Plan Review Details - Permit 23031274
Plan Review Stops For Permit 23031274
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-06-21 Cont ID  
Sent By jwitmer Date 2023-06-21 Time 14:38 Rev Time 0.00
Received By jwitmer Date 2023-06-21 Time 14:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 12:34 Rev Time 0.00
Received By jwitmer Date 2023-06-06 Time   Sent To  
Notes
2023-06-06 12:34:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031274
 ADD: 5200 N FLAGLER DR.
 CONT: PROMAR BUILDING SERVICES LLC
 TEL: 561-598-4549
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS???
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 4TH REVIEW
 DATE: TUES. JUNE 06TH/ 2023
 ACTION: DENIED
 1) COMPLIED. THRESHOLD INSPECTION PLAN
  
 2) SEMI-COMPLIED, NEW FORMS.
  
 3) THRESHOLD BUILDING / FL S. S. 553.71(7) THRESHOLD
 BUILDING MEANING ANY BUILDING WHICH IS GREATER THAN (3)
 STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY CLASSIFICATION AS DENIED IN THE FLORIDA
 BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND
 AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 3A) COMPLIED. THRESHOLD INSPECTION PLAN SIGNATURE.
  
  
 3B) 4TH REQUEST. THE PROBLEM WITH JOBSITE INSPECTOR.
 ENGINEER INTERN DOES THE INTERN HOLD A STATE BN
 INSPECTOR LICENSE. JOHNATHAN GIL REGISTRATION NOT FILED
 IN AS AN ENGINEER NOR INSPECTOR BN LICENSE. NOTE THE
 STATE SHOWS THERE ARE 2 JOHNATHAN GILS AS INTERNS.
 STATE STATUTE 468 PART XII OF THE STATE OF FLORIDA AND
 SECTION 110.8.6 FLORIDA BUILDING CODE.
 JAVIER E. LEIVA, EI. DOES NOT HOLD A BN INSPECTOR
 LICENSE. STATE STATUTE 468 PART XII OF THE STATE OF
 FLORIDA AND SECTION 110.8.6 FLORIDA BUILDING CODE.
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-05-09 Cont ID  
Sent By jwitmer Date 2023-05-09 Time 09:27 Rev Time 0.00
Received By jwitmer Date 2023-05-09 Time 07:51 Sent To  
Notes
2023-05-09 09:27:39WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031274
 ADD: 5200 N FLAGLER DR.
 CONT: PROMAR BUILDING SERVICES LLC
 TEL: 561-598-4549
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. MAY 09TH/ 2023
 ACTION: DENIED
 1)3RD REQUEST. DIGITAL SEAL WILL NOT OPEN FOR
 VERIFICATION FOR PLANS S-1, S-2 & S-3 , THRESHOLD
 INSPECTION PLAN AND PROJECT MANUAL UPLOADED 4/6/23. THE
 DIGITAL SIGNATURE DOES NOT OPEN FOR 3RD PARTY
 VERIFICATION. FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 (3)(C) PLANS IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE???S
 SIGNATURE SHALL NOT BE USED ON ELECTRONIC/DIGITALLY
 SIGNED AND SEALED ENGINEERING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 FL. ADMINISTRATIVE CODE 61G15-23.004 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
  
 2) SEMI-COMPLIED, NEW FORMS.
  
 3) THRESHOLD BUILDING / FL S. S. 553.71(7) ???THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) SEMI-COMPLIED, THRESHOLD INSPECTION PLAN DIGITAL
 SIGNATURE WILL NOT OPEN FOR THIRD PARTY VERIFICATION.
 FL. ADMINISTRATIVE CODE 61G15-23.004 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
 1) ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C., MAY BE SIGNED
 DIGITALLY AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE. AS USED HEREIN, THE
 TERMS ???CERTIFICATION AUTHORITY,??? AND ???DIGITAL
 SIGNATURE??? SHALL HAVE THE MEANINGS ASCRIBED TO THEM
 IN SECTIONS 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND,
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 DIGITAL SIGNATURE AND CORRESPONDINGLY THE DOCUMENT IS
 INVALIDATED IF ANY DATA IN THE DOCUMENT IS CHANGED.
  
  
 3B) SEMI-COMPLIED PROBLEM WITH JOBSITE INSPECTOR.
 ENGINEER INTERN, DOES THE INTERN HOLD A STATE BN
 INSPECTOR LICENSE.
 JOHNATHAN GIL REGISTRATION NOT FILED IN AS AN ENGINEER
 NOR INSPECTOR BN LICENSE. NOTE THE STATE SHOWS THERE
 ARE 2 JOHNATHAN GIL???S AS INTERNS. STATE STATUTE 468
 PART XII OF THE STATE OF FLORIDA AND SECTION 110.8.6
 FLORIDA BUILDING CODE.
  
 3C) 3RD REQUEST. RESPONSE STATES THIS STATEMENT ADDED
 TO SHEET S-1. THERE ARE NO REVISION DATES SHOWN ON
 SHEET S1, NEITHER IS THERE DELTAS OR CLOUDED AREA WHERE
 THIS STATEMENT HAS BEEN ADDED.
 THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) SEMI-COMPLIED. FOR THE SPECIAL INSPECTOR. NOT
 JOBSITE INSPECTORS WITH EITHER ENGINEERS LICENSE, OR BN
 INSPECTORS LICENSE. THE BUILDING OFFICIAL OR HIS
 DESIGNEE WILL REVIEW THE RESUME'. AFTER THE RESUME' IS
 REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
  
 3E) 3RD REQUEST. RESPONSE CONTRACTOR WILL PROVIDE. THE
 CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY FOR
 THIS TYPE OF CONSTRUCTION. NOT THIS REVIEW CYCLE.
  
 4) 3RD REQUEST. WITHIN THE DOCUMENTS SUBMITTED THE
 JOBSITE INSPECTOR IS AN ENGINEER INTERN, DOES THE
 INTERN HOLD A STATE BN INSPECTOR LICENSE. THE RESPONSE
 LETTER STATES THAT YOU ARE MEETING THE STATE STATUTES,
 YES UNDER THE ENGINEERING STATUTE BUT NOT UNDER OUR
 STATE STATUTE 468 PART XII OF THE STATE OF FLORIDA AND
 SECTION 110.8.6 FLORIDA BUILDING CODE
  
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-11 Cont ID  
Sent By jwitmer Date 2023-04-11 Time 08:05 Rev Time 0.00
Received By jwitmer Date 2023-04-11 Time 07:33 Sent To  
Notes
2023-04-11 08:05:06WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031274
 ADD: 5200 N FLAGLER DR.
 CONT: PROMAR BUILDING SERVICES LLC
 TEL: 561-598-4549
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. APRIL 11TH/ 2023
 ACTION: DENIED
 1)2ND REQUEST. DIGITAL SEAL WILL NOT OPEN FOR
 VERIFICATION, PLANS AND PROJECT MANUAL UPLOADED 4/5/23.
 SHEETS S-1 THROUGH S-4 IT APPEARS THEY WERE DOWNLOADED
 INTO PAPER PLANS THEN UPLOADED TO THE BUILDING
 DEPARTMENT. THE DIGITAL SIGNATURE DOES NOT OPEN FOR 3RD
 PARTY VERIFICATION. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) PLANS IN THE FILE FOLDER, SCANNED,
 FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE
 LICENSEE???S SIGNATURE SHALL NOT BE USED ON
 ELECTRONIC/DIGITALLY SIGNED AND SEALED ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FL. ADMINISTRATIVE CODE 61G15-23.004 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
  
 2) 2ND REQUEST. THE FORMS ARE OLD FORMS NOT FROM THE
 OCT. 2018 WEST PALM BEACH GUIDELINES AND POLICIES FOR
 PROJECTS CONCERNING THRESHOLD/ SPECIAL INSPECTORS.
 GUIDELINES AND FORMS WILL BE E-MAILED TO:
 E-MAIL: [email protected] SENT @ 3:04 PM
 3/28/2023.
  
 3) 2ND REQUEST. THRESHOLD BUILDING / FL S. S. 553.71(7)
 ???THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 3B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
  
 3C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 3E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4) 2ND REQUEST. WITHIN THE DOCUMENTS SUBMITTED THE
 JOBSITE INSPECTOR IS AN ENGINEER INTERN, DOES THE
 INTERN HOLD A STATE BN INSPECTOR LICENSE. SEE WEST PALM
 THRESHOLD BUILDING SPECIAL INSPECTOR PROGRAM PAGE 3
 REQUIRED COMPLIANCE # 4-CHAPTER 468 PART XII OF THE
 FLORIDA STATUTES PER SECTION 110.8.6 FLORIDA BUILDING
 CODE.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-28 Cont ID  
Sent By jwitmer Date 2023-03-28 Time 15:11 Rev Time 0.00
Received By jwitmer Date 2023-03-28 Time 14:18 Sent To  
Notes
2023-03-28 15:10:38WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031274
 ADD: 5200 N FLAGLER DR.
 CONT: PROMAR BUILDING SERVICES LLC
 TEL: 561-598-4549
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 28TH/ 2023
 ACTION: DENIED
 1) SHEETS S-1 THROUGH S-4 IT APPEARS THEY WERE
 DOWNLOADED INTO PAPER PLANS THEN UPLOADED TO THE
 BUILDING DEPARTMENT. THE DIGITAL SIGNATURE DOES NOT
 OPEN FOR 3RD PARTY VERIFICATION. FLORIDA ADMINISTRATIVE
 CODE 61G15-23.005 (3)(C) PLANS IN THE FILE FOLDER,
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE???S SIGNATURE SHALL NOT BE USED ON
 ELECTRONIC/DIGITALLY SIGNED AND SEALED ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FL. ADMINISTRATIVE CODE 61G15-23.004 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
 2) THE FORMS ARE OLD FORMS NOT FROM THE OCT. 2018 WEST
 PALM BEACH GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/ SPECIAL INSPECTORS. GUIDELINES
 AND FORMS WILL BE E-MAILED TO:
 E-MAIL: [email protected] SENT @ 3:04 PM
 3/28/2023.
  
 3) THRESHOLD BUILDING / FL S. S. 553.71(7) ???THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4) WITHIN THE DOCUMENTS SUBMITTED THE JOBSITE INSPECTOR
 IS AN ENGINEER INTERN, DOES THE INTERN HOLD A STATE BN
 INSPECTOR LICENSE. SEE WEST PALM THRESHOLD BUILDING
 SPECIAL INSPECTOR PROGRAM PAGE 3 REQUIRED COMPLIANCE #
 4-CHAPTER 468 PART XII OF THE FLORIDA STATUTES PER
 SECTION 110.8.6 FLORIDA BUILDING CODE.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-12 Cont ID  
Sent By clfranci Date 2023-05-12 Time   Rev Time 0.00
Received By clfranci Date 2023-05-12 Time   Sent To  
Notes
2023-05-12 13:13:08THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PLEASE ENSURE THAT ALL FIRE EXITS IS MAINTAINED
 CLEAR AND UNOBSTRUCTED.
  
 2) PLEASE ENSURE THAT FIRE DEPARTMENT ACCESS IS
 MAINTAINED CLEAR AND UNOBSTRUCTED.
  
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561.804.4728
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-07 Cont ID  
Sent By clfranci Date 2023-04-07 Time   Rev Time 0.00
Received By clfranci Date 2023-04-07 Time   Sent To  
Notes
2023-04-07 15:03:59THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PLEASE ENSURE THAT ALL FIRE EXITS IS MAINTAINED
 CLEAR AND UNOBSTRUCTED.
  
 2) PLEASE ENSURE THAT FIRE DEPARTMENT ACCESS IS
 MAINTAINED CLEAR AND UNOBSTRUCTED.
  
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561.804.4728
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-03-23 Cont ID  
Sent By clfranci Date 2023-03-23 Time   Rev Time 0.00
Received By clfranci Date 2023-03-23 Time   Sent To  
Notes
2023-03-23 09:40:09THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PLEASE ENSURE THAT ALL FIRE EXITS IS MAINTAINED
 CLEAR AND UNOBSTRUCTED.
  
 2) PLEASE ENSURE THAT FIRE DEPARTMENT ACCESS IS
 MAINTAINED CLEAR AND UNOBSTRUCTED.
  
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561.804.4728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 12:35 Rev Time 0.00
Received By jwitmer Date 2023-05-11 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-05-09 Time   Rev Time 0.00
Received By amcgrego Date 2023-04-18 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2023-04-11 Time   Rev Time 0.00
Received By amcgrego Date 2023-04-06 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-03-28 Time 15:16 Rev Time 0.00
Received By cdecoeur Date 2023-03-21 Time 08:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-06-21 Cont ID  
Sent By jwitmer Date 2023-06-21 Time 14:39 Rev Time 0.00
Received By jwitmer Date 2023-06-21 Time 14:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 12:34 Rev Time 0.00
Received By jwitmer Date 2023-06-06 Time   Sent To  
Notes
2023-06-06 12:34:29WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031274
 ADD: 5200 N FLAGLER DR.
 CONT: PROMAR BUILDING SERVICES LLC
 TEL: 561-598-4549
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS???
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 4TH REVIEW
 DATE: TUES. JUNE 06TH/ 2023
 ACTION: DENIED
 1) COMPLIED. THRESHOLD INSPECTION PLAN
  
 2) SEMI-COMPLIED, NEW FORMS.
  
 3) THRESHOLD BUILDING / FL S. S. 553.71(7) THRESHOLD
 BUILDING MEANING ANY BUILDING WHICH IS GREATER THAN (3)
 STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY CLASSIFICATION AS DENIED IN THE FLORIDA
 BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND
 AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 3A) COMPLIED. THRESHOLD INSPECTION PLAN SIGNATURE.
  
  
 3B) 4TH REQUEST. THE PROBLEM WITH JOBSITE INSPECTOR.
 ENGINEER INTERN DOES THE INTERN HOLD A STATE BN
 INSPECTOR LICENSE. JOHNATHAN GIL REGISTRATION NOT FILED
 IN AS AN ENGINEER NOR INSPECTOR BN LICENSE. NOTE THE
 STATE SHOWS THERE ARE 2 JOHNATHAN GILS AS INTERNS.
 STATE STATUTE 468 PART XII OF THE STATE OF FLORIDA AND
 SECTION 110.8.6 FLORIDA BUILDING CODE.
 JAVIER E. LEIVA, EI. DOES NOT HOLD A BN INSPECTOR
 LICENSE. STATE STATUTE 468 PART XII OF THE STATE OF
 FLORIDA AND SECTION 110.8.6 FLORIDA BUILDING CODE.
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-05-09 Cont ID  
Sent By jwitmer Date 2023-05-09 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2023-05-09 Time 08:30 Sent To  
Notes
2023-05-09 09:29:25. DIGITAL SEAL WILL NOT OPEN FOR VERIFICATION FOR PLANS
 S-1, S-2 & S-3, THRESHOLD INSPECTION PLAN AND PROJECT
 MANUAL UPLOADED 4/6/23. THE DIGITAL SIGNATURE DOES NOT
 OPEN FOR 3RD PARTY VERIFICATION. FLORIDA ADMINISTRATIVE
 CODE 61G15-23.005 (3)(C) PLANS IN THE FILE FOLDER,
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE'S SIGNATURE SHALL NOT BE USED ON
 ELECTRONIC/DIGITALLY SIGNED AND SEALED ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FL. ADMINISTRATIVE CODE 61G15-23.004 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-11 Cont ID  
Sent By jwitmer Date 2023-04-11 Time 08:05 Rev Time 0.00
Received By jwitmer Date 2023-04-11 Time 07:33 Sent To  
Notes
2023-04-11 08:05:42SEE BUILDING COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-24 Cont ID  
Sent By mpeterso Date 2023-03-24 Time 09:51 Rev Time 0.00
Received By mpeterso Date 2023-03-24 Time 09:51 Sent To  
Notes
2023-03-24 09:55:03SIGNATURE REVIEW FAILED
  
