Plan Review Details - Permit 23030592
Plan Review Stops For Permit 23030592
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-04-06 Cont ID  
Sent By rmcphers Date 2023-04-06 Time 10:39 Rev Time 0.00
Received By rmcphers Date 2023-04-06 Time 10:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-04 Cont ID  
Sent By rmcphers Date 2023-04-04 Time 07:53 Rev Time 0.00
Received By rmcphers Date 2023-04-04 Time 07:53 Sent To  
Notes
2023-04-04 07:57:45REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE ENGINEERING PROVIDED FROM FORENSIC ENGINEERING
 CONSULTANTS INC - THE DISCRIPTION OF THE PRODUCT
 APPROVAL PAGE AND DESIGN WIND PRESSURE DOES NOT MATCH -
 ENGINEERING SAYS PAGE 7 OF 8 AND WIND DESIGN PRESSURE
 OF (-67.5) - PRODUCT APPROVAL SHOWS PAGE 5 OF 8 WIND
 DESIGN PRESSURE OF (-45) - THE TWO SHOULD MATCH.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-29 Cont ID  
Sent By rmcphers Date 2023-03-29 Time 07:50 Rev Time 0.00
Received By rmcphers Date 2023-03-29 Time 07:50 Sent To  
Notes
2023-03-29 07:55:12REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-45) -
 SEE GENERAL LIMITATION NUMBER 7 ON THE PRODUCT
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-24 Cont ID  
Sent By rmcphers Date 2023-03-24 Time 08:11 Rev Time 0.00
Received By rmcphers Date 2023-03-24 Time 08:08 Sent To  
Notes
2023-03-24 08:11:48REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE
 PRODUCT APPROVAL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-06 Cont ID  
Sent By rmcphers Date 2023-04-06 Time 10:39 Rev Time 0.00
Received By rmcphers Date 2023-04-05 Time 17:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-04 Cont ID  
Sent By rmcphers Date 2023-04-04 Time 07:58 Rev Time 0.00
Received By rmcphers Date 2023-04-03 Time 10:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-29 Cont ID  
Sent By rmcphers Date 2023-03-29 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2023-03-28 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-24 Cont ID  
Sent By rmcphers Date 2023-03-24 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2023-03-22 Time 12:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-04 Cont ID  
Sent By rmcphers Date 2023-04-04 Time 07:58 Rev Time 0.00
Received By rmcphers Date 2023-04-04 Time 07:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-03-24 Cont ID  
Sent By rmcphers Date 2023-03-24 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2023-03-24 Time 08:11 Sent To  
Notes
***NONE***