Plan Review Details - Permit 23031084
Plan Review Stops For Permit 23031084
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-04 Cont ID  
Sent By pleduc Date 2023-04-04 Time   Rev Time 0.00
Received By pleduc Date 2023-04-04 Time 16:13 Sent To  
Notes
2023-04-04 16:23:29FIRE COMMENYS:
  
 TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13
  
 CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION
 (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM IS CHARGED/
 DISCHARGED UNDER WORKING PRESSURE. (I.E. VISUAL FOR
 LEAKS
 & INSPECTOR DRAIN AFTER 2 HRS)
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-05 Cont ID  
Sent By jgomez Date 2023-04-05 Time 15:04 Rev Time 0.00
Received By jgomez Date 2023-04-03 Time 14:24 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-04-05 Cont ID  
Sent By jgomez Date 2023-04-05 Time 15:03 Rev Time 0.00
Received By jgomez Date 2023-04-05 Time 15:00 Sent To  
Notes
2023-04-05 15:04:16NO ARCHITECT OR ENGINEER PLANS/DOCUMENTS. JG.