Plan Review Details - Permit 23031011
Plan Review Stops For Permit 23031011
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-04-20 Cont ID  
Sent By jbrooks Date 2023-04-20 Time 09:53 Rev Time 0.00
Received By jbrooks Date 2023-04-20 Time 07:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-03 Cont ID  
Sent By jbrooks Date 2023-04-03 Time 13:03 Rev Time 0.00
Received By jbrooks Date 2023-04-03 Time 09:01 Sent To  
Notes
2023-04-03 13:03:49JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL4595.10-R6 MAXIMUM DESIGN PRESSURE -93.5
 PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE
 REQUIREMENT OF -102 FOR EXPOSURE CATEGORY C AREAS WITH
 A GABLE ROOF; ROOF SLOPES 5/12-6/12 MEAN ROOF HEIGHT UP
 TO 15 FT. SELECT SYSTEM THAT MEETS OR EXCEEDS THIS
 REQUIREMENT. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING. SECOND REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-20 Cont ID  
Sent By jbrooks Date 2023-03-20 Time 14:04 Rev Time 0.00
Received By jbrooks Date 2023-03-20 Time 08:07 Sent To  
Notes
2023-03-20 14:04:16JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL4595.10-R6 MAXIMUM DESIGN PRESSURE -93.5
 PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE
 REQUIREMENT OF -102 FOR EXPOSURE CATEGORY C AREAS WITH
 A GABLE ROOF; ROOF SLOPES 5/12-6/12 MEAN ROOF HEIGHT UP
 TO 15 FT. SELECT SYSTEM THAT MEETS OR EXCEEDS THIS
 REQUIREMENT. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-20 Cont ID  
Sent By jbrooks Date 2023-04-20 Time 09:53 Rev Time 0.00
Received By jbrooks Date 2023-04-11 Time 11:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-03 Cont ID  
Sent By jbrooks Date 2023-04-03 Time 13:03 Rev Time 0.00
Received By jbrooks Date 2023-03-24 Time 07:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-20 Cont ID  
Sent By jbrooks Date 2023-03-20 Time 14:04 Rev Time 0.00
Received By jbrooks Date 2023-03-17 Time 10:32 Sent To  
Notes
***NONE***