| Plan Review Stops For Permit 23030823 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-24 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-24 |
Time |
08:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-19 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-19 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2023-04-19 09:23:06 | | | | PREVIOUS SIGNATURE COMMENT STILL APPLIES: | | | | | | SHEETS NON DIGITALLY SIGNED AND SEALED: | | | | | | T000 CLARIFY THE GRAPHIC SO WE CAN READ THE INDEX- | | | SP100 | | | EX100 | | | EX101.0 | | | EX200.0 | | | SP101 | | | A100 | | | A100 NUMBER IS DUPLICATED PLEASE ADD PROPER NUMBER FOR | | | THE SHEET AND UPDATE INDEX PROPOSED ROOF PLAN | | | A200 | | | A201 | | | A600 | | | A601 | | | | | | PLEASE UPLOAD AND RESUBMIT. | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-30 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-30 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2023-03-30 15:14:37 | REF TO LATEST SIGNATURE COMMENTS REV 2. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-17 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-17 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-17 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2023-03-17 11:07:56 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23030823 | | | | | | REVIEWED: MARCH 17, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | AS PER SECTION 107.2.1 | | | PROVIDE FULL SET OF DRAWING FOR THE SCOPE OF WORK AS | | | PER DRAWIG INDEX. | | | MAKE SURE THE DRAWING INDEX IS EASY TO READ. | | | PROVIDE ALL LEVELS ON FLOOR PLANS AND ELEVATIONS | | | SHOW EXISTING AND PROPOSED ELEVATIONS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
jcooley |
Date |
2023-04-26 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
jcooley |
Date |
2023-04-26 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-16 |
|
|
Cont ID |
|
| Sent By |
jcooley |
Date |
2023-04-16 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
jcooley |
Date |
2023-04-16 |
Time |
07:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-03-27 |
|
|
Cont ID |
|
| Sent By |
jcooley |
Date |
2023-03-27 |
Time |
18:42 |
Rev Time |
0.00 |
| Received By |
jcooley |
Date |
2023-03-27 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2023-03-27 18:45:34 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY | | | THE ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT | | | ANY ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE | | | THAT ON PLAN. FS 471.003(2)(H); 471.025; WPB FBC | | | 107.2.1, 107.3.5 | | | | | | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC | | | 107.3.5; FBC RE E3706.2, E3902 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | JONATHAN COOLEY | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | (561)345-4377 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2023-05-04 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
2023-05-04 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
2023-05-04 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-26 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-26 |
Time |
07:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-04-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-05 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-05 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2023-04-05 08:08:10 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 23030823 | | | 4/4/2023 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1: THE COMBUSTION AIR CALCULATIONS CANNOT BE | | | VERIFIED BECAUSE THE ROOM DIMENSIONS ARE NOT SHOWN ON | | | THE FLOOR PLANS- SEC. G2407.5.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2023-05-15 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-05-15 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-05-05 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-05-04 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-05-04 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-04-24 |
Time |
08:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-04-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-04-20 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-04-19 |
Time |
12:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-04-17 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-03-29 |
Time |
11:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-29 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-03-29 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-14 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-06-02 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-06-02 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-05-18 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2023-05-31 12:38:58 | RECEIPT MU-2023-022401-0000 PAID - $475.63 AO | | 2023-05-18 14:33:44 | EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-30 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-30 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2023-03-30 15:16:44 | 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2023-05-09 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-09 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-05-09 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-24 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-24 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2023-04-24 11:43:03 | 1ST REVIEW FMC | | | PERMIT: 23030823 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENERGY CALCULATIONS SUBMITTED ARE FOR 2 | | | MECHANICAL SYSTEMS, 1- KITCHEN DINING ROOMS; SYSTEM 2- | | | MASTER SUITE. THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS ARE FOR 4 SYSTEMS. THE GARAGE IN THE | | | EQUIPMENT WAS NOT INCLUDED IN THE ENERGY CALCULATIONS. | | | PROVIDE ENERGY CALCULATIONS FOR THE GARAGE AND INCLUDE | | | THE GARAGE DOOR. FRC R101.5.1.