Plan Review Details - Permit 23030340
Plan Review Stops For Permit 23030340
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-04-26 Cont ID  
Sent By jbrooks Date 2023-04-26 Time 10:47 Rev Time 0.00
Received By jbrooks Date 2023-04-26 Time 07:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-10 Cont ID  
Sent By jbrooks Date 2023-04-10 Time 14:27 Rev Time 0.00
Received By jbrooks Date 2023-04-10 Time 14:05 Sent To  
Notes
2023-04-10 14:28:06JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL41940
 COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECTED
 ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.2
 MECHANICALLY-ATTACHED BASE SHEET TABLE 4B ALLOWABLE
 DESIGN PRESSURES, 2-PLY UNDERLAYMENT SYSTEMS IN TILE
 ROOF APPLICATIONS SYSTEM NO. UDL-12 DO NOT MEET OR
 EXCEED THE MINIMUM DESIGN PRESSURE REQUIREMENTS FOR A
 HIP ROOF; (3:12 AND OVER) ROOF SLOPE; MEAN ROOF HEIGHT
 15 FT. MINIMUM DESIGN PRESSURE REQUIREMENT OF -115.5 IN
 AN EXPOSURE CATEGORY C AREA. PROVIDE UNDERLAYMENT
 SYSTEM THAT MEETS OR EXCEEDS THE ABOVE CRITERIA. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-27 Cont ID  
Sent By jbrooks Date 2023-03-27 Time 10:30 Rev Time 0.00
Received By jbrooks Date 2023-03-27 Time 07:40 Sent To  
Notes
2023-03-27 10:31:15JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL2346-R8 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT). TEST REPORT PAGES 1-3.
 INSTALLATION INSTRUCTIONS PAGES 1 & 2. THE TEST REPORTS
 AND INSTALLATION INSTRUCTIONS CAN BE PRINTED FROM THE
 SUMMARY OF PRODUCTS LOCATED AT THE BOTTOM OF THE COVER
 PAGE.
 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL5374-R6 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL4190 IS INCOMPLETE, PROVIDE THE FOLLOWING ADDITIONAL
 INFORMATION: COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS
 WILL INCLUDE THE CODE VERSION, PRODUCT APPROVAL NUMBER,
 STATUS, GENERAL INFORMATION ABOUT THE PRODUCT).
 4. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL41940
 (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF
 WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT
 CONSIDER USING FL41940 (NON-HVHZ).
 5. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL41940
 (NON- HVHZ) COVERS MULTIPLE PRODUCT TYPES; ROOF COVER
 OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS, ALLOWABLE SUBSTRATES, ATTACHMENT
 LIMITATIONS & INSTALLATION APPROVED ASSEMBLIES. SELECT
 ALL APPLICABLE OPTIONS INCLUDING ATTACHMENT LIMITATION
 SYSTEM USED FROM 5.8.3.1 DIRECT-TO-DECK TABLE 4A:
 ALLOWABLE DESIGN PRESSURES, DIRECT-TO-DECK UNDERLAYMENT
 IN TILE ROOF APPLICATIONS PAGE #4 & 5 OR ATTACHMENT
 LIMITATION SYSTEM FROM 5.8.3.2 MECHANICALLY-ATTACHED
 BASE SHEET TABLE 4B ALLOWABLE DESIGN PRESSURES, 2-PLY
 UNDERLAYMENT SYSTEMS IN TILE ROOF APPLICATIONS PAGES
 #6-9.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-26 Cont ID  
Sent By jbrooks Date 2023-04-26 Time 10:47 Rev Time 0.00
Received By jbrooks Date 2023-04-19 Time 08:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-10 Cont ID  
Sent By jbrooks Date 2023-04-10 Time 14:28 Rev Time 0.00
Received By jbrooks Date 2023-03-31 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-27 Cont ID  
Sent By jbrooks Date 2023-03-27 Time 10:31 Rev Time 0.00
Received By jbrooks Date 2023-03-24 Time 11:18 Sent To  
Notes
***NONE***