Plan Review Details - Permit 23031034
Plan Review Stops For Permit 23031034
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-04-03 Cont ID  
Sent By cpuell Date 2023-04-03 Time 09:09 Rev Time 0.00
Received By cpuell Date 2023-04-03 Time 09:09 Sent To  
Notes
2023-04-03 09:55:08APPLICANT IDENTIFIED THAT THE WORK IS BEING DONE ON THE
 NORTH BUILDING WITH THE ADDRESS OF 3205 BROADWAY,
 UPDATED PERMIT TO THE CORRECT ADDRESS

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-03-28 Cont ID  
Sent By cpuell Date 2023-03-28 Time 10:23 Rev Time 0.00
Received By cpuell Date 2023-03-28 Time 10:23 Sent To  
Notes
2023-03-28 10:24:02APPLICATION FORMS STATES 3201 BROADWAY, PLANS STATE
 3205 BROADWAY, IS THE WORK FOR THE NORTH OR THE SOUTH
 BUILDING, NO SITE PLAN PROVIDED, PLEASE CONTACT
 [email protected] OR CALL 561-805-6659 WITH
 RESPONCE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-05-22 Cont ID  
Sent By pvalenti Date 2023-05-22 Time 06:45 Rev Time 0.00
Received By pvalenti Date 2023-05-22 Time 06:44 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-05-19 Cont ID  
Sent By pvalenti Date 2023-05-19 Time 14:17 Rev Time 0.00
Received By pvalenti Date 2023-05-19 Time 14:17 Sent To  
Notes
2023-05-19 14:20:12PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 FAILED PLAN REVIEW DENIED:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 16:30 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 16:20 Sent To  
Notes
2023-04-03 16:30:48TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-05-22 Cont ID  
Sent By pvalenti Date 2023-05-22 Time 06:45 Rev Time 0.00
Received By pvalenti Date 2023-05-22 Time 06:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-19 Cont ID  
Sent By pvalenti Date 2023-05-19 Time 14:21 Rev Time 0.00
Received By pvalenti Date 2023-05-19 Time 14:20 Sent To  
Notes
2023-05-19 14:22:31PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 6) WHAT TYPE OF USE IS LOCATED AT THIS PROPERTY, THERE
 IS NO BUSINESS LICENSE FOR EITHER 3201 OR 3205
 BROADWAY?

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 17:06 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 16:22 Sent To  
Notes
2023-04-03 17:06:11 
 WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23031034
 ADD: 3201/ 3205 BROADWAY UNITS 7, 8, 9, 10, 11, 12, 14
 & 15
 CONT: ALDON RAY BOOKHARDT
 TEL: 561-822-8904
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 03/2023
 ACTION: DENIED
  
 1) PLEASE PROVIDE A OVERALL SITE PLAN WITH THE LOCATION
 OF THESE UNITS, ARE THEY ON THE FIRST FLOOR OR SECOND
 FLOOR. 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2) WITH THE FLOOR PLAN OF EACH UNIT AND THE DESCRIPTION
 GIVEN OF EACH UNIT AND DESCRIPTION OF WORK REPAIR
 DRYWALL/ BATHROOMS, IS THE DRYWALL REPLACEMENT CONFINED
 TO ALL WALLS AND CEILING OF THE LISTED UNITS. IT
 APPEARS THE TUB IS BEING REMOVED AND NEW SHOWER IN EACH
 OF THE LISTED UNITS. PLEASE PROVIDE ADDITIONAL
 INFORMATION. THERE ARE 8 UNITS BEING REMODELED AND THE
 DOLLAR AMOUNT SHOWN ON THE PERMIT APPLICATION OF
 $5,000.00 DOLLARS, THIS IS EXTREMELY LOW FOR THE SCOPE
 OF WORK.
  
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 3) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 4) WITH THE NEW SHOWER DRAIN IS THE OLD DRAIN TO BE
 USED OR NEW FLOOR PENETRATION. THROUGH-PENETRATIONS
 FIRESTOP SYSTEMS (HORIZONTAL ASSEMBLIES). IF A NEW
 FLOOR PENETRATION IS MADE FOR THE FUTURE SHOWER DRAIN,
 THEN YOU NEED TO SHOW COMPLIANCE WITH THE 2020 FBC-B
 SECTION 714.5.1.2. THROUGH-PENETRATIONS FIRESTOP
 SYSTEMS (HORIZONTAL ASSEMBLIES). THROUGH PENETRATIONS
 SHALL BE PROTECTED BY A THROUGH PENETRATION FIRESTOP
 SYSTEM INSTALLED IN ACCORDANCE WITH ASTM E814 OR UL
 1479. THE SYSTEM SHALL HAVE AN F RATING / T RATING OF
 NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED
 RATING OF THE FLOOR PENETRATED.
 5) IS THE BATHROOM FLOOR GOING TO BE REMOVED AND NEW
 FLOOR COVERING INSTALLED? IF SO WHAT MATERIAL. FLOOR
 INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 5A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 5B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 5C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE
 & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 OR
 5C) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 -PILL TEST (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253.
  
 6) WHAT TYPE OF USE IS LOCATED AT THIS PROPERTY, THERE
 IS NO BUSINESS LICENSE FOR EITHER 3201 OR 3205
 BROADWAY?
  
 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-15 Cont ID  
Sent By pleduc Date 2023-05-15 Time   Rev Time 0.00
Received By pleduc Date 2023-05-12 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-03-28 Cont ID  
Sent By pleduc Date 2023-03-28 Time   Rev Time 0.00
Received By pleduc Date 2023-03-28 Time 11:36 Sent To  
Notes
2023-03-28 11:55:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) PLEASE PROVIDE A DETAILED SCOPE OF WORK FOR THESE
 UNITS.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 THERE IS NO INDICATION OF WHAT IS EXISTING VS.
 PROPOSED.
  
 THERE IS NO PROPOSED OCCUPANCY CLASSIFICATION.
  
 THERE IS NO INDICATIONS OF SMOKE ALARM/FIRE ALARM.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK FOR THESE
 UNITS.
  
  
  
 2) THERE IS NO FLOOR PLAN OF THE 1ST & 2ND FLOORS
 INDICATING THE LOCATIONS OF THE ROOMS BEING REPAIRED.
  
 ARE THERE ANY UNITS THAT ARE NOT BEING REPAIRED?
  
 FOR THE RECORD, PLEASE PROVIDE A FLOOR PLAN INDICATING
 THE LOCATIONS OF THE ROOMS.
  
  
  
 3) THERE ARE NO INDICATIONS OF THE PROPOSED FLOOR
 FINISHES THAT INDICATE MEETING THE REQUIREMENTS PER
 NFPA
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
  
 IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE, NATURAL
 STONE TILE, CONCRETE TILES, SPEC SHEETS WOULD NOT BE
 REQUIRED.
  
 IS THE FLOORING BEING INSTALLED UNDER A SEPARATE
 PERMIT?
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
  
 4) THE APPLICATION INDICATES 3201 BROADWAY; HOWEVER,
 THE SUBMITTED PLAN SHEETS INDIATE 3205 BROADWAY.
  
 WHICH IS CORRECT AND PROVIDE FOR CORRECTIONS?
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-22 Cont ID  
Sent By pvalenti Date 2023-05-22 Time 06:46 Rev Time 0.00
Received By pvalenti Date 2023-05-22 Time 06:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-19 Cont ID  
Sent By pvalenti Date 2023-05-19 Time 14:26 Rev Time 0.00
Received By pvalenti Date 2023-05-11 Time 08:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-07 Cont ID  
Sent By rwbrown Date 2023-04-07 Time 06:28 Rev Time 0.00
Received By rwbrown Date 2023-03-27 Time 12:18 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 17:06 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 16:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-04-07 Cont ID  
Sent By rwbrown Date 2023-04-07 Time 06:26 Rev Time 0.00
Received By rwbrown Date 2023-04-07 Time 06:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-19 Cont ID  
Sent By pvalenti Date 2023-05-19 Time 14:07 Rev Time 0.00
Received By pvalenti Date 2023-05-19 Time 14:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-04-07 Cont ID  
Sent By rwbrown Date 2023-04-07 Time 06:28 Rev Time 0.00
Received By rwbrown Date 2023-04-07 Time 06:28 Sent To  
Notes
***NONE***