). ACCORDING TO THIS, THE CONCRETE PAD |
| | ENGINEERING IS VOID BECAUSE THE LOCATION OF THIS |
| | PROJECT DOESN'T MATCH THAT LIMITATION. PROVIDE |
| | ENGINEERING FOR THIS SITE SPECIFIC LOCATION. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |