Plan Review Details - Permit 23031345
Plan Review Stops For Permit 23031345
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2023-05-08 Cont ID  
Sent By cpuell Date 2023-05-08 Time 09:56 Rev Time 0.00
Received By cpuell Date 2023-05-08 Time 09:56 Sent To  
Notes
2023-05-08 09:57:46PARCEL DELETED FROM PAPA MOVING FORWARD WITH 529 S
 FLAGLER DR 28E

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2023-04-25 Cont ID  
Sent By cpuell Date 2023-04-25 Time 09:14 Rev Time 0.00
Received By cpuell Date 2023-04-25 Time 09:13 Sent To  
Notes
2023-04-25 09:20:32APPLICANT IS WORKING THROUGH THE DIFFERENT STEPS, THE
 UNITY OF TITLE HAS BEEN RECORDED, THEY SHOULD BE
 REQUESTING A SINGLE PCN FROM PAPA AND THEN REACHING OUT
 TO ADDRESSING [email protected] OR CALL
 561-805-6659 TO BE ISSUED A SINGLE ADDRESS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By cpuell Date 2023-04-10 Time 12:12 Rev Time 0.00
Received By cpuell Date 2023-04-10 Time 12:12 Sent To  
Notes
2023-04-10 12:19:30PLANS INDICATE THAT AREA OF WORK ENCOMPASSES TWO
 ADDRESSES 529 S FLAGLER DR 28E AND 28F AND TWO PARCELS
 74434322250002805 AND 74434322250002806. TWO UNITS WILL
 NEED TO BE UNIFIED, YOU WILL NEED TO CONTACT VINCE NOEL
 [email protected] OR CALL 561-494-1040 TO START THE UNITY
 OF TITLE PROCEDURE. CURRENTLY THERE ARE TWO SEPARATE
 PROPERTY CONTROL NUMBER (PCN) FOR THE TWO UNITS, YOU
 WILL NEED TO GO FILL OUT PALM BEACH COUNTYS PARCEL
 COMBINATION REQUEST FORM WHICH CAN BE FOUND AT THIS
 LINK HTTPS://WWW.PBCGOV.ORG/PAPA/DEPARTMENTS/GIS.HTM,
 THEY WILL ISSUE YOU WITH A UNIFIED PARCEL CONTROL
 NUMBER (PCN). WHEN YOU CONTACT THE PROPERTY APPRAISERS
 YOU NEED TO REQUEST PRELIMINARY LETTER OF THE UNIFIED
 PCN. ONCE YOU HAVE RECEIVED THE PRELIMINARY LETTER
 PLEASE CONTACT [email protected] OR CALL
 561-805-6659 TO BE ISSUED AN ADDRESS.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-03-28 Cont ID  
Sent By jwitmer Date 2023-03-28 Time 16:38 Rev Time 0.00
Received By jwitmer Date 2023-03-28 Time 15:21 Sent To  
Notes
2023-03-28 15:22:40TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-05-23 Cont ID  
Sent By jwitmer Date 2023-05-23 Time 15:43 Rev Time 0.00
Received By jwitmer Date 2023-05-23 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-08 Cont ID  
Sent By jwitmer Date 2023-05-08 Time 11:50 Rev Time 0.00
Received By jwitmer Date 2023-05-08 Time 11:12 Sent To  
Notes
2023-05-08 11:50:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031345
 ADD: 529 S FLAGLER DR # 28E
 CONT: CAMBRIDGE CONSTRUCTION LLC
 TEL: 561-784-3722
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MAY 08/2023
 ACTION: DENIED
  
 1) SHEET A-100:
 1A) SEMI-COMPLIED. NOTE # 7 STATES NEW 5/8-INCH DRYWALL
 OVER 1/2-INCH PLYWOOD. PLEASE NOTE THIS IS A HIGHRISE
 BUILDING, IF WOOD IS TO BE USED WITHIN WALL CAVITIES.
 PLEASE REVIEW IN THE 2020 FBC-BUILDING SECTION 603.1.
 FIRE RETARDANT TREATED WOOD SHALL BE PERMITTED IN:
 603.1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
 1B) 2ND REQUEST. TEST REPORTS ONLY NOT SPECS. NOTE # 10
 STATES INSTALL NEW WOOD FLOORS OVER PROFLEX MSC 90
 ACOUSTIC MEMBRANE TO MATCH EXISTING. TEST REPORTS NEED
 TO MATCH THE MATERIAL BEING INSTALLED. WE HAVE NOT SEEN
 PROFLEX MSC 90 TESTED FOR WOOD OR WOOD LAMINATES.
 PROFLEX DOES HAVE A PRODUCT PROFLEX LV-200 WHICH THE
 CITY IS IN RECEIPT OF ALL TEST REPORTS.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1B)(1) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B)(2) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1B)(3) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. (TILE & MARBLE) INSULATION INSTALLED
 BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 OR
 1B)(3) 2ND REQUEST. FBC-B 804.4.4.1 SOFT FLOOR FINISHES
 (LVT/ LPT OR LAMINATED OR ENGINEERED WOOD FLOORING)
 WITHIN TENANT SPACE. INTERIOR FLOOR COVERING MATERIALS
 SHALL COMPLY WITH THE REQUIREMENTS OF THE COC FF-1
 -PILL TEST (CPSC 16 CFR PART 1630) OR WITH ASTM D2859.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-28 Cont ID  
Sent By jwitmer Date 2023-03-28 Time 16:38 Rev Time 0.00
Received By jwitmer Date 2023-03-28 Time 15:21 Sent To  
Notes
2023-03-28 16:37:57WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031345
 ADD: 529 S FLAGLER DR # 28E
 CONT: CAMBRIDGE CONSTRUCTION LLC
 TEL: 561-784-3722
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 28/2023
 ACTION: DENIED
  
 1) SHEET A-100:
 1A) NOTE # 7 STATES NEW 5/8-INCH DRYWALL OVER ??-INCH
 PLYWOOD WITH BATT INSULATION IN 2X4 OR 2X6 STUD SPACE.
 PLEASE NOTE THIS IS A HIGHRISE BUILDING, IF WOOD IS TO
 BE USED WITHIN WALL CAVITIES. PLEASE REVIEW IN THE 2020
 FBC-BUILDING SECTION 603.1. FIRE RETARDANT TREATED WOOD
 SHALL BE PERMITTED IN:
 603.1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
 1B) NOTE # 10 STATES INSTALL NEW WOOD FLOORS OVER
 PROFLEX SUPER SIM 90 ACOUSTIC MEMBRANE TO MATCH
 EXISTING. PLEASE NOTE DOCUMENTS SUBMITTED ARE WHISPER
 MAT CS FOR SOUND AND FLAME SPREAD NOT PROFLEX SUPER SIM
 90. BOTH PRODUCT WERE TEST FOR CERAMIC OR PORCELAIN
 TILE NOT FOR WOOD FLOORS. PROFLEX MAKES A PRODUCT THAT
 IS TESTED FOR WOOD LAMINATE FLOORING STC 50 AND IIC 54
 WITH FLAME SPREAD TESTING.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1B)(1) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B)(2) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1B)(3) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 (TILE & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 OR
 1B)(3) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 -PILL TEST (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-01 Cont ID  
Sent By rperdomo Date 2023-05-01 Time 16:39 Rev Time 0.00
Received By rperdomo Date 2023-05-01 Time 16:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-01 Cont ID  
Sent By rperdomo Date 2023-04-06 Time 10:11 Rev Time 0.00
Received By rperdomo Date 2023-04-06 Time 09:36 Sent To  
Notes
2023-04-06 10:10:37FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE.
 NEC 220
 2. PROVIDE PANEL SCHEDULE SHOWING THE FOLLOWING
 INFORMATION:
 A. PANEL RATING WITH PROTECTION (MAIN BREAKER) RATING
 B. PANEL SCHEDULE SHOWING NEW EQUIMENT INSTALLED
 NEC 408.4(A)
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-16 Cont ID  
Sent By pleduc Date 2023-05-16 Time   Rev Time 0.00
Received By pleduc Date 2023-05-16 Time 11:52 Sent To  
Notes
2023-05-16 11:53:01FIRE PROVISO:
  
 DUE TO THE RECONSTRUCTION, THE FIRE SPRINKLER
 PROTECTION REQUIRES MODIFICATION.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-26 Cont ID  
Sent By pleduc Date 2023-04-26 Time   Rev Time 0.00
Received By pleduc Date 2023-04-26 Time 10:47 Sent To  
Notes
2023-04-26 10:49:23FIRE PROVISO:
  
 DUE TO THE RECONSTRUCTION, THE FIRE SPRINKLER
 PROTECTION REQUIRES MODIFICATION.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-03-24 Cont ID  
Sent By pleduc Date 2023-03-24 Time   Rev Time 0.00
Received By pleduc Date 2023-03-24 Time 11:50 Sent To  
Notes
2023-03-24 11:58:11FIRE PROVISO:
  
 DUE TO THE RECONSTRUCTION, THE FIRE SPRINKLER
 PROTECTION REQUIRES MODIFICATION.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-31 Cont ID  
Sent By hmoser Date 2023-05-31 Time 13:34 Rev Time 0.00
Received By hmoser Date 2023-05-26 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-23 Cont ID  
Sent By hmoser Date 2023-05-23 Time 17:32 Rev Time 0.00
Received By hmoser Date 2023-05-15 Time 08:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2023-05-08 Time   Rev Time 0.00
Received By amcgrego Date 2023-04-20 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-10 Cont ID  
Sent By cpuell Date 2023-04-10 Time 12:19 Rev Time 0.00
Received By cpuell Date 2023-03-23 Time 10:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-03-28 Cont ID  
Sent By jwitmer Date 2023-03-28 Time 15:21 Rev Time 0.00
Received By jwitmer Date 2023-03-28 Time 15:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-05-31 Cont ID  
Sent By hmoser Date 2023-05-31 Time 13:22 Rev Time 0.00
Received By hmoser Date 2023-05-31 Time 13:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-05-23 Cont ID  
Sent By hmoser Date 2023-05-23 Time 17:31 Rev Time 0.00
Received By hmoser Date 2023-05-23 Time 16:59 Sent To  
Notes
2023-05-23 17:31:30PLAN DENIED
 1) MECHANICAL PLAN MUST INCLUDE THE ARCHITECTS DIGITAL
 SIGNATURE. FS 471/481
 2) EQUIPMENT SCHEDULE FOR NEW EQUIPMENT REQUIRED
 ON THE PLAN. SECTION 107 WPB AMENDMENTS.
 3) ERFER TO SECTION 107.2.1.4 QUALITY PLAN
 WPB AMENDMENTS.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 10:16 Rev Time 0.00
Received By medwards Date 2023-05-02 Time 10:16 Sent To  
Notes
2023-05-02 10:17:26THE MECHANICAL DRAWING MUST INCLUDE THE ARCHITECTS
 DIGITAL SIGNATURE. FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-31 Cont ID  
Sent By medwards Date 2023-03-31 Time 16:05 Rev Time 0.00
Received By medwards Date 2023-03-31 Time 16:05 Sent To  
Notes
2023-03-31 16:05:511ST REVIEW FMC
 PERMIT: 23031345
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 PROVIDE A SCOPE OF WORK AND MECHANICAL DESIGN FOR THE
 MECHANICAL WORK BEING COMPLETED IN THIS PROJECT. THIS
 SHOULD BE SUBMITTED FOR REVIEW UNDER THIS MASTER PERIT.
 A MECHANICAL SUB PERMIT WILL ALSO BE REQUIRED. FBC
 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-04-21 Cont ID  
Sent By ccole Date 2023-04-21 Time 16:11 Rev Time 0.00
Received By ccole Date 2023-04-21 Time 16:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-03-30 Cont ID  
Sent By ccole Date 2023-03-30 Time 09:25 Rev Time 0.00
Received By ccole Date 2023-03-30 Time 08:55 Sent To  
Notes
2023-03-30 12:03:111ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23031345
 3/29/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SIGNATURE ERROR: THE PLUMBING PLANS P0.1 & P1.1
 CANNOT BE APPROVED DUE TO A SIGNATURE ERROR WHICH
 TERMINATED THE VERIFICATION PROCESS. PLANS DESIGNED BY
 ENGINEERS AND UPLOADED FOR REVIEW SHALL HAVE VERIFIABLE
 DIGITAL SIGNATURES AND SEALS BY THE ENGINEER AS
 REQUIRED BY FL. STATUTE 471.025 AND SEC. 61G15-23.005
 FLORIDA ADMINISTRATIVE CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-05-31 Cont ID  
Sent By hmoser Date 2023-05-31 Time 13:22 Rev Time 0.00
Received By hmoser Date 2023-05-31 Time 13:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-05-23 Cont ID  
Sent By hmoser Date 2023-05-23 Time 17:31 Rev Time 0.00
Received By hmoser Date 2023-05-23 Time 17:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-08 Cont ID  
Sent By jwitmer Date 2023-05-08 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2023-05-08 Time 11:52 Sent To  
Notes
2023-05-08 11:55:52FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) PLANS
 IN THE FILE FOLDER, SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEE???S SIGNATURE
 SHALL NOT BE USED ON ELECTRONIC/DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.SIGNATURE FILE DOES NOT OPEN FOR
 VERIFIACATION.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By cthroop Date 2023-04-10 Time 10:44 Rev Time 0.00
Received By cthroop Date 2023-04-10 Time 10:29 Sent To  
Notes
2023-04-10 10:46:181ST SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: ALL PLAN PAGES ???
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
2023-03-30 12:04:06SIGNATURE ERROR: THE PLUMBING PLANS P0.1 & P1.1 CANNOT
 BE APPROVED DUE TO A SIGNATURE ERROR WHICH TERMINATED
 THE VERIFICATION PROCESS. PLANS DESIGNED BY ENGINEERS
 AND UPLOADED FOR REVIEW SHALL HAVE VERIFIABLE DIGITAL
 SIGNATURES AND SEALS BY THE ENGINEER AS REQUIRED BY FL.
 STATUTE 471.025 AND SEC. 61G15-23.005 FLORIDA
 ADMINISTRATIVE CODE.
2023-03-28 16:41:45ARCHITECTURAL SHEETS APPEAR TO BE PAPER PLANS WITH WET
 INK SEAL. FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 (3)(C) PLANS IN THE PLAN FILE FOLDER, SCANNED,
 FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE
 LICENSEE???S SIGNATURE SHALL NOT BE USED ON
 ELECTRONIC/DIGITALLY SIGNED AND SEALED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  