| Plan Review Stops For Permit 23021524 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-05-03 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-05-03 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-05-03 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2023-05-03 08:42:22 | PLEASE REFER TO PREVIOUS COMMENT AND PROVIDE INFO IN | | | SUPPORTING DOCUMENT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-13 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-13 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2023-04-13 14:05:38 | PROVISO: PLEASE PROVIDE SHOP DRAWINGS OR ADDITIONAL | | | DETAIL ON SHEET A2.5 REGARDING THE NEW CABLE RAILING | | | THROUGHOUT. | | | PROVIDE NEW ELEVATOR FBC PRODUCT APPROVAL OR DIFFER | | | UNDER SEPERATE PERMIT. | | | IF YOU HAVE ANY QUESTIONS OR CONCERN YOU CAN REACH ME | | | AT: | | | | | | | | | | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-05-10 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-05-10 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-05-10 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2023-05-10 16:20:45 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW | | | | | | 1. LOW VOLTAGE WIRING REQUIRES A SEPARATE PERMIT | | | APPLICATION. | | | | | | END OF COMMENTS | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | | 561-805-6738 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-04-17 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-04-17 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2023-04-17 11:56:08 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON | | | MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN | | | ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315 | | | | | | 2. AT LEAST ONE 120-VOLT, 20-AMPERE BRANCH CIRCUIT | | | SHALL BE INSTALLED TO SUPPLY RECEPTACLE OUTLETS IN | | | ATTACHED GARAGES AND IN DETACHED GARAGES WITH ELECTRIC | | | POWER. THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS AS PER | | | NEC 210.11(C)(4) | | | | | | 3. INFORMATION PROVIDED ON PAGE 018 E1 ELECTRICAL PLAN | | | (ELECTRICAL RISER DIAGRAM) DOES NOT MATCH THE | | | INFORMATION ON PAGE 019 UE1 UNIT ELECTRICAL (ELECTRICAL | | | RISER). | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-05-11 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-05-11 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-05-02 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-18 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-12 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-05-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-08 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-05-08 |
Time |
08:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-18 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-18 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2023-04-18 14:25:38 | PROVIDE A COMPLETE SCOPE OF WORK FOR THE MECHANICAL | | | SYSTEMS FOR THIS TOWNHOME.THIS WOULD INCLUDE THE SPECS | | | ON THE KITCHEN RANGE AND THE EXHAUST HOOD. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-05-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-05-03 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-05-03 |
Time |
08:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-13 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-13 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2023-04-13 16:52:31 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23021524 | | | 4/13/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A PLUMBING PLAN INCLUDING A WRITTEN | | | SCOPE OF WORK AND PLUMBING RISER DRAWINGS- SEC. 107.2.1 | | | & 107.3.5.2 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-05-03 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-05-03 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-05-03 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2023-05-03 08:37:38 | PLUMBING PLAN PASSED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-04-13 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-04-13 |
Time |
13:45 |
Sent To |
|
|
| Notes |
|
|