 1) ALL PAERE DOCUMENTS SUBMITTED ARE COPIES OF THE EOR
 DIGITAL SIGNATURE. PLEASE CORRECT AS OUTLINED BELOW.
  
 THERE ARE ONLY TWO WAYS IN WHICH PLANS PREPARED BY AN
 ENGINEER OR ARCHITECT ARE ACCEPTABLE AND WILL PASS A
 SIGNATURE REVIEW. SEE THE DESCRIPTION BELOW.
  
 1) PAPER DOCUMENTS SUBMITTED MUST HAVE A SEAL WITH A
 WET SIGNATURE.
  
 2) DIGITALLY SUBMITTED DOCUMENTS MUST HAVE A SEAL WITH
 A DIGITAL SIGNATURE. PLEASE NOTE IT IS EXTREMELY
 IMPORTANT THAT ALL DIGITAL SIGNATURES ARE VERIFIABLE
 THROUGH ADOBE OR BLUEBEAM SOFTWARE
  
 DIGITALLY SUBMITTED DOCUMENTS ARE PREFERRED
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2023-06-21 Cont ID  
Sent By jwitmer Date 2023-06-21 Time 14:38 Rev Time 0.00
Received By jwitmer Date 2023-06-21 Time 14:00 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2023-06-06 Cont ID  
Sent By jwitmer Date 2023-06-06 Time 12:35 Rev Time 0.00
Received By jwitmer Date 2023-06-06 Time 12:34 Sent To  
Notes
2023-06-06 12:35:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031274
 ADD: 5200 N FLAGLER DR.
 CONT: PROMAR BUILDING SERVICES LLC
 TEL: 561-598-4549
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS???
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 4TH REVIEW
 DATE: TUES. JUNE 06TH/ 2023
 ACTION: DENIED
 1) COMPLIED. THRESHOLD INSPECTION PLAN
  
 2) SEMI-COMPLIED, NEW FORMS.
  
 3) THRESHOLD BUILDING / FL S. S. 553.71(7) THRESHOLD
 BUILDING MEANING ANY BUILDING WHICH IS GREATER THAN (3)
 STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY CLASSIFICATION AS DENIED IN THE FLORIDA
 BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND
 AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 3A) COMPLIED. THRESHOLD INSPECTION PLAN SIGNATURE.
  
  
 3B) 4TH REQUEST. THE PROBLEM WITH JOBSITE INSPECTOR.
 ENGINEER INTERN DOES THE INTERN HOLD A STATE BN
 INSPECTOR LICENSE. JOHNATHAN GIL REGISTRATION NOT FILED
 IN AS AN ENGINEER NOR INSPECTOR BN LICENSE. NOTE THE
 STATE SHOWS THERE ARE 2 JOHNATHAN GILS AS INTERNS.
 STATE STATUTE 468 PART XII OF THE STATE OF FLORIDA AND
 SECTION 110.8.6 FLORIDA BUILDING CODE.
 JAVIER E. LEIVA, EI. DOES NOT HOLD A BN INSPECTOR
 LICENSE. STATE STATUTE 468 PART XII OF THE STATE OF
 FLORIDA AND SECTION 110.8.6 FLORIDA BUILDING CODE.
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2023-05-09 Cont ID  
Sent By jwitmer Date 2023-05-09 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2023-05-09 Time 07:52 Sent To  
Notes
2023-05-09 09:28:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031274
 ADD: 5200 N FLAGLER DR.
 CONT: PROMAR BUILDING SERVICES LLC
 TEL: 561-598-4549
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. MAY 09TH/ 2023
 ACTION: DENIED
 1)3RD REQUEST. DIGITAL SEAL WILL NOT OPEN FOR
 VERIFICATION FOR PLANS S-1, S-2 & S-3 , THRESHOLD
 INSPECTION PLAN AND PROJECT MANUAL UPLOADED 4/6/23. THE
 DIGITAL SIGNATURE DOES NOT OPEN FOR 3RD PARTY
 VERIFICATION. FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 (3)(C) PLANS IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE'S
 SIGNATURE SHALL NOT BE USED ON ELECTRONIC/DIGITALLY
 SIGNED AND SEALED ENGINEERING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 FL. ADMINISTRATIVE CODE 61G15-23.004 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
  
