Plan Review Details - Permit 23031074
Plan Review Stops For Permit 23031074
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-06-20 Cont ID  
Sent By cpuell Date 2023-06-20 Time 10:27 Rev Time 0.00
Received By cpuell Date 2023-06-20 Time 10:27 Sent To  
Notes
2023-06-20 10:27:41PER ZONINGS COMMENTS, SECOND UNIT NOT PERMITTED, NO
 ADDITIONAL ADDRESS REQUIRED.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-03-27 Cont ID  
Sent By cpuell Date 2023-03-27 Time 12:09 Rev Time 0.00
Received By cpuell Date 2023-03-27 Time 12:09 Sent To  
Notes
2023-03-27 12:11:10A SECONDARY ADDRESS MAY NEED TO BE ASSIGNED IF ZONING
 APPROVES A SECONDARY UNIT. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659 ONCE ZONING
 APPROVES THEIR REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-20 Cont ID  
Sent By lbond Date 2023-06-20 Time 13:41 Rev Time 0.00
Received By lbond Date 2023-06-20 Time 13:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-28 Cont ID  
Sent By lbond Date 2023-03-28 Time 15:45 Rev Time 0.00
Received By lbond Date 2023-03-28 Time 15:45 Sent To  
Notes
2023-06-20 13:53:14NEED CLARIFICATION ABOUT BARN DOOR- REF TO PERM
 22060548

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-06-20 Cont ID  
Sent By jcooley Date 2023-06-20 Time 16:36 Rev Time 0.00
Received By jcooley Date 2023-06-20 Time 16:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-03-27 Cont ID  
Sent By jcooley Date 2023-03-27 Time 18:06 Rev Time 0.00
Received By jcooley Date 2023-03-27 Time 17:28 Sent To  
Notes
2023-03-27 18:10:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
  
 2.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 JONATHAN COOLEY
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 (561)345-4377
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2023-04-13 Cont ID  
Sent By vbroglia Date 2023-04-13 Time 12:41 Rev Time 0.00
Received By vbroglia Date 2023-04-13 Time 12:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-23 Cont ID  
Sent By cmontell Date 2023-06-23 Time 14:00 Rev Time 0.00
Received By cmontell Date 2023-06-23 Time 14:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-13 Cont ID  
Sent By vbroglia Date 2023-04-13 Time 12:41 Rev Time 0.00
Received By vbroglia Date 2023-03-23 Time 12:56 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-03-28 Cont ID  
Sent By lbond Date 2023-03-28 Time 16:03 Rev Time 0.00
Received By lbond Date 2023-03-28 Time 16:03 Sent To  
Notes
2023-03-28 16:04:20109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-06-23 Cont ID  
Sent By cmontell Date 2023-06-23 Time 13:59 Rev Time 0.00
Received By cmontell Date 2023-06-23 Time 13:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-24 Cont ID  
Sent By medwards Date 2023-03-24 Time 09:59 Rev Time 0.00
Received By medwards Date 2023-03-24 Time 09:59 Sent To  
Notes
2023-03-24 09:59:351ST REVIEW FMC
 PERMIT: 23031074
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS CHANGE OF
 USE. FEC R101.5.1.1.1
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS CHANGE OF USE. FEC R403.7
  
 3) PROVIDE A MECHANICAL DRAWING THAT IDENTIFIES THE
 LOCATION OF THE INDOOR UNIT AND THE LOCATION AND TIE
 DOWN OF THE CONDENSING UNIT. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-06-16 Cont ID  
Sent By ccole Date 2023-06-16 Time 09:27 Rev Time 0.00
Received By ccole Date 2023-06-16 Time 08:19 Sent To  
Notes
2023-06-16 09:27:282ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT 23031074
 6/16/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE SANITARY DRAINAGE AND VENT RISER
 DRAWING SHOWS NON-COMPLIANT WET VENTING FOR THE NEW
 BATHROOM FIXTURES. THE CURRENT DRAWING SHOWS NO VENTING
 FOR THE TOILET AND SHOWER. PLEASE REFER TO SEC. P3108.1
 & P3108.2.1 FBC RES. IN ORDER TO FIX THE SYSTEM, THE
 KITCHEN SINK FIXTURE DRAIN SHALL CONNECT TO THE 3-INCH
 BRANCH AT A POINT DOWNSTREAM OF THE BATHROOM FIXTURE
 DRAIN CONNECTIONS, AND THE LAV SINK DRAIN SHALL CONNECT
 TO THE 3-INCH AT A POINT UPSTREAM OF THE TOILET AND
 SHOWER FIXTURE DRAIN CONNECTIONS OR IN BETWEEN THE TWO.
  
 2) 2ND REQUEST. IT APPEARS TWO DWELLING UNITS WILL BE
 ON THE SAME LOT WHICH WILL REQUIRE WATER USERS TO
 INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF
 DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL
 BE REQUIRED FOR THE WATER METER PER THE CITY OF WEST
 PALM CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION
 CONTROL PROGRAM. PLEASE PLACE A NOTE ON THE PLAN
 ACCORDINGLY- SEC. 107.2.1 WPB.
  
 PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR AN RPZ
 BACKFLOW PREVENTION DEVICE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-03-24 Cont ID  
Sent By ccole Date 2023-03-24 Time 12:08 Rev Time 0.00
Received By ccole Date 2023-03-24 Time 11:52 Sent To  
Notes
2023-03-24 12:09:001ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT0 23031074
 3/24/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: PROVIDE A SANITARY DRAINAGE AND VENT RISER
 DRAWING FOR THE NEW CABANA BATHROOM AND KITCHEN
 PLUMBING FIXTURES- SEC. 107.3.5.3 FBC P.
  
 2) IT APPEARS TWO DWELLING UNITS WILL BE ON THE SAME
 LOT WHICH WILL REQUIRE WATER USERS TO INSTALL A
 BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF DELIVERY.
 A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL BE
 REQUIRED FOR THE WATER METER PER THE CITY OF WEST PALM
 CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION CONTROL
 PROGRAM. PLEASE PLACE A NOTE ON THE PLAN ACCORDINGLY-
 SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2023-06-20 Cont ID  
Sent By lbond Date 2023-06-20 Time 13:50 Rev Time 0.00
Received By lbond Date 2023-06-20 Time 13:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-03-28 Cont ID  
Sent By lbond Date 2023-03-28 Time 16:07 Rev Time 0.00
Received By lbond Date 2023-03-28 Time 16:07 Sent To  
Notes
2023-03-28 16:16:29FLORIDA LICENSED CONTRACTOR ON BOARD RESIDENTIAL

Review Stop Z ZONING
Rev No 1 Status P Date 2023-04-13 Cont ID  
Sent By AMHamil Date 2023-04-13 Time 11:42 Rev Time 0.00
Received By vbroglia Date 2023-04-13 Time 11:42 Sent To  
Notes
2023-04-13 11:44:204/13/2023
  
 NO KITCHEN PERMITTED
  
 SECONADRY UNIT ONLY PERMITTED WITH A SPEACIAL USE CLASS
 B PERMIT ISSUED, PLEASE EMAIL PLANNING FOR APPLICATION
 IF DESIRED.
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  