| Plan Review Stops For Permit 23031171 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-13 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-13 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-31 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-31 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2023-03-31 12:03:18 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23031171 | | | | | | REVIEWED: MARCH 31, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENT: | | | | | | ASBESTOS REVIEW: | | | | | | FAILED PLAN REVIEW: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | | ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION | | | -RENOVATION.HTML | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-13 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-13 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-31 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-31 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2023-03-31 12:09:04 | PLEASE COMPLY TO FIRE COMMENTS AND OTHER TRADES IF | | | APPLICATBLE AND INLCUDE FLOOR FINISH SHEDULE WITH NOA | | | OR FBC APPROVED UNDERLAYMENT IF REQUIRED AND SIGNED | | | PLAN BY PALM BEACH CONTRACTOR AND CONTACT INFO WHO WILL | | | INSTALL THE NEW FLOORING- | | | OR DETAIL AND NOTES ON THE ARCHITECTURAL SIGNED AND | | | SEALED PLAN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-04-13 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-04-13 |
Time |
16:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-04-04 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-04-04 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-04-04 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-04-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-04-13 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-03-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-03-30 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2023-03-30 10:45:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION ON THE SUBMITTED PLANS OF | | | REMOVING ALL FLOORING BUT NO INDICATION OF NEW FLOORING | | | NOR A SPEC SHEET NOR A PRODUCT NAME FOR THE ACTUAL | | | PROPOSED FLOORING. | | | | | | FFLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT ALL | | | ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. | | | | | | PER NFPA 101, CH 30 | | | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | | ACCORDANCE WITH | | | SECTION 10.2. | | | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | | 10.2.2.2 | | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | | HAVE A | | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL | | | FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING | | | THE FIRE BEHAVIOR RATING. | | | | | | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, | | | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS | | | WOULD NOT BE REQUIRED. | | | | | | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL | | | FLOORING, WOOD/VINYL LAMINATES, ETC. | | | | | | | | | | | | 2) IT IS UNCLEAR IF THERE ARE FIRE ALARM DEVICES ON THE | | | WALL THAT IS BEING REMOVED AND RECONSTRUCTED. | | | | | | SHOULD THERE BE ANY FIRE ALARM DEVICES ON THAT WALL AND | | | IT NEEDS TO BE RELOCATED, THE FIRE ALARM SYSTEMS SHALL | | | BE MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | AND ANY WORK ON THE FIRE ALARM SYSTEM, INCLUDING DEMO, | | | SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICALE NOTE ON THE | | | ELECTRICAL PLAN | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-14 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-12 |
Time |
18:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-04-05 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-04-05 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-29 |
Time |
08:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-04-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-14 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-14 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2023-04-14 13:49:07 | LIKE FOR LIKE CHANGE OUT. NO PLAN REVIEW REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-31 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-31 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2023-03-31 12:36:12 | SHEET A-3 OF 4 KEYNOTE H: PROVIDE THE LIKE FOR LIKE | | | CHANGE OUT FORM FOR THE MECHANICAL SYSTEM ALSO, A | | | MECHANICAL SUBPERMIT WILL BE REQUIREMENT FOR THIS LIKE | | | FOR LIKE CHANGE OUT. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-13 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-13 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-03 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-03 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2023-04-03 13:04:10 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-23031171 | | | 4/3/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-4: THE RISER APPEARS TO MISREPRESENT ACTUAL | | | FIELD CONDITIONS BECAUSE IT SHOWS THE WASHING MACHINE | | | FIXTURE DRAIN DISCHARGING INTO THE MAIN SOIL STACK | | | INSTEAD OF A SEPARATE WASTE STACK- SEE SEC. 202 FBC P. | | | FOR DEFINITION OF WASTE. TYPICALLY, MULTI-STORY | | | PLUMBING DESIGN WOULD PROVIDE SEPARATE WASTE AND SOIL | | | STACKS- SEC. 107.2.1 WPB. | | | | | | 2) A-4: THE PLAN SHEET IS NOT DIGITALLY SIGNED AND | | | SEALED BY THE ARCHITECT OF RECORD RODNEY NORTH GREEN- | | | FL. STATUTE 481.221 AND SEC. 61G1-16.005 FAC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
2 |
Status |
N |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-13 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-13 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2023-03-31 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2023-03-31 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2023-03-31 13:53:55 | 1. 553.791, F.S. NOTICE TO BUILDING OFFICIAL | | | - PLEASE PROVIDE NOTICE TO BUILDING OFFICIAL. UPLOAD | | | INTO SUPPORTING DOCUMENTS IN PROJECTDOX. | | | | | | 2. CERTIFICATE OF INSURANCE FOR PROFESSIONAL LIABILITY | | | OF FIRM. MINIMUM COVERAGE OF $1,000,000.00 PER | | | OCCURRENCE AND $2,000,000.00 AGGREGATE ARE REQUIRED. | | | F.S. 553.791 (4) (B) AND (16). CERTIFICATE OF INSURANCE | | | FOR PROFESSIONAL LIABILITY OF FIRM. MINIMUM COVERAGE OF | | | $1,000,000.00 PER OCCURRENCE AND $2,000,000.00 | | | AGGREGATE ARE REQUIRED. F.S. 553.791 (4) (B) AND (16). | | | IN THE DESCRIPTION OF OPERATIONS PLEASE ADD LANGUAGE TO | | | STATE ""THE PROFESSIONAL LIABILITY POLICY INCLUDES AN | | | EXTENDED REPORTING PERIOD ENDORSEMENT (TAIL COVERAGE) | | | FOR FIVE YEARS. ___________IS PROVIDING PROFESSIONAL | | | LIABILITY INSURANCE COVERING ALL SERVICES TO BE | | | PERFORMED AS A PRIVATE PROVIDER. | | | - PLEASE PROVIDE INSURANCE CERTIFICATE. | | | | | | 3. QULIFICATIONS | | | - PLEASE PROVIDE QUALIFICATIONS FOR REVIEWERS OR | | | INSPECTORS WITH THEIR LICENSES. | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-13 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-13 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-31 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-31 |
Time |
11:42 |
Sent To |
|
|
| Notes |
|
|