 2) SEMI-COMPLIED, NEW FORMS.
  
 3) THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) SEMI-COMPLIED, THRESHOLD INSPECTION PLAN DIGITAL
 SIGNATURE WILL NOT OPEN FOR THIRD PARTY VERIFICATION.
 FL. ADMINISTRATIVE CODE 61G15-23.004 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
 1) ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C., MAY BE SIGNED
 DIGITALLY AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE. AS USED HEREIN, THE
 TERMS "CERTIFICATION AUTHORITY"? AND "DIGITAL
 SIGNATURE" SHALL HAVE THE MEANINGS ASCRIBED TO THEM IN
 SECTIONS 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND,
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 DIGITAL SIGNATURE AND CORRESPONDINGLY THE DOCUMENT IS
 INVALIDATED IF ANY DATA IN THE DOCUMENT IS CHANGED.
  
  
 3B) SEMI-COMPLIED PROBLEM WITH JOBSITE INSPECTOR.
 ENGINEER INTERN, DOES THE INTERN HOLD A STATE BN
 INSPECTOR LICENSE.
 JOHNATHAN GIL REGISTRATION NOT FILED IN AS AN ENGINEER
 NOR INSPECTOR BN LICENSE. NOTE THE STATE SHOWS THERE
 ARE 2 JOHNATHAN GIL???S AS INTERNS. STATE STATUTE 468
 PART XII OF THE STATE OF FLORIDA AND SECTION 110.8.6
 FLORIDA BUILDING CODE.
  
 3C) 3RD REQUEST. RESPONSE STATES THIS STATEMENT ADDED
 TO SHEET S-1. THERE ARE NO REVISION DATES SHOWN ON
 SHEET S1, NEITHER IS THERE DELTAS OR CLOUDED AREA WHERE
 THIS STATEMENT HAS BEEN ADDED.
 THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) SEMI-COMPLIED. FOR THE SPECIAL INSPECTOR. NOT
 JOBSITE INSPECTORS WITH EITHER ENGINEERS LICENSE, OR BN
 INSPECTORS LICENSE. THE BUILDING OFFICIAL OR HIS
 DESIGNEE WILL REVIEW THE RESUME'. AFTER THE RESUME' IS
 REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
  
 3E) 3RD REQUEST. RESPONSE CONTRACTOR WILL PROVIDE. THE
 CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY FOR
 THIS TYPE OF CONSTRUCTION. NOT THIS REVIEW CYCLE.
  
 4) 3RD REQUEST. WITHIN THE DOCUMENTS SUBMITTED THE
 JOBSITE INSPECTOR IS AN ENGINEER INTERN, DOES THE
 INTERN HOLD A STATE BN INSPECTOR LICENSE. THE RESPONSE
 LETTER STATES THAT YOU ARE MEETING THE STATE STATUTES,
 YES UNDER THE ENGINEERING STATUTE BUT NOT UNDER OUR
 STATE STATUTE 468 PART XII OF THE STATE OF FLORIDA AND
 SECTION 110.8.6 FLORIDA BUILDING CODE
  
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  