| Plan Review Stops For Permit 23030611 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-07-07 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-07 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-07 |
Time |
16:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-17 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-17 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-17 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2023-03-17 08:59:02 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23030611 | | | | | | REVIEWED: MARCH 17, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | AS PER SECTION 107.2.1 | | | PROVIDE SUPPORTING DOCUMENT FOR NOA OR FPA APPROVED FOR | | | ALL NEW WINDOWS AND DOORS, PRESSURE CALCULATION | | | ACCORDING TO ZONE "D" | | | INDICATE ALL FLOOR ELEVATIONS ON EXISITING AND PROPOSED | | | PLANS SAME FOR ALL ELEVATION AND SECTIONS THROUGHOUT | | | THE SET OF DRAWINGS FOR ALL DISCIPLINES. | | | SURVEY SHOULD BE DIGITALLY SIGNED AND SEALED- PLEASE | | | INDICATE FLOOR ELEVATIONS ON SURVEY. | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-16 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-16 |
Time |
10:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2023-06-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-23 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-23 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-14 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-14 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2023-03-14 11:28:44 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 23030611 | | | 3/14/2023 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-2.1: THE GAS RISER DRAWING IS INCOMPLETE, | | | AND ALSO NEEDS CORRECTIONS. PLEASE PROVIDE THE | | | FOLLOWING ITEMS. | | | A) TOTAL DEVELOPED LENGTHS OF THE 2 PSI AND THE LOW | | | PRESSURE PIPING SYSTEMS- SEC. G2413.4.1 FBC RES. | | | B) GALV. PIPE SIZES FROM THE PRV OUTLETS TO THE | | | GENERATOR AND POOL HEATER- SEC. G2413.3 | | | C) BASED ON THE LOW PRESSURE TABLE CALLED OUT- TABLE | | | 402.4(3) FBC FG- THE 3/4-INCH GALV. PIPE FROM THE PRV | | | TO THE TEE FOR TWH-1 & 2 MUST BE INCREASED TO 1-INCH, | | | AND THE 1/2-INCH BRANCHES FROM THE TEE TO THE WATER | | | HEATERS SHALL BE INCREASED TO 3/4-INCH. | | | D) PLACE NOTES TO INDICATE SEPARATE PERMITS ARE | | | REQUIRED FOR THE GENERATOR AND THE POOL HEATER- SEC. | | | 107.2.1 WPB. | | | | | | 2) P-2.1: SHOW THE CLEARANCE DISTANCE MEASUREMENTS FOR | | | THE GAS WATER HEATER EXHAUST OUTLETS TO THE GAS WATER | | | HEATER EXHAUST CLEARANCES FROM OPENINGS INTO THE | | | BUILDING SUCH AS OPERABLE DOORS AND WINDOWS, AND OTHER | | | AIR INTAKES SUCH AS SOFFIT VENTS- SEC. G2427.8 & | | | G2448.1 FBC RES. PLEASE NOTE A MINIMUM OF 4FT. | | | HORIZONTAL CLEARANCE IS TYPICALLY REQUIRED. | | | | | | 3) P-2.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | RANGE- SEC. G2407.1 FBC RES. PLEASE NOTE IF USING THE | | | STANDARD METHOD OF INDOOR AIR VOLUME, A MINIMUM OF 7500 | | | CU. FT. IS REQUIRED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-07-17 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-07-17 |
Time |
14:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-03-31 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-03-31 |
Time |
07:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-07-18 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-07-18 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-06-22 |
Time |
08:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-03 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-13 |
Time |
09:51 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-06-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2023-06-29 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2023-06-29 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-14 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-14 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2023-03-14 08:18:28 | 1ST REVIEW FMC | | | PERMIT: 23030611 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE GARAGE CONVERSION IS A CHANGE OF USE AND | | | THEREFORE AN ENERGY CALCULATION IS REQUIRED. FEC | | | R101.5.1.1.1 | | | | | | 2) IDENTIFY THE MECHANICAL SYSTEM ON THE FIRST FLOOR | | | AND SHOW ITS LOCATION ON THE DRAWING. FBC 107.3.5 | | | | | | 3) SHOW THE OPERABLE WINDOW IN THE BATHROOM ON THE MAIN | | | HOUSE 1ST FLOOR MEETS THE AGGREGATE AREA OF 3 SQUARE | | | FEET TO EXEMPT AN EXHAUST FAN. FRC R303.3 | | | | | | 4) PROVIDE DETAILS FOR THE KITCHEN RANGE. IS THIS A | | | BROILER COOKTOP? IS THERE TO BE A HOOD ABOVE THIS | | | COOKTOP? IF SO, PROVIDE THE CFMS OF THE HOOD MOTOR. FRC | | | M1503.4 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
P |
Date |
2023-07-03 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2023-07-03 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2023-07-03 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2023-07-03 15:44:02 | OK PROVIDED THE FLOOD BARRIER IS INSTALLED AT THE | | | OPENINGS IN THE SITE WALL IN ACCORDANCE WITH THE | | | SUBMITTED HAMMERHEAD ALUMINUM FLOOD PLANKS | | | SPECIFICATION AND DETAILS IN ORDER TO MEET THE | | | FOLLOWING REQUIREMENT SET BY THE CONSTRUCTION BOARD OF | | | ADJUSTMENT AND APEALS (CBAA). | | | | | | AT THE CBAA MEETING ON 4/20/23, THE BOARD GRANTED THE | | | APPLICANT'S APPEAL TO ALLOW THE STRUCTURE TO REMAIN AT | | | THE CURRENT ELEVATION PROVIDED THE PROPERTY OWNER AND | | | ARCHITECT PROVIDE FLOOD MITGATION MEASURES TO THE | | | GREATEST EXTENT POSSIBLE WITHOUT LIFTING THE STRUCTURE. | | | SUCH MEASURES WOULD INCLUDE A FLOOD BARRIER SITE WALL | | | WITH FLOOD-PROOF BARRIERS AT THE GATES TO PREVENT | | | INUNDATION WITH FLOOD WATER UP TO AN ELEVATION OF 8.0 | | | FEET NAVD WHICH IS 2.0 FEET ABOVE BASE FLOOD ELEVATION. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2023-04-20 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2023-04-20 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2023-04-20 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2023-04-20 16:02:29 | STATUS UPDATE FROM PREVIOUS NFIP REVIEW. | | | | | | AT THE CONSTRUCTION BOARD OF ADJUSTMENT AND APEALS | | | (CBAA) MEETING ON 4/20/23, THE BOARD GRANTED THE | | | APPLICANT'S APPEAL TO ALLOW THE STRUCTURE TO REMAIN AT | | | THE CURRENT ELEVATION PROVIDED THE PROPERTY OWNER AND | | | ARCHITECT PROVIDE FLOOD MITGATION MEASURES TO THE | | | GREATEST EXTENT POSSIBLE WITHOUT LIFTING THE STRUCTURE. | | | SUCH MEASURES WOULD INCLUDE A FLOOD BARRIER SITE WALL | | | WITH FLOOD-PROOF BARRIERS AT THE GATES TO PREVENT | | | INUNDATION WITH FLOOD WATER UP TO AN ELEVATION OF 8.0 | | | FEET NAVD WHICH IS 2.0 FEET ABOVE BASE FLOOD ELEVATION. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2023-03-17 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2023-03-17 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2023-03-17 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2023-03-17 09:26:48 | PROVIDE ELEVATION CERTIFICATE FOR EXISTING BUILDING. | | | DYLAN BATTLES | | | 561-805-6718 | | | [email protected] | | | | | | THE PROPOSED WORK WOULD EXCEED THE THRESHOLD FOR | | | SUBSTANTIAL IMPROVEMENT. | | | SINCE THIS IS A CONTRIBUTING HISTORICAL PROPERTY YOU | | | NAY APPLY FOR RELEF FROM OUR CONSTRUCTION BOARD OF | | | ADJUSTMENT AND APPEALS. | | | PLEASE CONTACT: | | | KATHY PERRE | | | PH: 561-805-6682 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-06-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-23 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-23 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-14 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-14 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-07-07 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-07 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-07 |
Time |
16:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-04-03 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-04-03 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2023-04-03 16:57:19 | SIGNATURE REVIEW: | | | | | | 1- DRAWING A-4 IS MISSING THE DIGITAL SIGNATURE AS | | | REQUIRED BY CHAPTER 481 F.S. WHEN SUBMITTING | | | DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS. NEED TO SUBMIT | | | DRAWINGS ELECTRONICALLY WITH VERIFIABLE DIGITAL | | | SIGNATURE. | | | | | | ARCHITECTS | | | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
|
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-16 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-16 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2023-03-16 10:37:20 | ALL TRADES PASSED SIGNATURES-PASSED | | 2023-03-14 10:58:05 | PLUMBING AND GAS (P) PLANS PASSED/CC | | 2023-03-14 08:19:09 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-07-17 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-07-17 |
Time |
14:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-31 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-03-31 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-03-31 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2023-03-31 07:56:25 | REQUIRES SUBMITTAL OF SEPERATE LANDSCAPE PERMIT |
|
|