| 2023-03-14 16:16:49 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT A DIMENSIONED DIAGRAM DRAWING OF THE ROOF. |
| | SHOW WHICH PARTS OF THE ROOF ARE WOOD AND WHICH ARE |
| | CONCRETE. PROVIDE THE AREAS OF EACH TYPE OF ROOF. SHOW |
| | THE LOCATIONS AND SIZES OF ALL EXISTING ROOF DRAINS AND |
| | SCUPPERS. SPECIFY THE LOCATION AND HEIGHTS OF ANY |
| | PARAPET WALLS. FBC 107.2.1 |
| | |
| | 2) PROVIDE FLASHING DETAILS OF THE PRAPET WALLS. FBC |
| | 1503 |
| | |
| | 3) SHOW THE SLOPES OF THE ROOFS ON THE DRAWINGS. FBC |
| | 1503 |
| | |
| | 4) THE W-30 ROOF SYSTEM ON PAGE 10 OF FL2533-R28 HAS A |
| | MAXIMUM DESIGN PRESSURE OF -60 PSF. THIS IS NOT |
| | ADEQUATE FOR A FLAT ROOF IN A LOCATION THAT HAS A 170 |
| | MPH VULT WIND SPEED AND EXPOSURE CATEGORY C. SUBMIT |
| | SIGNED AND SEALED ENHANCED FASTENING CALCULATIONS FOR |
| | MECHANICALLY FASTENED SYSTEMS THAT ALLOW THEM. SEE |
| | LIMITATION NUMBER 9 ON PAGE 3. FBC 107.2.1 |
| | |
| | 5) THE VALUE OF $6,004.00 APPEARS THAT IT MIGHT BE LOW |
| | DEPENDING ON THE AREA OF ROOF THAT IS BEING REPLACED. |
| | PROVIDE A COMPLETE SCOPE OF WORK. BUILDING PERMIT |
| | VALUATION. FOR PERMITTING PURPOSES, VALUATION OF FBC |
| | 109.3 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |