Plan Review Details - Permit 23030889
Plan Review Stops For Permit 23030889
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-22 Cont ID  
Sent By cthroop Date 2023-03-22 Time 14:39 Rev Time 0.00
Received By cthroop Date 2023-03-22 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-16 Cont ID  
Sent By cthroop Date 2023-03-16 Time 14:07 Rev Time 0.00
Received By cthroop Date 2023-03-16 Time 13:47 Sent To  
Notes
2023-03-16 14:08:32APPROVAL OF THE BUILDING REVIEW IS PENDING APPROVAL OF
 THE SIGNATURE REVIEW. CT 2ND REQUEST

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-14 Cont ID  
Sent By cthroop Date 2023-03-14 Time 16:24 Rev Time 0.00
Received By cthroop Date 2023-03-14 Time 16:12 Sent To  
Notes
2023-03-14 16:25:06APPROVAL OF THE BUILDING REVIEW IS PENDING APPROVAL OF
 THE SIGNATURE REVIEW. CT

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-16 Cont ID  
Sent By pleduc Date 2023-03-16 Time   Rev Time 0.00
Received By pleduc Date 2023-03-16 Time 13:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-03-15 Cont ID  
Sent By pleduc Date 2023-03-15 Time   Rev Time 0.00
Received By pleduc Date 2023-03-15 Time 12:22 Sent To  
Notes
2023-03-15 12:27:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 FIRE HAS NO OBJECTION TO THE TENT INSTALLATION LIFE
 SAFETY REVIEW.
  
 1) THERE IS AN INDICATION OF THE TENT WITHIN THE
 ROADWAY.
  
 AN APPROVED MOT HAS NOT BEEN SUBMITTED THAT I AM AWARE
 OF.
  
 AS THIS TENT LOCATION MAY NEGATIVELY AFFECT EMERGENCY
 RESPONSE AN APPROVED MOT IN ADVANCE IS REQUIRED.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A COPY OF THE
 APPROVED MOT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-15 Cont ID  
Sent By lmarchan Date 2023-03-15 Time 16:49 Rev Time 0.00
Received By lmarchan Date 2023-03-14 Time 10:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-22 Cont ID  
Sent By cthroop Date 2023-03-22 Time 14:39 Rev Time 0.00
Received By cthroop Date 2023-03-22 Time 14:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-03-16 Cont ID  
Sent By cthroop Date 2023-03-16 Time 14:08 Rev Time 0.00
Received By cthroop Date 2023-03-16 Time 14:03 Sent To  
Notes
2023-03-16 14:09:242ND SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: TENT ANCHORING AND WIND LOAD CALC'S
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-14 Cont ID  
Sent By cthroop Date 2023-03-14 Time 16:22 Rev Time 0.00
Received By cthroop Date 2023-03-14 Time 16:22 Sent To  
Notes
2023-03-14 16:24:261ST SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: TENT ANCHORING AND WIND LOAD CALC'S
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  