Plan Review Details - Permit 23030435
Plan Review Stops For Permit 23030435
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-21 Cont ID  
Sent By rmcphers Date 2023-07-21 Time 15:54 Rev Time 0.00
Received By rmcphers Date 2023-07-21 Time 15:54 Sent To  
Notes
2023-07-21 15:55:07CONCRETE FENCE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE WIND DESIGN DATA ON DRAWING C2 SHOWS RISK
 CATEGORY II WITH WIND SPEED AT 145MPH - WIND SPEED
 NEEDS TO BE 150MPH FOR A RISK CATEGORY I AND 170MPH FOR
 A RISK CATEGORY II SEE FBC WPB SECTION 120
  
 2) THE FOUNDATIONS ARE SHOWN FOR THE COLUMNS - PLEASE
 SHOW THE FOUNDATION FOR THE BLOCK WALL IN BETWEEN THE
 COLUMNS - FBC WPB 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-08 Cont ID  
Sent By rmcphers Date 2023-06-08 Time 15:34 Rev Time 0.00
Received By rmcphers Date 2023-06-08 Time 15:27 Sent To  
Notes
2023-06-08 15:34:38CONCRETE FENCE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE WIND DESIGN DATA ON DRAWING C2 SHOWS RISK
 CATEGORY II WITH WIND SPEED AT 145MPH - WIND SPEED
 NEEDS TO BE 150MPH FOR A RISK CATEGORY I AND 170MPH FOR
 A RISK CATEGORY II SEE FBC WPB SECTION 120
  
 2) THE FOUNDATIONS ARE SHOWN FOR THE COLUMNS - PLEASE
 SHOW THE FOUNDATION FOR THE BLOCK WALL IN BETWEEN THE
 COLUMNS - FBC WPB 107.2.1
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-21 Cont ID  
Sent By pleduc Date 2023-07-21 Time   Rev Time 0.00
Received By pleduc Date 2023-07-21 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-23 Cont ID  
Sent By pleduc Date 2023-05-23 Time   Rev Time 0.00
Received By pleduc Date 2023-05-23 Time 10:39 Sent To  
Notes
2023-05-23 10:48:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF A 6FT BRICK FENCE WALL
 THAT APPEARS TO BEGIN AT THE APT COMPLEX ENTRY/EXIT
 POINT, HOWEVER, THERE IS NO INDICATION OF THE DIMENSION
 OF THE WIDTH OF THE OPENING AT THAT ENTRY /EXIT POINT.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC
 DIMENSION AND/OR THE SPECIFIC LOCATION OF WHERE THE
 FENCE WALL BEGINS ON EACH SIDE OF THE ENTRY/EXIT POINT.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aoliver Date 2023-07-20 Time 14:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-14 Cont ID  
Sent By lngelman Date 2023-06-14 Time 12:44 Rev Time 0.00
Received By lngelman Date 2023-05-19 Time 16:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-21 Cont ID  
Sent By rmcphers Date 2023-07-21 Time 15:55 Rev Time 0.00
Received By rmcphers Date 2023-07-21 Time 15:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-08 Cont ID  
Sent By rmcphers Date 2023-06-08 Time 15:35 Rev Time 0.00
Received By rmcphers Date 2023-06-08 Time 15:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-06-14 Cont ID  
Sent By lgelman Date 2023-06-14 Time 12:44 Rev Time 0.00
Received By lngelman Date 2023-06-14 Time 12:37 Sent To  
Notes
2023-06-14 12:44:40SUBMITTED PLANS ARE NOT SUFFICIENT FOR ZONING REVIEW,
 LOCATION OF BRICK WALL SHOULD BE REFERENCED WITH A
 THICKER LINE TO DIFFERENTIATE FROM SETBACKS, RIGHT OF
 WAY, PROPERTY LINES AN SECURITY FENCE. PROVIDED PLANS
 HAVE TOO MANY LINES THAT OVERLAP AND NEED TO BE
 LEGIBLE.
  
 WALLS OR FENCES MUST CLEAR ALL EASEMENTS OF RECORDS.
 PROVIDE EASEMENT CONSENT FORM IF FENCING/WALLS ENCROACH
 ONTO UTILITY EASEMENT ON SOUTH PROPERTY LINE.
  
 ****
 REVIEWED BY
  
 LINDSEY GELMAN
 561-822-1275
 [email protected]