| Plan Review Stops For Permit 23030346 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2023-03-29 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-29 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-29 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-10 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-10 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2023-03-10 11:42:40 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23030346 | | | | | | REVIEWED: MARCH 10, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | ASBESTOS REVIEW: | | | FAILED PLAN REVIEW: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | | ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION | | | -RENOVATION.HTML | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-04-07 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-07 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-07 |
Time |
08:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-03-29 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-29 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-29 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2023-03-29 14:32:55 | SHEET A1, A2, A3, E1 | | | ARE NOT DIGITALLY SIGNED AND SEALED- REFER TO PREVIOUS | | | SIGNATURE COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-10 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-10 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2023-03-10 11:44:41 | SEE SIGNATURE COMMENTS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-03-20 |
Time |
22:20 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-03-20 |
Time |
21:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2023-03-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-03-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-03-09 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2023-03-09 11:50:10 | FIRE PROVISO: | | | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-04-07 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-07 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-06 |
Time |
08:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-04-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-28 |
Time |
14:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-21 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-08 |
Time |
08:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-04-13 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-04-10 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2023-04-13 15:53:28 | NO IMPACT FEES DUE. LEM | | 2023-04-10 08:31:02 | EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-21 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-21 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2023-03-21 14:27:56 | 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-04-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-04 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-04 |
Time |
07:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-13 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-13 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2023-03-13 12:39:43 | 1ST REVIEW FMC | | | PERMIT: 23030346 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A SCOPE OF WORK FOR THE MECHANICAL SYSTEM. | | | IS THE SYSTEM BEING REPLACED? IS THE DUCTWORK BEING | | | REPLACED? | | | | | | 2) SHOW THE RETURN AIR PATH FROM THE ROOMS BACK TO THE | | | MECHANICAL SYSTEM. FMC 601.6 | | | | | | 3) IS THE KITCHEN HOOD DUCTED TO THE EXTERIOR? WHAT ARE | | | THE CFMS OF THE HOOD EXHAUST FAN? IF OVER 400 CFM | | | PROVIDE THE MAKE-UP AIR FOR THIS HOOD. FMC 505.2 | | | | | | 4) THE DESIGNER MUST DIGITALLY SIGN DIGITALLY SUBMITTED | | | DOCUMENTS. FS 471/481 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-04 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-04 |
Time |
12:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-10 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-10 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2023-03-10 16:14:45 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 23030346 | | | 3/10/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS A3 & P1: SHEET A3 SHOWS A STEAM GENERATOR IN | | | THE MASTER BATH. PLEASE PROVIDE A NOTE AND/OR DETAIL TO | | | INDICATE AN INLINE BACKFLOW PREVENTER WILL BE INSTALLED | | | ON THE WATER SUPPLY LINE TO THE UNIT- SEC. 608.3 FBC P. | | | A) TYPICAL STEAM GENERATORS HAVE DRAIN LINES. PLEASE | | | SHOW THE DRAIN LINE DISCHARGE LOCATION ON THE PLAN- | | | SEC. 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-04-07 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-07 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-07 |
Time |
08:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-03-29 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-29 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-29 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2023-03-29 14:35:00 | ONLY M1 AND P1 ARE DIGITALLY SIGNED AND SEALED THE REST | | | NEED TO BE UPLOADED WITH ORIGINAL-THOSE ARE COPIES OF A | | | SIGNED AND SEAL DOCUMENT. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-10 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-10 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2023-03-10 11:47:20 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23030346 | | | | | | REVIEWED: MARCH 10, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | 1) THE PLANS SHEETS FOR THE PROJECT AND NOT DIGITALLY | | | SIGNED BY THE ARCHITECT OF RECORD AS REQUIRED BY FL. | | | STATUTE AND SEC.: 61G1-16.005 FLORIDA ADMINISTRATIVE | | | CODE. PLANS TRANSMITTED ELECTRONICALLY SHALL BEAR | | | DIGITAL SIGNATURES AND SEALS CAPABLE OF BEING VERIFIED. | | | THE PLANS SUBMITTED FOR REVIEW ARE COPIES OF A SIGNED | | | AND SEALED PAPER PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|