Plan Review Details - Permit 23031267
| Plan Review Stops For Permit 23031267 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2023-06-26 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-06-26 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-06-26 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2023-06-26 15:39:19 | WORK IS FOR UNITS 402, 403 & 404 UPDATED PERMIT. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2023-05-09 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-05-09 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-05-09 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2023-05-09 08:52:05 | CURRENT SUITE ADDRESSES NOT MATCHING WHAT WE CURRENLTY | | | HAVE, PLEASE PUT NSEW ON THE PLANS SO THAT I CAN UPDATE | | | THE SUITE CONFIGURATION. PLEASE RESPOND TO | | | [email protected] OR CALL 561-805-6659 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2023-06-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-06-23 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-06-23 |
Time |
14:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2023-05-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-05-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-05-09 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2023-05-09 10:39:31 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS OF DOOR DETAILS/DOOR | | | SCHEDULE FOR THE 3 NEW SUITES. | | | | | | PER NFPA 1, CH 1 | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS. | | | | | | | | | PER NFPA 101, CH 38 | | | | | | 38.2.2.2 DOORS. | | | 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE | | | PERMITTED. | | | | | | PLEASE PROVIDE DOOR DETAILS, EXISTING OR NEW. | | | | | | | | | | | | 2) THERE ARE INDICATIONS OF NEW WALLS IN A BUILDING | | | THAT HAS FIRE SPRINKLER AND FIRE ALARM SYSTEMS THAT MAY | | | REQUIRE MODIFICATIONS FOR CODE COMPLIANCE. | | | | | | PER NFPA 241, 13 & 72 | | | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS | | | | | | | | | FOR THE OFFICIAL RECORD, PROVIDE A NOTE OF | | | ACKNOWLEDGEMENT TOCOMPLY WITH THE NOTED ABOVE | | | REQUIRMENTS. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-06-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-06-23 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-05-08 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2023-06-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-06-23 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-06-23 |
Time |
14:26 |
Sent To |
|
|
| Notes |
|
|
|