Plan Review Details - Permit 23030377
Plan Review Stops For Permit 23030377
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-06 Cont ID  
Sent By rmcdouga Date 2023-06-06 Time 16:31 Rev Time 0.00
Received By rmcdouga Date 2023-06-06 Time 16:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By rmcdouga Date 2023-04-04 Time 14:09 Rev Time 0.00
Received By rmcdouga Date 2023-04-04 Time 14:09 Sent To  
Notes
2023-04-04 14:09:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 PROPOSED GENERATOR. FBC AMENDMENTS 107.2.1
  
 2) SUBMIT SIGNED AND SEALED GENERATOR PAD DRAWINGS WITH
 GENERATOR TO PAD ANCHORING DETAILS FOR WIND LOADS. FBC
 1601
  
 3) PROVIDE A SITE PLAN THAT SPECIFIES THE LOCATION OF
 THE PROPOSED GENERATOR. FBC 107.2.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-06-05 Cont ID  
Sent By rperdomo Date 2023-06-05 Time 13:05 Rev Time 0.00
Received By rperdomo Date 2023-06-05 Time 12:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-03-21 Cont ID  
Sent By rperdomo Date 2023-03-21 Time 12:53 Rev Time 0.00
Received By rperdomo Date 2023-03-21 Time 12:34 Sent To  
Notes
2023-03-21 12:53:56FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE GENERATOR AND ATS SPECS. FBC 107.3.5
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-26 Cont ID  
Sent By pleduc Date 2023-05-26 Time   Rev Time 0.00
Received By pleduc Date 2023-05-26 Time 09:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-03-09 Cont ID  
Sent By cwalker Date 2023-03-09 Time   Rev Time  
Received By cwalker Date 2023-03-09 Time   Sent To  
Notes
2023-03-09 10:59:50FIRE REVIEW COMMENTS:
  
 THIS SUBMITTAL WAS REVIEWED AND FAILED DUE TO A LACK OF
 SUFFICIENT INFORMATION FOR A PROPER CODE REVIEW.
 PROVIDE DOCUMENTATION ON THE TYPE AND SIZE OF GENERATOR
 TO BE INSTALLED, AUTOMATIC TRANSFER, TYPE OF FUEL,
 DISTANCE TO BUILDINGS OR BUILDING OPENINGS, AND ANY
 OTHER ITEM THAT WILL INDICATE THE INSTALLATION COMPLIES
 WITH NFPA 110, NFPA 37, NFPA 70 AND ANY OTHER
 APPLICABLE CODE. NFPA 1, 11.7
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-07 Cont ID  
Sent By dbattles Date 2023-06-07 Time 15:54 Rev Time 0.00
Received By dbattles Date 2023-05-25 Time 08:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-04 Cont ID  
Sent By rmcdouga Date 2023-04-04 Time 14:14 Rev Time 0.00
Received By rmcdouga Date 2023-03-08 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2023-06-07 Cont ID  
Sent By dbattles Date 2023-06-07 Time 15:54 Rev Time 0.00
Received By dbattles Date 2023-06-07 Time 15:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-13 Cont ID  
Sent By medwards Date 2023-03-13 Time 15:14 Rev Time 0.00
Received By medwards Date 2023-03-13 Time 15:14 Sent To  
Notes
2023-03-13 15:15:10NO MECHANICAL WORK SHOWN FOR THIS PROJECT. PROVIDE THE
 GENERATOR SPECS AND LOCATION. FBC 107.3.5

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-06 Cont ID  
Sent By rmcdouga Date 2023-06-06 Time 16:31 Rev Time 0.00
Received By rmcdouga Date 2023-06-06 Time 16:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By rmcdouga Date 2023-04-04 Time 14:14 Rev Time 0.00
Received By rmcdouga Date 2023-04-04 Time 14:14 Sent To  
Notes
2023-04-04 14:14:35THE CIVIL PLANS HAVE NOT BEEN DIGITALLY SIGNED BY THE
 ENGINEER LISTED IN THE TITLE BLOCKS OF THE DRAWINGS.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 FS 481 & FAC 61G1 OR FS 471 & FAC 61G15

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-17 Cont ID  
Sent By kdefranc Date 2023-04-17 Time 13:40 Rev Time 0.00
Received By kdefranc Date 2023-04-17 Time 13:39 Sent To  
Notes
2023-04-17 13:40:174/17/23 ??? PASSED
  
 REVIEW COMMENT TO BE ADDRESSED:
 1. PLEASE PROVIDE THE APPROVED SITE PLAN (SHEET NUMBER
 SP101 ASSOCIATED WITH THE MASTER PERMIT # 21090266) AND
 IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF THE
 PROPOSED BACK UP GENERATOR. [SATISFIED]
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-14 Cont ID  
Sent By kdefranc Date 2023-03-14 Time 12:57 Rev Time 0.00
Received By kdefranc Date 2023-03-14 Time 12:56 Sent To  
Notes
2023-03-14 12:56:483/14/23 ??? FAILED
  
 REVIEW COMMENT TO BE ADDRESSED:
 1. PLEASE PROVIDE THE APPROVED SITE PLAN (SHEET NUMBER
 SP101 ASSOCIATED WITH THE MASTER PERMIT # 21090266) AND
 IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF THE
 PROPOSED BACK UP GENERATOR.
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  