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-06 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-06 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2023-04-06 11:45:52 | 1ST REVIEW FMC | | | PERMIT: 23030823 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT. | | | FEC R101.5.1.1.1 | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS PROJECT. FEC R403.7.1 | | | 3) THE DESIGNERS SEAL APPEARS TO BE A COPY. PROVIDE | | | ORIGINAL MECHANICAL DOCUMENTS THAT INCLUDE THE | | | DESIGNERS ORIGINAL DIGITAL SIGNATURE. FS 471/481 | | | 4) SHEET M-1: REMOVE THE RETURN AIR DUCT AND GRILL FOR | | | THE MASTER CLOSET AS RETURN AIR CANNOT COME FROM A | | | CLOSET. FRC M1602.2 NUMBER 4 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-16 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-16 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2023-03-16 10:11:36 | PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS PROJECT. | | | FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
N |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-30 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-30 |
Time |
15:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-04-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-26 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-26 |
Time |
07:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-05 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-04 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-20 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-20 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2023-03-20 17:24:40 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23030823 | | | 3/20/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A100: PROVIDE A SANITARY DRAINAGE AND VENT | | | ISOMETRIC DRAWING FOR THE NEW MASTER BATHROOM PLUMBING- | | | SEC. 107.3.5.3 WPB. | | | | | | 2) A100: PLEASE PROVIDE A PLUMBING SCOPE OF WORK FOR | | | THE EXISTING KITCHEN AND BATH FIXTURES- SEC. 107.2.1 | | | WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-17 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-17 |
Time |
10:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-24 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-24 |
Time |
08:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-19 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-19 |
Time |
09:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-30 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-30 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2023-03-30 15:13:36 | SURVEY HAS VALID SIGNED AND SEALED DIGITAL VERIFIABLE | | | SIGNATURE. | | | ELEV CERTIFICATE IS GOOD, | | | STRUCTURAL SHEETS - GOOD AS WELL. | | | PLUMBING SHEETS- GOOD ALSO. | | | ARCHITECTURAL AND CIVIL ARE NOT: DENIED | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-03-17 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-17 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-17 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2023-03-17 11:10:28 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23030823 | | | | | | REVIEWED: MARCH 17, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | PLAN BY FL. LICENSES ENGINEERS OR ARCHITECTS THAT ARE | | | SUBMITTED ELECTRONICALLY SHALL BEAR VERIFIABLE, | | | ORIGINAL DIGITAL SIGNATURE AND SEALS- FL STATUTE | | | 471.025 AND SEC 61G15-23.005 FLORIDA ADMINISTRATIVE | | | CODE. | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-05-12 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-05-12 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-05-12 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2023-05-12 09:37:03 | THERE WILL BE A HOLD PLACED ON THE PERMIT FOR THE | | | LANDSCAPE PERMIT REQUIREMENT TO BE MET PRIOR TO THE | | | ISSUANCE OF THE CO. | | | THEREFORE, THE FINAL WILL NOT BE APPROVED WITHOUT | | | CONFIRMATION THAT THE LANDSCAPE PERMIT HAS BEEN ISSUED | | | AND THAT ITS INSPECTION HAS BEEN APPROVED. | | | | | | (CONDITIONAL PERMIT ATTACHED TO THIS PERMIT) | | | | | | REVIEWED BY: | | | GAISHA (ANNE) VOLCY | | | PLANNER | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2023-05-04 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-05-04 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-05-04 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2023-05-04 10:07:57 | SEPARATE PERMIT REQUIRED FOR ALL APPLICABLE: | | | FENCE/WALL, DRIVEWAY, POOL, GENERATOR, | | | MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION, LANDSCAPE, | | | ACCESSORY STRUCTURE, OTHER | | | | | | | | | SUBMITTAL OK. LANDSCAPE PERMIT REQUIRED. | | | THE VALUE OF THE CONSTRUCTION ($500,000.00) EXCEEDS 50% | | | OF THE STRUCTURE'S VALUE ($71,443.00) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. SUBMIT A SEPARATE LANDSCAPE | | | PERMIT WITH PLANS SHOWING MATERIAL EXISTING ON SITE OR | | | ANY ADDITION OF TREES OR SHRUBS TO BRING THE SITE INTO | | | CONFORMITY | | | | | | REASON: | | | FOR THE MAJORITY OF PROPERTIES, THE EXISTING LANDSCAPE | | | IS NON-CONFORMING. THE MINIMAL CHARGE FOR A PERMIT | | | VALUE OF LESS THAN $2500.00 IS $125.00. THIS ALLOWS FOR | | | STAFF TO REVIEW THE EXISTING MATERIAL ON SITE TO VERIFY | | | THE REQUIREMENTS ARE MET AND ALSO ALLOWS FOR AN | | | INSPECTION TO CONFIRM THE SITE IS IN COMPLIANCE AT THE | | | CONCLUSION OF THE PROJECT. | | | | | | | | | **** REVIEWD BY **** | | | GAISHA (ANNE CLERISSE) VOLCY | | | PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
AVolcy |
Date |
2023-04-17 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-04-17 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2023-04-17 16:32:24 | SEPARATE PERMIT REQUIRED FOR ALL APPLICABLE: | | | FENCE/WALL, DRIVEWAY, POOL, GENERATOR, | | | MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION, LANDSCAPE, | | | ACCESSORY STRUCTURE, OTHER | | | | | | **** REVIEWD BY **** | | | GAISHA (ANNE CLERISSE) VOLCY | | | PLANNER | | | [email protected] | | | |
|
|