| 2023-04-04 08:56:37 | |
| | WEST PALM BEACH DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 23030575 |
| | W. P. B. PERMIT: 22090229 |
| | ADD: 1210 PALM BEACH LAKES BLVD. |
| | CONT: 87 CONSTRUCTION & ENGINEERING |
| | TEL: 786-247-1148 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. APRIL 04TH/ 2023 |
| | ACTION: DENIED |
| | |
| | 1) THIS REVISION: 23030575 IS STATED ON THE PLAN TO |
| | REMOVE AN EXISTING NONBEARING CMU WALL AND REPLACE THE |
| | WALL WITH NEW WOOD FRAMING. THE FLOOR PLAN DOES NOT |
| | STATE WHICH OF THE THREE WALLS THAT SURROUND THE TUB |
| | ARE THE NONBEARING CMU WALLS TO BE REMOVED. IN ALL |
| | CASES THERE IS AT LEAST ONE WALL ADJACENT TO THE TUB |
| | WHICH IS A TENANT SEPARATION WALL THAT REQUIRES |
| | COMPLIANCE WITH SECTION 420.2 DWELLING UNITS CONTIGUOUS |
| | TO THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS |
| | FIRE PARTITIONS IN ACCORDANCE WITH SECTION 708. SECTION |
| | 708.3 FIRE PARTITIONS SHALL HAVE A FIRE RESISTANCE |
| | RATING OF NOT LESS THAN 1 HOUR. PLEASE PROVIDE EITHER |
| | THE UL LISTING AND ASSEMBLY OR GYPSUM ASSOCIATION FIRE |
| | ASSEMBLY. |
| | |
| | 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |