Plan Review Details - Permit 23030322
Plan Review Stops For Permit 23030322
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-07-03 Cont ID  
Sent By lbond Date 2023-07-03 Time 17:01 Rev Time 0.00
Received By lbond Date 2023-07-03 Time 17:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-14 Cont ID  
Sent By lbond Date 2023-06-14 Time 08:19 Rev Time 0.00
Received By lbond Date 2023-06-14 Time 08:19 Sent To  
Notes
2023-06-14 08:21:33FBC 107.2.1
 SCOPE OF WORK MUST BE CLEARLY DEFINED IN CONSTRUCTION
 DOCUMENTS PROVIDED
  
 COMPLY TO SIGNATURE COMMENTS AND RESPOND TO ALL OTHER
 TRADES COMMENTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-25 Cont ID  
Sent By lbond Date 2023-04-25 Time 11:42 Rev Time 0.00
Received By lbond Date 2023-04-25 Time 11:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-31 Cont ID  
Sent By lbond Date 2023-03-31 Time 10:41 Rev Time 0.00
Received By lbond Date 2023-03-31 Time 10:41 Sent To  
Notes
2023-03-31 10:42:56COMPLY TO ALL TRADES COMMENTS INCLUDING DIGITAL
 SIGNATURE AND SEAL ON OCRESSPONDING DOCUMENTS.

Review Stop E ELECTRICAL
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2023-07-07 Cont ID  
Sent By jleahy Date 2023-07-07 Time 15:41 Rev Time 0.00
Received By jleahy Date 2023-07-07 Time 15:28 Sent To  
Notes
2023-07-07 16:09:25FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SUBMIT A COST BREAKDOWN OF THE LABOR AND
 MATERIAL FOR THIS PROJECT. (50K) VALUE IS LOW FOR WORK
 SHOWN. FBC 109.3
  
 GLASS TEMPERING FURNACE IS TO BE LISTED BY A NATIONALLY
 RECOGNOZED TESTING LAB. 110.3

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2023-06-05 Cont ID  
Sent By jleahy Date 2023-06-05 Time 15:29 Rev Time 0.00
Received By jleahy Date 2023-06-05 Time 15:23 Sent To  
Notes
2023-06-05 15:31:02FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS ARE NOT SIGNED AND SEALED. 107.2.1
  
 PAGE E-03 DISCONNECT STILL SHOWS 1000A FUSES OR
 BREAKER.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By mpeterso Date 2023-04-19 Time 16:26 Rev Time 0.00
Received By mpeterso Date 2023-04-19 Time 15:07 Sent To  
Notes
2023-04-19 16:29:12ELECTRIC REVIEW FAILED
  
 1) OVERCURRENT PROTECTION DETAILED FOR FEEDER TO MDP2
 ARE REQUIRED TO BE RATED AT 125% OF THE CONTINUOUS
 LOAD, (915 X 1.25%= 1144 AMPERES) IN ACCORDANCE WITH
 NEC 215.3. THE RATING OF THIS DEVICE IS REQUIRED TO BE
 A MINIMUM RATING OF 1200 AMPS IN ACCORDANCE WITH THE
 STANDARD AMPERE RATINGS LISTED IN NEC 240.6(A). PLEASE
 CORRECT FEEDER OVERCURRENT PROTECTION SIZE AS
 APPLICABLE.
  
 2) FEEDER CONDUCTORS DETAILED FROM FPL TRANSFORMER TO
 MDS2 AND MDS2 TO MDP2 ARE DETAILED AS (3) SETS OF
 400MCM CONDUCTORS WITH A TOTAL AMPACITY OF 1005 AMPS.
 THE INDUSTRIAL PROCESS GLASS TEMPERING HEATER ARE
 REQUIRED TO BE CONSIDERED A CONTINUOUS LOAD IN
 ACCORDANCE WITH NEC 424.3(B). CONDUCTORS SUPPLYING
 CONTINUOUS LOADS IS REQUIRED TO BE RATED AT 125% OF THE
 LOAD SERVED IN ACCORDANCE WITH NEC 215.2(A)(1)(A). THE
 TOTAL LOAD FOR THE GLASS TEMPERING HEATER IS DETAILED
 AS 915 AMPS. MINIMUM CONDUCTOR AMPACITY REQUIRED IS 915
 X 1.25=1144 AMPS. NEC 424.3(B) NEC 215.2(A)(1)(A).
 IN ADDITION, ENSURE THE CONDUCTOR AMPACITY RATING IS
 EQUAL OR GREATER THAN THE OVERCURRENT DEVICE PROTECTING
 WITH A RATING OVER 800 AMPERES, IN ACCORDANCE WITH NEC
 240.4(C). PLEASE CORRECT FEEDER CONDUCTOR SIZE AS
 APPLICABLE.
  
