Plan Review Details - Permit 23031192
Plan Review Stops For Permit 23031192
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-04-20 Cont ID  
Sent By lquinone Date 2023-04-20 Time 19:35 Rev Time 0.00
Received By lquinone Date 2023-04-20 Time 19:35 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-03-27 Cont ID  
Sent By rrossano Date 2023-03-27 Time   Rev Time  
Received By rrossano Date 2023-03-27 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-21 Cont ID  
Sent By aoliver Date 2023-04-21 Time 07:57 Rev Time 0.00
Received By aoliver Date 2023-04-11 Time 10:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-28 Cont ID  
Sent By aoliver Date 2023-03-28 Time 11:03 Rev Time 0.00
Received By aoliver Date 2023-03-21 Time 06:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-04-12 Cont ID  
Sent By ccole Date 2023-04-12 Time 12:46 Rev Time 0.00
Received By ccole Date 2023-04-12 Time 12:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-03-24 Cont ID  
Sent By ccole Date 2023-03-24 Time 15:21 Rev Time 0.00
Received By ccole Date 2023-03-24 Time 14:34 Sent To  
Notes
2023-03-24 15:23:031ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23031192
 3/24/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE- 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GREASE INTERCEPTOR: PROVIDE THE FOLLOWING
 INFORMATION ON THE PLAN PER SEC. 1003.3.5 FBC P.
 A) MAKE AND MODEL AND CAPACITY FOR THE INTERCEPTOR.
 B) GREASE WASTE CALCULATIONS.
  
 2) ISOMETRIC DRAWING: IDENTIFY THE TYPE OF INDIRECT
 WASTE RECEPTOR SHOWN IN THE DRAWING. IT APPEARS TO BE A
 FLOOR SINK- SECS. 414.1 & 802.1 FBC P.
  
 3) ISOMETRIC: SHOW THE SIZE OF THE UNDERSLAB WASTE PIPE
 FROM THE FLOOR SINK TO THE INTERCEPTOR. A MINIMUM
 2-INCH DRAIN PIPE IS REQUIRED- TABLE 709.1 FBC P.
  
 4) ISOMETRIC: THE AAV CANNOT BE USED TO VENT THE GREASE
 INTERCEPTOR PER SEC. 918.8 FBC P AND ARE TYPICALLY NOT
 APPROVED PER MANUFACTURER'S GUIDELINES. PROVIDE A VENT
 PIPE FOR THE SYSTEM THAT EXTENDS TO A VENT HEADER OR TO
 THE EXTERIOR OF THE BUILDING.
  
 5) ISOMETRIC: PLEASE REFER TO THE MANUFACTURER'S
 INSTALLATION GUIDELINES CONCERNING THE FLOW CONTROL
 DEVICE. THE DEVICE MAY REQUIRE AN AIR INTAKE PIPE SEC.
 1003.3.5 FBC P.
  
 6) ISOMETRIC: PLEASE PROVIDE A WATER RISER AND SHOW THE
 SOURCE OF THE HOT WATER TO THE SINK- SEC. 107.3.5.1.3
 WPB, AND SEC. 607.1 FBC P.
  
 7) PLEASE PROVIDE A BASIC FLOOR DRAWING SHOWING THE
 PROPOSED LOCATION OF THE SINK AND GREASE INTERCEPTOR-
 SEC. 107.2.1 WPB.
  
 8) PROVIDE A COMPLETE SCOPE OF WORK FOR THE NEW
 CATERING BUSINESS AND SUBMIT ADDITIONAL PLANS AND
 DETAILS FOR BUILDING DEPARTMENT REVIEW- SEC. 107.2.1
 WPB.
  
 9) THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR OR
 QUALIFIER SHALL BE ON THE DRAWING- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-12 Cont ID  
Sent By ccole Date 2023-04-12 Time 12:46 Rev Time 0.00
Received By ccole Date 2023-04-12 Time 12:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-24 Cont ID  
Sent By ccole Date 2023-03-24 Time 15:24 Rev Time 0.00
Received By ccole Date 2023-03-24 Time 15:24 Sent To  
Notes
2023-03-24 15:27:001ST REVIEW SIGNATURE
 PERMIT- 23031192
 3/24/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PRINTED AN AND SIGNATURE OF THE FL. LICENSED
 PLUMBING CONTRACTOR SHALL BE ON ISOMETRIC DRAWING- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  