Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-26 Cont ID  
Sent By rmcphers Date 2023-04-26 Time 11:42 Rev Time 0.00
Received By rmcphers Date 2023-04-26 Time 11:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-24 Cont ID  
Sent By rmcphers Date 2023-03-24 Time 14:32 Rev Time 0.00
Received By rmcphers Date 2023-03-24 Time 14:26 Sent To  
Notes
2023-03-24 14:32:47ROOF TOP GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE HEIGHT OF THE PARAPET WALL - FBC
 1015.6 MECHANICAL EQUIPMENT, SYSTEMS AND DEVICES.
 GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-03-06 Cont ID  
Sent By jleahy Date 2023-03-06 Time 08:33 Rev Time 0.00
Received By jleahy Date 2023-03-06 Time 08:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-27 Cont ID  
Sent By pleduc Date 2023-04-27 Time   Rev Time 0.00
Received By pleduc Date 2023-04-27 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-03-06 Cont ID  
Sent By pleduc Date 2023-03-06 Time   Rev Time 0.00
Received By pleduc Date 2023-03-06 Time 11:02 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2023-03-27 Cont ID  
Sent By ccole Date 2023-03-27 Time 08:10 Rev Time 0.00
Received By ccole Date 2023-03-27 Time 07:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-17 Cont ID  
Sent By aoliver Date 2023-05-17 Time 16:34 Rev Time 0.00
Received By aoliver Date 2023-04-25 Time 15:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-12 Cont ID  
Sent By lmarchan Date 2023-04-12 Time 08:41 Rev Time 0.00
Received By lmarchan Date 2023-03-03 Time 08:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2023-03-27 Cont ID  
Sent By medwards Date 2023-03-27 Time 08:43 Rev Time 0.00
Received By medwards Date 2023-03-27 Time 08:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-03-27 Cont ID  
Sent By ccole Date 2023-03-27 Time 08:10 Rev Time 0.00
Received By ccole Date 2023-03-27 Time 07:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-26 Cont ID  
Sent By rmcphers Date 2023-04-26 Time 11:43 Rev Time 0.00
Received By rmcphers Date 2023-04-26 Time 11:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-24 Cont ID  
Sent By rmcphers Date 2023-03-24 Time 14:34 Rev Time 0.00
Received By rmcphers Date 2023-03-24 Time 14:34 Sent To  
Notes
2023-03-06 08:34:22ELECTRICAL PAGES SIGNATURES ARE APPROVED JLEAHY

Review Stop Z ZONING
Rev No 2 Status P Date 2023-05-17 Cont ID  
Sent By eschneid Date 2023-05-17 Time 15:39 Rev Time 0.25
Received By eschneid Date 2023-05-17 Time 15:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-04-11 Cont ID  
Sent By eschneid Date 2023-04-11 Time 14:24 Rev Time 0.25
Received By eschneid Date 2023-04-11 Time 14:19 Sent To  
Notes
2023-04-11 14:29:22FAILED
  
 THE CITYPLACE DEVELOPMENT REGULATIONS REQUIRE THE
 SCREENING OF ROOFTOP MECHANICAL EQUIPMENT. PROVIDE THE
 HEIGHT OF THE GENERATOR PLUS THE MOUNTING RACK FROM THE
 ROOF DECK AND THE HEIGHT OF THE PARAPET WALL FROM THE
 ROOF DECK TO VERIFY THAT THE PARAPET HEIGHT EXCEEDS THE
 HEIGHT OF THE TOP OF THE GENERATOR. .WHILE SHEET A-5
 APPEARS TO SHOW THE PARAPET EXCEEDING THE GENERATOR,
 PLEASE PROVIDE THE DIMENSIONS.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]