 3) OVERCURRENT PROTECTION DETAILED AS 500 AMPERES FOR
 BRANCH CIRCUIT CONDUCTORS TO GLASS HEATERS 1 AND 2 ARE
 REQUIRED TO BE RATED AT 125% OF THE CONTINUOUS LOAD,
 (349 X 1.25%= 436 AMPERES) IN ACCORDANCE WITH NEC
 210.20(A)THE RATING OF THIS DEVICE IS REQUIRED TO BE A
 MINIMUM RATING OF 450 AMPS IN ACCORDANCE WITH THE
 STANDARD AMPERE RATINGS LISTED IN NEC 240.6(A) AND A
 MAXIMUM RATING OF 450 AMPERES IN ACCORDANCE WITH NEC
 670.4(C). PLEASE CORRECT BRANCH CIRCUIT OVERCURRENT
 PROTECTION SIZE AS APPLICABLE.
  
 4) BRANCH CIRCUIT CONDUCTORS DETAILED AS 500MCM TO
 GLASS HEATERS 1 AND 2 WITH AN AMPACITY OF 380 AMPERES.
 THE INDUSTRIAL PROCESS GLASS TEMPERING HEATERS 1 AND 2
 ARE REQUIRED TO BE CONSIDERED A CONTINUOUS LOAD IN
 ACCORDANCE WITH NEC 424.3(B). CONDUCTORS SUPPLYING
 CONTINUOUS LOADS IS REQUIRED TO BE RATED AT 125% OF THE
 LOAD SERVED IN ACCORDANCE WITH NEC 21O.19(A)(1)(A). THE
 TOTAL LOAD FOR EACH GLASS TEMPERING HEATER IS DETAILED
 AS 349 AMPS. MINIMUM CONDUCTOR AMPACITY REQUIRED IS 349
 X 1.25=436 AMPERES. PLEASE CORRECT BRANCH CIRCUIT
 CONDUCTOR SIZE AS APPLICABLE.
  
 5) BRANCH CIRCUIT CONDUCTORS DETAILED AS 4/0. THE
 LISTED ALLOWED AMPACITY OF 4/0 IS 230 AMPERES. THE
 BLOWER MOTOR IS REQUIRED TO BE CONSIDERED A CONTINUOUS
 LOAD IN ACCORDANCE WITH NEC 670.4(A). CONDUCTORS
 SUPPLYING CONTINUOUS LOADS ARE REQUIRED TO BE RATED AT
 125% OF THE LOAD SERVED IN ACCORDANCE WITH NEC
 670.4(A). THE TOTAL LOAD FOR THIS MOTOR IS DETAILED AS
 224 AMPERES. MINIMUM CONDUCTOR AMPACITY REQUIRED IS 224
 X 1.25=280 AMPERES. PLEASE CORRECT BRANCH CIRCUIT
 CONDUCTOR SIZE AS APPLICABLE.
  
 6) THE PANEL SCHEDULE FOR MDP2 LISTS THE CONTROL
 CIRCUIT AS HAVING A 100 AMPERE CIRCUIT BREAKER. THE
 CONDUCTOR SIZE IS LISTED AS A #8 CONDUCTOR. PLEASE
 CORRECT THE OVERCURRENT PROTECTION SIZE IN ACCORDANCE
 WITH NEC 240 REQUIREMENTS. PLEASE NOTE: SUBMITTAL OF
 ADDITIONAL AND/OR REVISED MATERIALS MAY RESULT IN NEW
 PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
 7) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACT OR,
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-03-09 Cont ID  
Sent By jleahy Date 2023-03-09 Time 16:21 Rev Time 0.00
Received By jleahy Date 2023-03-09 Time 14:54 Sent To  
Notes
2023-03-09 16:25:56FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED SPECS ON EQUIPMENT BEING INSTALLED, GAS FIRED?,
 ELECTRIC? EXHAUST SYSTEM? SPRINKLER SYSTEM REQUIRED?
  
 PLANS NEED TO BE SIGNED AND SEALED BY AN ENGINEER
  
  
 WHERE A BUILDING OR STRUCTURE IS SUPPLIED BY MORE THAN
 ONE SERVICE, OR ANY COMBINATION OF BRANCH CIRCUITS,
 FEEDERS, AND SERVICES, A PERMANENT PLAQUE OR DIRECTORY
 SHALL BE INSTALLED AT EACH SERVICE DISCONNECT LOCATION
 DENOTING ALL OTHER SERVICES
  
 F.S. 471.003 (H)???ANY ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL CONTRACTOR WHOSE
 PRACTICE INCLUDES THE DESIGN AND FABRICATION OF
 ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR MECHANICAL
 SYSTEMS, RESPECTIVELY, WHICH SHE OR HE INSTALLS BY
 VIRTUE OF A LICENSE ISSUED UNDER CHAPTER 489, UNDER
 1PART I OF CHAPTER 553, OR UNDER ANY SPECIAL ACT OR
 ORDINANCE WHEN WORKING ON ANY CONSTRUCTION PROJECT
 WHICH:
  
 1.???REQUIRES AN ELECTRICAL OR PLUMBING OR
 AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE
 OF $125,000 OR LESS; AND
  
 2.A .REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600
 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL
 SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A
 COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM;
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-07-03 Cont ID  
Sent By clfranci Date 2023-07-03 Time   Rev Time 0.00
Received By clfranci Date 2023-07-03 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-31 Cont ID  
Sent By pleduc Date 2023-05-31 Time   Rev Time 0.00
Received By pleduc Date 2023-05-31 Time 12:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-17 Cont ID  
Sent By pleduc Date 2023-04-17 Time   Rev Time 0.00
Received By pleduc Date 2023-04-17 Time 11:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-03-10 Cont ID  
Sent By pleduc Date 2023-03-10 Time   Rev Time 0.00
Received By pleduc Date 2023-03-10 Time 13:55 Sent To  
Notes
2023-03-10 14:00:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF A GLASS TEMPERING
 FURNANCE.
  
 THIS FURNACE APPEARS TO BE NEW EQUIPMENT THAT HAS NO
 PERMIT RECORD FOR LIFE AND FIRE SAFETY.
  
 PLEASE REVIEW YOUR RECORDS FOR A PERMIT # AND PROVIDE,
 OR CONTACT THE BUILDING DEPEARTMENT FOR THEIR PERMIT
 REQUIREMENTS.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
2023-03-09 16:38:48SENT THIS TO FIRE FOR REVIEW DUE TO NATURE OF
 EQUIPMENT. JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-26 Time 08:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-18 Cont ID  
Sent By cmontell Date 2023-07-18 Time 12:19 Rev Time 0.00
Received By cmontell Date 2023-07-18 Time 12:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-20 Cont ID  
Sent By cmontell Date 2023-06-20 Time 13:21 Rev Time 0.00
Received By cmontell Date 2023-06-20 Time 13:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-25 Cont ID  
Sent By lbond Date 2023-04-25 Time 11:43 Rev Time 0.00
Received By lbond Date 2023-04-14 Time 14:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-31 Cont ID  
Sent By lbond Date 2023-03-31 Time 10:43 Rev Time 0.00
Received By lbond Date 2023-03-08 Time 08:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-07-18 Cont ID  
Sent By cmontell Date 2023-07-18 Time 12:19 Rev Time 0.00
Received By cmontell Date 2023-07-18 Time 12:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-06-20 Cont ID  
Sent By cmontell Date 2023-06-20 Time 13:20 Rev Time 0.00
Received By cmontell Date 2023-06-20 Time 13:20 Sent To  
Notes
2023-06-20 13:21:31PLAN REVIEW FAIL
  
 1 THERE IS NOT ENOUGH INFORMATION SUBMITTED TO DO A
 MECHANICAL REVIEW. PLEASE SUBMIT A COMPLETE MECHANICAL
 DESIGN FOR THIS NEWLY ADDED FURNACE, INCLUDING A
 DRAWING OF THE BUILD, SITE PLAN, EXHAUST FOR THIS
 FURNACE, TYPE OF FUEL FOR THIS FURNACE AND A
 VENTILATION PLAN FOR THE COMBUSTION, MAKE-UP AIR AND
 EXHAUST AIR FOR THIS FURNACE. FBC 107.3.5.
  
 CHRIS MONTELLO
 561-805-6733
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-04-25 Cont ID  
Sent By medwards Date 2023-04-25 Time 11:32 Rev Time 0.00
Received By medwards Date 2023-04-25 Time 11:32 Sent To  
Notes
2023-04-25 11:36:322ND CYCLE REVIEW:
 RESPOND TO THE FIRST CYCLE REVIEW COMMENTS BELOW:
  
 1ST REVIEW FMC
 PERMIT: 23030322
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE IS NOT ENOUGH INFORMATION SUBMITTED TO DO A
 MECHANICAL REVIEW. PLEASE SUBMIT A COMPLETE MECHANICAL
 DESIGN FOR THIS NEWLY ADDED FURNACE, INCLUDING A
 DRAWING OF THE BUILD, SITE PLAN, EXHAUST FOR THIS
 FURNACE, TYPE OF FUEL FOR THIS FURNACE AND A
 VENTILATION PLAN FOR THE COMBUSTION, MAKE-UP AIR AND
 EXHAUST AIR FOR THIS FURNACE. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-13 Cont ID  
Sent By medwards Date 2023-03-13 Time 14:39 Rev Time 0.00
Received By medwards Date 2023-03-13 Time 14:39 Sent To  
Notes
2023-03-13 14:40:121ST REVIEW FMC
 PERMIT: 23030322
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE IS NOT ENOUGH INFORMATION SUBMITTED TO DO A
 MECHANICAL REVIEW. PLEASE SUBMIT A COMPLETE MECHANICAL
 DESIGN FOR THIS NEWLY ADDED FURNACE, INCLUDING A
 DRAWING OF THE BUILD, SITE PLAN, EXHAUST FOR THIS
 FURNACE, TYPE OF FUEL FOR THIS FURNACE AND A
 VENTILATION PLAN FOR THE COMBUSTION, MAKE-UP AIR AND
 EXHAUST AIR FOR THIS FURNACE. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-07-03 Cont ID  
Sent By lbond Date 2023-07-03 Time 17:05 Rev Time 0.00
Received By lbond Date 2023-07-03 Time 17:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-06-05 Cont ID  
Sent By jleahy Date 2023-06-05 Time 15:31 Rev Time 0.00
Received By jleahy Date 2023-06-05 Time 15:31 Sent To  
Notes
2023-06-05 15:32:00PLANS NOT SIGNED AND SEALED BY ENGINEER JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-17 Cont ID  
Sent By lbond Date 2023-04-17 Time 14:35 Rev Time 0.00
Received By lbond Date 2023-04-17 Time 14:35 Sent To  
Notes
2023-06-14 08:24:04PROVISO DOCUMENTS MUST BE DIGITALLY SIGNED AND SELAED
 BY ENGINEER
 CONTRACTOR NOT SUFFICIENT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-09 Cont ID  
Sent By jleahy Date 2023-03-09 Time 16:26 Rev Time 0.00
Received By jleahy Date 2023-03-09 Time 14:54 Sent To  
Notes
2023-03-09 16:32:41 
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 PLANS NEED TO BE SIGNED AND SEALED BY AN ENGINEEER.
 JLEAHY
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
  