Plan Review Details - Permit 23031402
Plan Review Stops For Permit 23031402
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-05-08 Cont ID  
Sent By jbrooks Date 2023-05-08 Time 12:17 Rev Time 0.00
Received By jbrooks Date 2023-05-08 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-28 Cont ID  
Sent By jbrooks Date 2023-04-28 Time 10:30 Rev Time 0.00
Received By jbrooks Date 2023-04-28 Time 07:55 Sent To  
Notes
2023-04-28 10:30:31JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL10497-R8 HAS BEEN
 REVISED TO FL10497-R10. PLEASE PROVIDE THE FOLLOWING:
 COVER PAGE, EVALUATION REPORT PAGES 1-4 AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3. THIRD REQUEST.
 2. SUBMITTED MIAMI-DADE COUNTY NOA 20-0714.01 COVERS
 MULTIPLE PRODUCTS & APPROVED ASSEMBLIES: SYSTEMS E(1)
 THROUGH E(4). SELECT PRODUCT & SYSTEM TO BE USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. SECOND
 REQUEST. CANNOT BE INSTALLED DIRECT-TO-DECK. SECOND
 REQUEST
 3. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE. THIRD REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-18 Cont ID  
Sent By jbrooks Date 2023-04-18 Time 11:23 Rev Time 0.00
Received By jbrooks Date 2023-04-18 Time 08:03 Sent To  
Notes
2023-04-18 11:23:44JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL10497-R8 HAS BEEN
 REVISED TO FL10497-R9. PLEASE PROVIDE THE FOLLOWING:
 COVER PAGE, EVALUATION REPORT PAGES 1-4 AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3. SECOND REQUEST.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL10497-R8 SYSTEM NO. W-1 DOES NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM.
 3. SUBMITTED MIAMI-DADE COUNTY NOA 20-0714.01 COVERS
 MULTIPLE PRODUCTS & APPROVED ASSEMBLIES: SYSTEMS E(1)
 THROUGH E(4). SELECT PRODUCT & SYSTEM TO BE USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. SECOND
 REQUEST. CAN NOT BE INSTALLED DIRECT-TO-DECK.
 4. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE. SECOND REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-28 Cont ID  
Sent By jbrooks Date 2023-03-28 Time 10:33 Rev Time 0.00
Received By jbrooks Date 2023-03-28 Time 07:47 Sent To  
Notes
2023-03-28 10:33:45JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL10497-R8 HAS BEEN
 REVISED TO FL10497-R9. PLEASE PROVIDE THE FOLLOWING:
 COVER PAGE, EVALUATION REPORT PAGES 1-4 AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL10497-R9 COVERS MULTIPLE ROOF SYSTEMS FOR
 WOOD DECKS; SYSTEM TYPE A1-F NO. W-1 THRU W-168.
 SELECTED SYSTEM TYPE TO BE USED. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM. -108.
 3. SUBMITTED MIAMI-DADE COUNTY NOA 20-0714.01 COVERS
 MULTIPLE PRODUCTS & APPROVED ASSEMBLIES: SYSTEMS E(1)
 THROUGH E(4). SELECT PRODUCT & SYSTEM TO BE USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 4. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-08 Cont ID  
Sent By aoliver Date 2023-05-08 Time 12:17 Rev Time 0.00
Received By jbrooks Date 2023-05-03 Time 10:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-28 Cont ID  
Sent By jbrooks Date 2023-04-28 Time 10:30 Rev Time 0.00
Received By jbrooks Date 2023-04-24 Time 08:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-18 Cont ID  
Sent By jbrooks Date 2023-04-18 Time 11:23 Rev Time 0.00
Received By jbrooks Date 2023-04-10 Time 08:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-28 Cont ID  
Sent By jbrooks Date 2023-03-28 Time 10:33 Rev Time 0.00
Received By jbrooks Date 2023-03-27 Time 08:57 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved